Derived from what the read produced, so none of it can drift from the data behind it. A blocker stops a price being presented as complete; it never stops you looking. These definitions are this build’s own — no RRE document specifies them yet.
| Check | Status | What the check found |
|---|---|---|
| Sheet scale | pass | All 1 plan sheet(s) carry a scale, so measurement is available. The other 8 read sheet(s) are specifications, schedules and details — nothing is measured on them, so a scale on one is not needed and a scale missing from one is not a gap. |
| Sheets read for scope | warning | 24 sheet(s) were indexed but not read for scope: A000, AS02, A002, A002.1, A002.2, A002.3, D101, D103, D104, D105, D106, A103, A104, A203, A212, A304, M3.0, M5.0, S101, S201, ST0, 001-rocklinelectric.net-Mail---Fwd_-INVITATION-TO-BID---Intimissimi---Roseville-CA-p1, 001-rocklinelectric.net-Mail---Fwd_-INVITATION-TO-BID---Intimissimi---Roseville-CA-p2, 001-rocklinelectric.net-Mail---Fwd_-INVITATION-TO-BID---Intimissimi---Roseville-CA-p3. Looked at by the takeoff and not read: no electrical work on it. Read them, or state the omission on the proposal — the basis of the offer already prints it. |
| Symbol source | warning | No symbol library was found on the drawings, and no engineering firm was identified from the title blocks, so there is no conventions file to fall back on either. This set is read against the default library alone: NECA 100-2006. It is the firm's baseline for what a symbol MEANS where a legend is silent, ambiguous or absent, and it is also the checklist of which symbol categories a plan of this kind ought to show. A line named from the baseline rather than from a legend is named by convention, not by the set. It is reported as 'named from NECA 100, confirm' and carries a semantic-risk flag — a misread convention is a 3× error that no percentage band expresses. Confirm a sample of the named groups on the drawing. Nothing is blocked by this — a default library reads most sets correctly — but a name taken from one is an assumption, and the proposal states it as such. |
| Symbols named | pass | All 364 marks belong to a named group. |
| Every line prices | pass | Every line points at an assembly. |
| Plan and schedule agree | pass | No line has a plan/schedule disagreement. |
| Lines accepted by a person | pass | All 102 eligible line(s) accepted. |
| Engineer conventions known | pass | No engineer-dependent lines. |
| Unsure flags resolved | pass | The model raised no open flags. |
| Cover sheet read | pass | A cover sheet was found and read; its notes parameterise every later pass. |
What the symbol names rest on. No symbol library was found on the drawings, so these names come from NECA 100-2006 rather than from this engineer’s own legend. Confirming a sample on the drawing is worth more here than anywhere else, and each correction is recorded as evidence for the next job.
Edition: 2025 California Electrical Code, because in force for permits from 2026-01-01, as of the bid date 2026-09-29. City and county amendments are the AHJ’s: check them on any job inside a city that amends the code. “To check” means the code requires it and the drawings do not show it: send an RFI, or make the call. Nothing here is added to the bid on its own.
| Section | Status | What the code requires | What the takeoff shows | RRE’s practice |
|---|---|---|---|---|
NEC 2023 250.30 Grounding a transformer (separately derived system) | to check | A transformer secondary is grounded as a separately derived system: a system bonding jumper, a grounding electrode conductor to an electrode, and the supply-side bonding jumper sized from 250.102. | In play for FEEDER WIRE #1 THWN CU (30 KVA XFMR SECONDARY TO PANEL L); FEEDER WIRE #6 THWN CU (PANEL H TO 30 KVA XFMR PRIMARY); GROUND WIRE #10 THWN CU (PANEL H TO XFMR); and 6 more. Nothing on the takeoff shows it. | — |
NEC 2023 300.21 Firestopping at rated penetrations | to check | Electrical penetrations of fire-resistance-rated walls, partitions, floors or ceilings firestopped by an approved method that keeps the rating. | In play for TENMAT FIRE-RATED COVER OVER RECESSED DOWNLIGHT. Nothing on the takeoff shows it. | — |
NEC 2023 406.12 Tamper-resistant receptacles | to check | Tamper-resistant 15- and 20-ampere, 125- and 250-volt receptacles in dwellings, guest rooms and dormitories, child care, preschools and schools, business offices, corridors, waiting rooms, clinics, medical and dental offices, outpatient facilities, assembly occupancies and the other areas the section lists. | In play for DUPLEX RECEPTACLE 20A 125V, WALL. Nothing on the takeoff shows it. |
The RRE item carries no price for the part named, so the estimate has the install labor and rough-in only, and the vendor or sub prices the rest. Send the lighting and gear lists from Material list & vendor quotes.
