Derived from what the read produced, so none of it can drift from the data behind it. A blocker stops a price being presented as complete; it never stops you looking. These definitions are this build’s own — no RRE document specifies them yet.
| Check | Status | What the check found |
|---|---|---|
| Sheet scale | blocker | Scale is UNSET on 4 of 8 plan sheet(s): A-004, A-092, A-130, A-150. Nothing on them has been measured, so there is no raceway and no branch wire — together the largest block of material on a job of this kind. Set the scale from each title block on the Drawings screen. |
| Sheets read for scope | warning | 27 sheet(s) were indexed but not read for scope: A-008, A-009, A-010, A-011, A-012, A-013, A-014, A-091, A-110, A-111, A-460, A-501, M-200, M-500, M-501, M-600, M-601, M-602, P-101, P-200, P-300, P-301, S100, FP-1, 007-rocklinelectric.net-Mail---Fwd_-Mango--...ion---Invitation-to-bid-DUE-05_08_2025-p1, 007-rocklinelectric.net-Mail---Fwd_-Mango--...ion---Invitation-to-bid-DUE-05_08_2025-p2, 007-rocklinelectric.net-Mail---Fwd_-Mango--...ion---Invitation-to-bid-DUE-05_08_2025-p3. Looked at by the takeoff and not read: no electrical work on it. Read them, or state the omission on the proposal — the basis of the offer already prints it. |
| Symbol source | pass | A symbol list was found on the drawings: 000-Copy-of-2498-A-set-2025-0530-Revision-1-p1 — COVER PAGE, E-100 — ELECTRICAL SPECIFICATIONS, E-200 — SYMBOLS LIST. The project legend is authoritative for this set and outranks everything else — NECA 100-2006 itself allows a drawing to use non-standard symbols provided the legend explains them. NECA 100-2006 stays underneath it for anything the legend leaves silent, and no conventions file exists for the engineering firm. |
| Symbols named | pass | All 641 marks belong to a named group. |
| Every line prices | pass | Every line points at an assembly. |
| Plan and schedule agree | pass | No line has a plan/schedule disagreement. |
| Lines accepted by a person | blocker | Nothing has been accepted. All 112 line(s) are still suggestions, and machine output is a suggestion until a named person accepts it. Accept on the Takeoff screen — 112 line(s) are ready. |
| Engineer conventions known | pass | No engineer-dependent lines. |
| Unsure flags resolved | pass | The model raised no open flags. |
| Cover sheet read | pass | A cover sheet was found and read; its notes parameterise every later pass. |
What the symbol names rest on. The set’s own legend (000-Copy-of-2498-A-set-2025-0530-Revision-1-p1, E-100, E-200), which is authoritative for this project.
Edition: 2022 California Electrical Code, because in force for permits from 2023-01-01, as of the bid date 2025-05-08. City and county amendments are the AHJ’s: check them on any job inside a city that amends the code. “To check” means the code requires it and the drawings do not show it: send an RFI, or make the call. Nothing here is added to the bid on its own.
