What the takeoff said: Read from 000-Copy of 2024.11.28_INT_US_CA_Roseville_Galleria at Roseville_LL PERMIT BID SET_FULL.pdf, page 35 (Peter A. Leptuch PE / Engineering & Consulting Services, 3/8"=1'-0"). The sheet draws VAV-1 (keyed note 1), EDH-1 duct heater (kn 7) just downstream of VAV-1 in the 16"x14" supply main, thermostat T at 48" AFF on the corridor/BOH wall (kn 4), remote sensor S at 60" AFF on the sales-area north wall (kn 5) and Young regulators at dampers above gyp ceiling (kn 6, manual, no power). Every electrical item here is already counted on E3.0 (L-0010/L-0011 VAV-1 motor-rated switch + J-box; L-0012/L-0013 EDH-1 30/3/15A fused disconnect + hardwire; L-0016/L-0017 thermostat/sensor J-boxes + 1/2" EMT with pull string; L-0026/L-0027 EDH-1 branch), so no line is re-taken. No equipment schedule, no responsibility matrix, no strut/support detail and no demolition on this sheet; no equipment file and no marks file written.