| Line | Needs a price for | Count | Sheet |
|---|---|---|---|
LIGHT FIXTURE TYPE EM Isolite LMIGN-EM ceiling recessed emergency light 6W, CFCI, unswitched leg (kn 1 / gen e) | LED EMERGENCYLIGHT DUAL | 6 ea | E2.0 |
LIGHT FIXTURE TYPE N Exitronix 902E recessed wall exit sign 5W (sales), CFCI, unswitched leg (kn 1) | LED GRN EXIT FIXTURE | 1 ea | E2.0 |
LIGHT FIXTURE TYPE EX Exitronix GVEX exit sign w/ 90-min battery (BOH), CFCI, unswitched leg | LED GRN EXIT FIXTURE | 1 ea | E2.0 |
| Line | Needs a price for | Count | Sheet |
|---|---|---|---|
PANELBOARD 100A MCB 120/208V 3PH 4W 42 CIRCUIT SURFACE NEMA 1 10KAIC (PANEL L) New Panel L, 42 circuit positions | 100/28 120/208V PNL 3PH | 1 ea | E4.1 |
18 lines the reader wrote at zero are not listed: they add nothing to the bid.
Nothing in this tab.
| — |
NEC 2023 110.16 Arc-flash warning label on gear | shown | Switchboards, switchgear, panelboards, meter socket enclosures and motor control centers likely to be worked on energized carry a field- or factory-applied arc-flash hazard warning. | In play for PANEL DIRECTORIES / CIRCUIT IDENTIFICATION; PANELBOARD 100A MCB 277/480V 3PH 4W SURFACE NEMA 1 22KAIC (PANEL H); PANELBOARD 100A MCB 120/208V 3PH 4W 42 CIRCUIT SURFACE NEMA 1 10KAIC (PANEL L). Shown: ENGRAVED PHENOLIC NAMEPLATE, BLACK/WHITE (spec nameplates 1.1, 3.10). | RRE carries phenolic nameplates and labels as their own item where the set calls for them. |
NEC 2023 210.62 Receptacles in show windows | shown | At least one 125-volt receptacle within 18 in. of the top of a show window for each 12 linear ft of show window. | In play for DUPLEX RECEPTACLE 20A, SHOW WINDOW (kn 2). Shown: DUPLEX RECEPTACLE 20A, SHOW WINDOW (kn 2). | — |
NEC 2023 300.11, 410.36(B) Support in suspended ceilings | shown | Raceways, cables and boxes above a suspended ceiling are supported independently of the ceiling grid, or by identified support wires; lay-in luminaires are fastened to the grid framing. | In play for #12 GA SUPPLEMENTAL HANGER WIRE AT EACH CORNER OF 2x2 LAY-IN FIXTURE, ACT GRID TO STRUCTURE, 3 TIGHT TURNS IN 3" (fixture <= 20 lb); LIGHT FIXTURE SEISMIC SUPPORT WIRE, #12 GALV. STEEL, TIED TO STRUCTURE, DIAGONAL OPPOSED CORNERS, 2x2 LAY-IN FIXTURE IN T-BAR (ACT) CEILING; LIGHT FIXTURE TYPE B; and 1 more. Shown: 1-5/8" STRUT CHANNEL, TRAPEZE HANGER CROSSMEMBERS ON 3/8" ALL-THREAD PAIRS FROM STRUCTURE (spec raceway 1.9); #12 GA SEISMIC SAFETY WIRE, RECESSED FIXTURE TO STRUCTURE, 3 TURNS IN 1-1/2" EACH END, W/ 3/8" EXPANSION ANCHOR OR TIE-OFF AT STRUCTURE (1 per fixture < 10 lb, gyp ceiling); #12 GA SUPPLEMENTAL HANGER WIRE AT EACH CORNER OF 2x2 LAY-IN FIXTURE, ACT GRID TO STRUCTURE, 3 TIGHT TURNS IN 3" (fixture <= 20 lb); and 1 more. | RRE carries the fixture support wire as its own item where the ceiling is a grid. |
NEC 2023 408.4(A) Circuit directory at every panel | shown | Every circuit and circuit modification legibly identified as to its clear, evident and specific purpose on a circuit directory at the panel. | In play for PANEL DIRECTORIES / CIRCUIT IDENTIFICATION; PANELBOARD 100A MCB 277/480V 3PH 4W SURFACE NEMA 1 22KAIC (PANEL H); PANELBOARD 100A MCB 120/208V 3PH 4W 42 CIRCUIT SURFACE NEMA 1 10KAIC (PANEL L). Shown: PANEL DIRECTORIES / CIRCUIT IDENTIFICATION. | RRE carries a panel directory update where circuits land in an existing panel. |