| Section | Status | What the code requires | What the takeoff shows | RRE’s practice |
|---|---|---|---|---|
NEC 2020 110.16 Arc-flash warning label on gear | to check | Switchboards, switchgear, panelboards, meter socket enclosures and motor control centers likely to be worked on energized carry a field- or factory-applied arc-flash hazard warning. | In play for PANELBOARD, CURRENT LIMITING, 120V 1PH 2W, 20-POLE, SURFACE (Lighting Control & Design GR 2400 'The Silverbullet') - panel 'CL'. Nothing on the takeoff shows it. | RRE carries phenolic nameplates and labels as their own item where the set calls for them. |
NEC 2020 210.8(B)(2) GFCI on commercial kitchen receptacles | to check | GFCI protection for every receptacle in a commercial kitchen: single-phase up to 50 A and three-phase up to 100 A, 150 V to ground or less. | 1 of 2 in play are not shown with it: TERMINATION, BRANCH CIRCUIT, 20A 1-POLE. | RRE carries a GFCI receptacle at the device where the set calls for GFCI, and adds none on code alone (Mango: no GFCI bid; The Melt: 25 where the set said so). |
NEC 2020 210.8(B)(1) GFCI on bathroom receptacles | to check | GFCI protection for every receptacle in a bathroom: single-phase up to 50 A and three-phase up to 100 A, 150 V to ground or less. | In play for TERMINATION, BRANCH CIRCUIT, 20A 1-POLE; DUPLEX RECEPTACLE 20A 125V, RESTROOM (B-11); RECEPTACLE 20A 125V DUPLEX, DEDICATED, FOR REFRIGERATED DRINKING FOUNTAIN FX-3 (ELKAY EZTL8C + LKAPREZL), IN 4" SQ BOX. Nothing on the takeoff shows it. |
The RRE item carries no price for the part named, so the estimate has the install labor and rough-in only, and the vendor or sub prices the rest. Send the lighting and gear lists from Material list & vendor quotes.
| Line | Needs a price for | Count | Sheet |
|---|---|---|---|
LIGHT FIXTURE TYPE LAL (schedule LAL) - LED strip / millwork linear, remote driver LIGHT FIXTURE TYPE LAL (schedule LAL) - LED strip / millwork linear, remote driver | LED REMOTE DRIVER | 153.8 ft | E-300 |
LIGHT FIXTURE TYPE LAF (schedule LAF) - LED strip / millwork linear, remote driver LIGHT FIXTURE TYPE LAF (schedule LAF) - LED strip / millwork linear, remote driver | LED REMOTE DRIVER | 125.3 ft | E-300 |
LIGHT FIXTURE TYPE P15.1W (schedule P15.1w) - track head LIGHT FIXTURE TYPE P15.1W (schedule P15.1w) - track head | LED TRACK SPOT FIXTURE | 115 ea | E-300 |
LIGHT FIXTURE TYPE P08.1W (schedule P08.1w) - track head LIGHT FIXTURE TYPE P08.1W (schedule P08.1w) - track head | LED TRACK SPOT FIXTURE | 95 ea | E-300 |
EMERGENCY BATTERY PACK, 90-MIN, FIELD-INSTALLED IN FIXTURE (tag /EMB, lighting note 6) EMERGENCY BATTERY PACK, 90-MIN, FIELD-INSTALLED IN FIXTURE (tag /EMB, lighting note 6) | LED EMERGENCYLIGHT DUAL | 18 ea |
9 lines the reader wrote at zero are not listed: they add nothing to the bid.
MODELLED - modelled from untagged fixtures: the circle circuit tags (15,h / 10,k / 41/EMB ...) are drawn as outlines and did not read (3 tags). raceway_model.py ran with panel A placed in the BOH beside the Lutron hub (panel not drawn on E-300; E-600 says existing) and --untagged-circuits 19 (A-1,3,5,7,9,10,11,13,15,17,19,21 lighting, A-41 EM, A-23..33 track via CL) over 20 fixture-tag stops; 7 shared homerun pipes, fixture-to-fixture chain in EMT per interview (EMT+THHN). Model sized 1/2"; carried at 3/4" per lighting note 2 ('2#12 & 1#12G in 3/4"C'). Wire from the same model, route factor 1.05 and makeup included. (Model line id L-0051.) The model also raised 'modelled from untagged fixtures', which the contract has no flag for; recorded here rather than dropped.
Lighting note 9 and E-900: 2 additional #12 for controls at all 0-10V dimmable fixtures; interview dimming_pair 'full circuit'. 2 x 2653.8 ft conduit x 1.05 route factor. (Model line id L-0052.)
Panel A: raceway_model wire 3,401.2 ft #12 (conductors x path x 1.05 + 2.6 ft/conductor/box). Panel B: 3 x 500.1 x 1.05 + 12 boxes x 3 x 2.6 = 1,668.9 ft. Total =3401.2+1668.9 = 5,070 ft. Voltage-drop upsizing (E-200: #12 max 62 ft at 120V) not applied per circuit; several B runs (signage ~98-110 ft) exceed it and would go #10 - flagged. (Model line id L-0073.) The model also raised 'voltage drop upsizing not applied', which the contract has no flag for; recorded here rather than dropped.
