What the takeoff said: Read from 000-Copy of Drawings.pdf, page 19. No usable text layer (203 chars; text outlined), read from renders at 60-200 dpi. No responsibility matrix, no equipment schedule, no LV plan, no strut/rod/support details, no demolition. Electrical items drawn: North elev. 1 wall-mounted light fixture at +9'-0" A.F.G. (leader 'WALL MOUNTED LIGHT FIXTURE, SEE ELEC. DWGS. (TYP.)'); West elev. 1 wall-mounted light fixture at +9'-0" A.F.G. (same leader); North elev. leader 'LINE OF ELEC. MAIN SWITCHBOARD CABINET, SEE ELEC. DWGS.'. The two small circles at +10'-0" A.F.F. on the West elevation are the overflow drains ('OVERFLOW DRAIN, SEE GENERAL NOTES #8 (TYP. OF 2)'), not electrical. The wall fixtures are the exterior sconces counted on E4.0 (type C, L-0003) and the MSB is taken off on E1.1/E5.0, so per the rules nothing is re-taken here: no lines, no marks file.