NEC 2023 422.31, 424.19, 430.102 Disconnect for water heaters, heaters, fans and motor loads | shown | A disconnect within sight of the appliance, heater or motor, or a branch-circuit breaker that can be locked in the open position. | In play for ENGRAVED PHENOLIC NAMEPLATE, BLACK/WHITE (spec nameplates 1.1, 3.10); FUSED DISCONNECT SWITCH 30A 3-POLE 240V NEMA 1 WITH (3) 15A FUSES (EDH-1); MOTOR RATED SWITCH 1-POLE 20A 120V NEMA 1 (VAV-1 DISCONNECT); and 1 more. Shown: 3/4" EMT, EDH-1 BRANCH L-37/39/41 (kn 13); ENGRAVED PHENOLIC NAMEPLATE, BLACK/WHITE (spec nameplates 1.1, 3.10); EQUIPMENT CONNECTION 6 FT 3/4" LIQUID-TIGHT FLEX WHIP (EDH-1, VAV-1); and 2 more. | A lockable breaker answers it as well as a switch: check the panel schedule before adding a disconnect. |
NEC 2023 450.3(B) Transformer overcurrent protection | shown | Primary (and where used, secondary) overcurrent protection for each transformer within the percentages of Table 450.3(B), and the secondary conductors protected per 240.21(C). | In play for FEEDER WIRE #1 THWN CU (30 KVA XFMR SECONDARY TO PANEL L); FEEDER WIRE #6 THWN CU (PANEL H TO 30 KVA XFMR PRIMARY); GROUND WIRE #10 THWN CU (PANEL H TO XFMR); and 6 more. Shown: FEEDER WIRE #1 THWN CU (30 KVA XFMR SECONDARY TO PANEL L); FEEDER WIRE #6 THWN CU (PANEL H TO 30 KVA XFMR PRIMARY); 3/4" EMT CONDUIT (PANEL H TO XFMR PRIMARY); and 4 more. | — |
NEC 2023 600.5(A) Sign outlet at each tenant entrance | shown | At least one outlet at each entrance to each tenant space accessible to pedestrians, for a sign, on a 20-ampere branch circuit that supplies no other load. | Shown: ENGRAVED PHENOLIC NAMEPLATE, BLACK/WHITE (spec nameplates 1.1, 3.10); SIGN DISCONNECT SWITCH 20A 1-POLE 120V (STOREFRONT SIGN, AS REQUIRED); JUNCTION BOX, STOREFRONT SIGN +145" AFF (kn 16). | RRE prices "power to building signage" where the set shows it; the matrix row is left blank where it does not. |
NEC 2023 600.6 Disconnect within sight of a sign | shown | Each sign or outline lighting system, or its feeder, has an externally operable disconnect within sight of the sign, or one capable of being locked in the open position. | In play for ENGRAVED PHENOLIC NAMEPLATE, BLACK/WHITE (spec nameplates 1.1, 3.10); SIGN DISCONNECT SWITCH 20A 1-POLE 120V (STOREFRONT SIGN, AS REQUIRED); JUNCTION BOX, STOREFRONT SIGN +145" AFF (kn 16). Shown: 3/4" EMT, EDH-1 BRANCH L-37/39/41 (kn 13); ENGRAVED PHENOLIC NAMEPLATE, BLACK/WHITE (spec nameplates 1.1, 3.10); EQUIPMENT CONNECTION 6 FT 3/4" LIQUID-TIGHT FLEX WHIP (EDH-1, VAV-1); and 3 more. | RRE prices a WP switch at signage as a fused disconnect assembly (firm practice wp_switch_mapping). |
A takeoff cannot settle every article: load calculations and coordination are the engineer of record’s, and workmanship is the inspector’s. Each is listed so nothing is silently skipped. “Waiting on a code read” means the article is in play and this job’s drawing read has not been checked against the code yet: re-run the read, or check it on the drawings.
| 90 | Introduction | general | Scope and definitions: nothing to check on a job. |
| 100 | Definitions | general | Scope and definitions: nothing to check on a job. |
| 110 | Requirements for Electrical Installations | checked | 1 section checked against the takeoff, all shown. |
| 200 | Use and Identification of Grounded Conductors | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 210 | Branch Circuits | checked | 1 section checked against the takeoff, all shown. |
| 215 | Feeders | checked | In play; none of its checked sections applies to these lines. |
| 220 | Branch-Circuit, Feeder, and Service Load Calculations | design | The engineer of record’s: sizing, calculation or coordination, not checked against a takeoff. |
| 225 | Outside Branch Circuits and Feeders | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 230 | Services | checked | In play; none of its checked sections applies to these lines. |
| 235 | Branch Circuits, Feeders, and Services Over 1000 Volts ac, 1500 Volts dc | not in play | Nothing on this takeoff puts it in play. |
| 240 | Overcurrent Protection | checked | In play; none of its checked sections applies to these lines. |
| 242 | Overvoltage Protection | not in play | Nothing on this takeoff puts it in play. |
| 245 | Overcurrent Protection for Systems Rated Over 1000 Volts ac, 1500 Volts dc | not in play | Nothing on this takeoff puts it in play. |
| 250 | Grounding and Bonding | to check | 1 section checked against the takeoff, 1 to check: 250.30. |
| 300 | General Requirements for Wiring Methods and Materials | to check | 2 sections checked against the takeoff, 1 to check: 300.21. |
| 305 | General Requirements for Wiring Methods and Materials for Systems Rated Over 1000 Volts ac, 1500 Volts dc | not in play | Nothing on this takeoff puts it in play. |
| 310 | Conductors for General Wiring | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 312 | Cabinets, Cutout Boxes, and Meter Socket Enclosures | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 314 | Outlet, Device, Pull, and Junction Boxes; Conduit Bodies; Fittings; and Handhole Enclosures | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 315 | Medium Voltage Conductors, Cable, Cable Joints, and Cable Terminations | not in play | Nothing on this takeoff puts it in play. |
| 320 | Armored Cable: Type AC | not in play | Nothing on this takeoff puts it in play. |
| 322 | Flat Cable Assemblies: Type FC | not in play | Nothing on this takeoff puts it in play. |
| 324 | Flat Conductor Cable: Type FCC | not in play |
| 400 | Flexible Cords and Flexible Cables | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 402 | Fixture Wires | not in play | Nothing on this takeoff puts it in play. |
| 404 | Switches | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 406 | Receptacles, Cord Connectors, and Attachment Plugs (Caps) | to check | 1 section checked against the takeoff, 1 to check: 406.12. |
| 408 | Switchboards, Switchgear, and Panelboards | checked | 1 section checked against the takeoff, all shown. |
| 409 | Industrial Control Panels | not in play | Nothing on this takeoff puts it in play. |
| 410 | Luminaires, Lampholders, and Lamps | checked | In play; none of its checked sections applies to these lines. |
| 411 | Low-Voltage Lighting | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 422 | Appliances | checked | 1 section checked against the takeoff, all shown. |
| 424 | Fixed Electric Space-Heating Equipment |
| 500 | Hazardous (Classified) Locations, Classes I, II, and III, Divisions 1 and 2 | not in play | Nothing on this takeoff puts it in play. |
| 501 | Class I Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 502 | Class II Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 503 | Class III Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 504 | Intrinsically Safe Systems | not in play | Nothing on this takeoff puts it in play. |
| 505 | Zone 0, 1, and 2 Locations | not in play | Nothing on this takeoff puts it in play. |
| 506 | Zone 20, 21, and 22 Locations for Combustible Dusts or Ignitible Fibers/Flyings | not in play | Nothing on this takeoff puts it in play. |
| 510 | Hazardous (Classified) Locations — Specific | not in play | Nothing on this takeoff puts it in play. |
| 511 | Commercial Garages, Repair and Storage | not in play | Nothing on this takeoff puts it in play. |
| 513 | Aircraft Hangars | not in play |
| 600 | Electric Signs and Outline Lighting | checked | 2 sections checked against the takeoff, all shown. |
| 604 | Manufactured Wiring Systems | not in play | Nothing on this takeoff puts it in play. |
| 605 | Office Furnishings | not in play | Nothing on this takeoff puts it in play. |
| 610 | Cranes and Hoists | not in play | Nothing on this takeoff puts it in play. |
| 620 | Elevators, Dumbwaiters, Escalators, Moving Walks, Platform Lifts, and Stairway Chairlifts | not in play | Nothing on this takeoff puts it in play. |
| 625 | Electric Vehicle Power Transfer System | not in play | Nothing on this takeoff puts it in play. |
| 626 | Electrified Truck Parking Spaces | not in play | Nothing on this takeoff puts it in play. |
| 630 | Electric Welders | not in play | Nothing on this takeoff puts it in play. |
| 640 | Audio Signal Processing, Amplification, and Reproduction Equipment | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 645 | Information Technology Equipment |
| 700 | Emergency Systems | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 701 | Legally Required Standby Systems | not in play | Nothing on this takeoff puts it in play. |
| 702 | Optional Standby Systems | not in play | Nothing on this takeoff puts it in play. |
| 705 | Interconnected Electric Power Production Sources | not in play | Nothing on this takeoff puts it in play. |
| 706 | Energy Storage Systems | not in play | Nothing on this takeoff puts it in play. |
| 708 | Critical Operations Power Systems (COPS) | not in play | Nothing on this takeoff puts it in play. |
| 710 | Stand-Alone Systems | not in play | Nothing on this takeoff puts it in play. |
| 712 | Direct Current Microgrids | not in play | Nothing on this takeoff puts it in play. |
| 722 | Cables for Power-Limited Circuits and Fault-Managed Power Circuits | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 724 | Class 1 Power-Limited Circuits and Class 1 Power-Limited Remote-Control and Signaling Circuits |
| 800 | General Requirements for Communications Systems | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 805 | Communications Circuits | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 810 | Radio and Television Antenna Equipment | not in play | Nothing on this takeoff puts it in play. |
| 820 | Community Antenna Television and Radio Distribution Systems | not in play | Nothing on this takeoff puts it in play. |
| 830 | Network-Powered Broadband Communications Systems | not in play | Nothing on this takeoff puts it in play. |
| 840 | Premises-Powered Broadband Communications Systems | not in play | Nothing on this takeoff puts it in play. |
| Ch. 9 | Tables: conduit fill, conductor properties, power-limited sources | checked | In play; none of its checked sections applies to these lines. |
| Line |
|---|
| Needs a price for |
|---|
| Count |
|---|
| Sheet |
|---|
TIME CLOCK 24 HR / 7 DAY ASTRONOMICAL (INTERMATIC ET91215CR OR EQUAL) TC1 Controls L-1,3,5,7,9,13,15,17,21 (REM TC) + 3 spares | 208/277V 24HR DPST 40A | 1 ea | E4.0 |
TIME CLOCK SET-UP AND PROGRAMMING - TC1 Intermatic ET91215CR astronomical time clock, 0-2 hr storefront override Set all time clocks per the owner's representative at turnover (AS01 Turnover Requirements 5); thermostats in the same note are the mechanical contractor's. | 208/277V 24HR DPST 40A | 1 ea | A101 |
Read off the schedules and notes. RRE buys none of the material named here. Check each against the responsibility matrix on the proposal: these are what it should say is by others.
| Line | Furnished by | Installed by | RRE’s part | Sheet |
|---|---|---|---|---|
LIGHT FIXTURE AIMING / DIRECTIONAL ADJUSTMENT, TRACK SPOTLIGHT TYPE T (KR103) AND RECESSED TYPE A (SLDRT), AS DIRECTED BY OWNER PM The drawings say “by owner”. | Owner | not stated | RRE installs / connects only | A101 |
LIGHT FIXTURE TYPE T The drawings say “owner furnished”. | Owner | not stated | RRE installs / connects only | E2.0 |
1-1/2" CONDUIT IN SLAB TRENCH, (7) RUNS, BOH WALL TO CASH DESK STUB-UP (horizontal in-slab run only) The drawings say “by gc”. | GC | not stated | RRE installs / connects only | A101 |
LED STRIP LIGHT, WARM WHITE, CONCEALED AROUND OVAL MIRROR PERIMETER (OM detail) The drawings say “owner-furnished”. | Owner | not stated | RRE installs / connects only | A213 |
LIGHT FIXTURE TYPE A The drawings say “owner furnished”. | Owner | not stated | RRE installs / connects only | E2.0 |
SAFE-OFF EXISTING ELECTRICAL (TI) RRE carries the line; the read says “removal is by others”. | Others | not stated | RRE carries it; a part is by others | A101 |
DOUBLE DUPLEX (QUAD) RECEPTACLE 20A The drawings say “by gc”. | GC | not stated | RRE installs / connects only | E3.0 |
DATA OUTLET POSITION, WALL (video wall +85" AFF, storefront) The drawings say “by gc”. | GC | not stated | RRE installs / connects only | E3.0 |
TRACK, 3-CIRCUIT 120V SURFACE (Quattrobi XTS) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | Owner | not stated | Struck: not in this bid | E2.0 |
16/2 CMR 0-10V DIMMING CABLE (TYPE B / BE 2x2 LED PANEL, LITHONIA CPX ...ZT 0-10V DRIVER), IN LIGHTING EMT Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E1.0 |
CIRCUIT BREAKER 20A 1-POLE 120V BOLT-ON (PANEL L) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E4.1 |
CIRCUIT BREAKER 20A 1-POLE 277V BOLT-ON (PANEL H SPARES) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E4.1 |
GROUNDING ELECTRODE CONDUCTOR #6 CU BARE (XFMR SEPARATELY DERIVED SYSTEM) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E4.0 |
TEMPORARY POWER AND LIGHTING FOR CONSTRUCTION Struck by House rule (RRE lead estimator practice): Not in this bid: RRE’s lead estimator carries no temporary power (none on his last three estimates, and on earlier ones none even where the specs gave it to the EC). Put it back if this job needs it. | — | not stated | Struck: not in this bid | E5.0 |
CIRCUIT BREAKER 50A 3-POLE 480V BOLT-ON (PANEL H) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E4.1 |
CIRCUIT BREAKER 15A 3-POLE 208V BOLT-ON (PANEL L, EDH-1) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E4.1 |
BREAKER HANDLE TIE (PANEL L POS COUNTER L-6/8/10/12) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E4.1 |
TIE-IN AT EXISTING LANDLORD SWITCHBOARD 100A CB (EXISTING BREAKER, NO NEW GEAR) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E4.0 |
#6 BARE CU GROUNDING ELECTRODE CONDUCTOR - 30 KVA XFMR (SEPARATELY DERIVED) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E4.0 |
CIRCUIT BREAKER 50A 3P 480V BOLT-ON, 22 KAIC (PANEL H) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E4.1 |
CIRCUIT BREAKER 20A 1P 277V BOLT-ON, 22 KAIC (PANEL H, SPARE) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E4.1 |
CIRCUIT BREAKER 20A 1P 120/208V BOLT-ON, 10 KAIC (PANEL L) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E4.1 |
CIRCUIT BREAKER 15A 3P 208V BOLT-ON, 10 KAIC (PANEL L, EDH-1) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E4.1 |
BREAKER HANDLE TIE, 1P BOLT-ON (PANEL L POS COUNTER CKTS 6,8,10,12) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E4.1 |
TEMPORARY POWER AND LIGHTING FOR CONSTRUCTION (EC scope, spec 5.1g) Struck by House rule (RRE lead estimator practice): Not in this bid: RRE’s lead estimator carries no temporary power (none on his last three estimates, and on earlier ones none even where the specs gave it to the EC). Put it back if this job needs it. | — | not stated | Struck: not in this bid | E5.0 |
TEMPORARY POWER AND LIGHTING FOR CONSTRUCTION - tenant space #111, 1231 sf, from new Panel L / LL source Struck by House rule (RRE lead estimator practice): Not in this bid: RRE’s lead estimator carries no temporary power (none on his last three estimates, and on earlier ones none even where the specs gave it to the EC). Put it back if this job needs it. | — | not stated | Struck: not in this bid | A101 |
EQUIPMENT CONNECTION - VAV-1 Titus AESV VAV box, 120V 1-phase, factory control transformer and power fuse, above ceiling Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | A101 |
| Nothing on this takeoff puts it in play. |
| 326 | Integrated Gas Spacer Cable: Type IGS | not in play | Nothing on this takeoff puts it in play. |
| 330 | Metal-Clad Cable: Type MC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 332 | Mineral-Insulated, Metal-Sheathed Cable: Type MI | not in play | Nothing on this takeoff puts it in play. |
| 334 | Nonmetallic-Sheathed Cable: Types NM and NMC | not in play | Nothing on this takeoff puts it in play. |
| 335 | Instrumentation Tray Cable: Type ITC | not in play | Nothing on this takeoff puts it in play. |
| 336 | Power and Control Tray Cable: Type TC | not in play | Nothing on this takeoff puts it in play. |
| 337 | Type P Cable | not in play | Nothing on this takeoff puts it in play. |
| 338 | Service-Entrance Cable: Types SE and USE | not in play | Nothing on this takeoff puts it in play. |
| 340 | Underground Feeder and Branch-Circuit Cable: Type UF | not in play | Nothing on this takeoff puts it in play. |
| 342 | Intermediate Metal Conduit: Type IMC | not in play | Nothing on this takeoff puts it in play. |
| 344 | Rigid Metal Conduit: Type RMC | not in play | Nothing on this takeoff puts it in play. |
| 348 | Flexible Metal Conduit: Type FMC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 350 | Liquidtight Flexible Metal Conduit: Type LFMC | not in play | Nothing on this takeoff puts it in play. |
| 352 | Rigid Polyvinyl Chloride Conduit: Type PVC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 353 | High Density Polyethylene Conduit: Type HDPE Conduit | not in play | Nothing on this takeoff puts it in play. |
| 354 | Nonmetallic Underground Conduit with Conductors: Type NUCC | not in play | Nothing on this takeoff puts it in play. |
| 355 | Reinforced Thermosetting Resin Conduit: Type RTRC | not in play | Nothing on this takeoff puts it in play. |
| 356 | Liquidtight Flexible Nonmetallic Conduit: Type LFNC | not in play | Nothing on this takeoff puts it in play. |
| 358 | Electrical Metallic Tubing: Type EMT | checked | In play; none of its checked sections applies to these lines. |
| 360 | Flexible Metallic Tubing: Type FMT | not in play | Nothing on this takeoff puts it in play. |
| 362 | Electrical Nonmetallic Tubing: Type ENT | not in play | Nothing on this takeoff puts it in play. |
| 366 | Auxiliary Gutters | not in play | Nothing on this takeoff puts it in play. |
| 368 | Busways | not in play | Nothing on this takeoff puts it in play. |
| 369 | Insulated Bus Pipe (IBP)/Tubular Covered Conductors (TCC) Systems | not in play | Nothing on this takeoff puts it in play. |
| 370 | Cablebus | not in play | Nothing on this takeoff puts it in play. |
| 371 | Flexible Bus Systems | not in play | Nothing on this takeoff puts it in play. |
| 372 | Cellular Concrete Floor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 374 | Cellular Metal Floor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 376 | Metal Wireways | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 378 | Nonmetallic Wireways | not in play | Nothing on this takeoff puts it in play. |
| 380 | Multioutlet Assembly | not in play | Nothing on this takeoff puts it in play. |
| 382 | Nonmetallic Extensions | not in play | Nothing on this takeoff puts it in play. |
| 384 | Strut-Type Channel Raceway | not in play | Nothing on this takeoff puts it in play. |
| 386 | Surface Metal Raceways | not in play | Nothing on this takeoff puts it in play. |
| 388 | Surface Nonmetallic Raceways | not in play | Nothing on this takeoff puts it in play. |
| 390 | Underfloor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 392 | Cable Trays | not in play | Nothing on this takeoff puts it in play. |
| 393 | Low-Voltage Suspended Ceiling Power Distribution Systems | not in play | Nothing on this takeoff puts it in play. |
| 394 | Concealed Knob-and-Tube Wiring | not in play | Nothing on this takeoff puts it in play. |
| 395 | Outdoor Overhead Conductors over 1000 Volts | not in play | Nothing on this takeoff puts it in play. |
| 396 | Messenger-Supported Wiring | not in play | Nothing on this takeoff puts it in play. |
| 398 | Open Wiring on Insulators | not in play | Nothing on this takeoff puts it in play. |
| checked |
| In play; none of its checked sections applies to these lines. |
| 425 | Fixed Resistance and Electrode Industrial Process Heating Equipment | not in play | Nothing on this takeoff puts it in play. |
| 426 | Fixed Outdoor Electric Deicing and Snow-Melting Equipment | not in play | Nothing on this takeoff puts it in play. |
| 427 | Fixed Electric Heating Equipment for Pipelines and Vessels | not in play | Nothing on this takeoff puts it in play. |
| 430 | Motors, Motor Circuits, and Controllers | checked | In play; none of its checked sections applies to these lines. |
| 440 | Air-Conditioning and Refrigerating Equipment | checked | In play; none of its checked sections applies to these lines. |
| 445 | Generators | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 450 | Transformers and Transformer Vaults (Including Secondary Ties) | checked | 1 section checked against the takeoff, all shown. |
| 455 | Phase Converters | not in play | Nothing on this takeoff puts it in play. |
| 460 | Capacitors | not in play | Nothing on this takeoff puts it in play. |
| 470 | Resistors and Reactors | not in play | Nothing on this takeoff puts it in play. |
| 480 | Stationary Standby Batteries | not in play | Nothing on this takeoff puts it in play. |
| 490 | Equipment Over 1000 Volts, Nominal | not in play | Nothing on this takeoff puts it in play. |
| Nothing on this takeoff puts it in play. |
| 514 | Motor Fuel Dispensing Facilities | not in play | Nothing on this takeoff puts it in play. |
| 515 | Bulk Storage Plants | not in play | Nothing on this takeoff puts it in play. |
| 516 | Spray Application, Dipping, Coating, and Printing Processes | not in play | Nothing on this takeoff puts it in play. |
| 517 | Health Care Facilities | not in play | Nothing on this takeoff puts it in play. |
| 518 | Assembly Occupancies | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 520 | Theaters, Audience Areas of Motion Picture and Television Studios, Performance Areas, and Similar Locations | not in play | Nothing on this takeoff puts it in play. |
| 522 | Control Systems for Permanent Amusement Attractions | not in play | Nothing on this takeoff puts it in play. |
| 525 | Carnivals, Circuses, Fairs, and Similar Events | not in play | Nothing on this takeoff puts it in play. |
| 530 | Motion Picture and Television Studios and Similar Locations | not in play | Nothing on this takeoff puts it in play. |
| 540 | Motion Picture Projection Rooms | not in play | Nothing on this takeoff puts it in play. |
| 545 | Manufactured Buildings and Relocatable Structures | not in play | Nothing on this takeoff puts it in play. |
| 547 | Agricultural Buildings | not in play | Nothing on this takeoff puts it in play. |
| 550 | Mobile Homes, Manufactured Homes, and Mobile Home Parks | not in play | Nothing on this takeoff puts it in play. |
| 551 | Recreational Vehicles and Recreational Vehicle Parks | not in play | Nothing on this takeoff puts it in play. |
| 552 | Park Trailers | not in play | Nothing on this takeoff puts it in play. |
| 555 | Marinas, Boatyards, Floating Buildings, and Commercial and Noncommercial Docking Facilities | not in play | Nothing on this takeoff puts it in play. |
| 590 | Temporary Installations | not in play | Nothing on this takeoff puts it in play. |
| Nothing on this takeoff puts it in play. |
| 646 | Modular Data Centers | not in play | Nothing on this takeoff puts it in play. |
| 647 | Sensitive Electronic Equipment | not in play | Nothing on this takeoff puts it in play. |
| 650 | Pipe Organs | not in play | Nothing on this takeoff puts it in play. |
| 660 | X-Ray Equipment | not in play | Nothing on this takeoff puts it in play. |
| 665 | Induction and Dielectric Heating Equipment | not in play | Nothing on this takeoff puts it in play. |
| 668 | Electrolytic Cells | not in play | Nothing on this takeoff puts it in play. |
| 669 | Electroplating | not in play | Nothing on this takeoff puts it in play. |
| 670 | Industrial Machinery | not in play | Nothing on this takeoff puts it in play. |
| 675 | Electrically Driven or Controlled Irrigation Machines | not in play | Nothing on this takeoff puts it in play. |
| 680 | Swimming Pools, Fountains, and Similar Installations | not in play | Nothing on this takeoff puts it in play. |
| 682 | Natural and Artificially Made Bodies of Water | not in play | Nothing on this takeoff puts it in play. |
| 685 | Integrated Electrical Systems | not in play | Nothing on this takeoff puts it in play. |
| 690 | Solar Photovoltaic (PV) Systems | not in play | Nothing on this takeoff puts it in play. |
| 691 | Large-Scale Photovoltaic (PV) Electric Supply Stations | not in play | Nothing on this takeoff puts it in play. |
| 692 | Fuel Cell Systems | not in play | Nothing on this takeoff puts it in play. |
| 694 | Wind Electric Systems | not in play | Nothing on this takeoff puts it in play. |
| 695 | Fire Pumps | not in play | Nothing on this takeoff puts it in play. |
| not in play |
| Nothing on this takeoff puts it in play. |
| 725 | Class 1, Class 2, and Class 3 Remote-Control, Signaling, and Power-Limited Circuits | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 726 | Class 4 (CL4) Fault-Managed Power Systems | not in play | Nothing on this takeoff puts it in play. |
| 728 | Fire-Resistive Cable Systems | not in play | Nothing on this takeoff puts it in play. |
| 750 | Energy Management Systems | not in play | Nothing on this takeoff puts it in play. |
| 760 | Fire Alarm Systems | not in play | Nothing on this takeoff puts it in play. |
| 770 | Optical Fiber Cables | not in play | Nothing on this takeoff puts it in play. |