MODELLED - modelled from untagged fixtures: the circle circuit tags (15,h / 10,k / 41/EMB ...) are drawn as outlines and did not read (3 tags). raceway_model.py ran with panel A placed in the BOH beside the Lutron hub (panel not drawn on E-300; E-600 says existing) and --untagged-circuits 19 (A-1,3,5,7,9,10,11,13,15,17,19,21 lighting, A-41 EM, A-23..33 track via CL) over 20 fixture-tag stops; 7 shared homerun pipes, fixture-to-fixture chain in EMT per interview (EMT+THHN). Model sized 1/2"; carried at 3/4" per lighting note 2 ('2#12 & 1#12G in 3/4"C'). Striking the line leaves the lighting branch unpiped. (Model line id L-0050.) The model also raised 'modelled from untagged fixtures', which the contract has no flag for; recorded here rather than dropped.
Added by kelchlin from a suggestion -- quantity 1666 ft ESTIMATED from RRE's ratio, not measured: RRE priced this on 2 of 3 past jobs (67%). RRE’s last retail job: 2,001.5 ft of MC luminary 16-2 and 758.6 ft of 12/3 for its 143 whip-fed fixtures (downlights, sconces, emergency, exit, suspended; track heads and strip excluded), measured off the lighting plan as fixture-to-fixture runs. One job so far -- a starting point, not a norm. Recommended: RRE-MC-LUM-16-2, priced as RRE bid it at 0.028 hr/ft.
Panel A branch: raceway_model.py run with the 40 hand-placed receptacle stops and the A-36 J-box, panel A placed at the drawn EXISTING PANEL 'A' bar (1171,1416), --untagged-panel A --untagged-circuits 18 (A-2,4,6,8,12,14,16,18,20,22,24,26,28,30,32,36,40,42 off the panel A schedule) because the circuit tags are outlined text and read 0: 832.2 ft, modelled from untagged stops, 6 shared homerun pipes. The model sized it 1/2"; carried at 3/4" per Power Note 1. Panel B branch measured by hand, Manhattan at 3/16"=1' (13.5 pt/ft) + 10 ft rise + 5 ft stub per run: EWH 59.3, B-1 sign 97.7, B-4 signs 110.0+9.6, B-5 chain CP/CP/EX-TX-1/CU J-boxes 113.3, B-6 GFCI 45.4, B-11 64.8 = 500.1 ft. Total 1,332.3 ft (=832.2+500.1). Wiring method not given by the interview in job facts: carried EMT+THHN throughout, no MC drops. (Model line id L-0072.)
Added by kelchlin from a suggestion -- quantity 1292 ft ESTIMATED from RRE's ratio, not measured: RRE priced this on 3 of 3 past jobs (100%). RRE’s last retail job: 692 ft of track (77 × 8' + 19 × 4'), 1,262.6 ft of 1-5/8" unistrut (2× the 629 ft drawn -- mall rule: supports to the joist, never the deck), 70 trapeze supports with 2 rods each (140 × 3 ft of 3/8" all-thread), one beam clamp per rod. 1 RRE estimate so far -- one job, so treat the ratio as a starting point, not a norm. Recommended: RRE-UNISTRUT-FT, RRE’s own item at 0.09 hr/ft.
Added by kelchlin from a suggestion -- quantity 743 ea ESTIMATED from RRE's ratio, not measured: RRE priced this on 3 of 3 past jobs (100%). RRE’s last restaurant job: 805 straps on 3,183 ft of 3/4" EMT (one per 4 ft); its last retail job 764 on 2,142 ft (one per 2.8 ft). The EMT item carries one per 8 ft, so 0.18 a foot more. Recommended: RRE-EMT-STRAP at 0.03 hr each.
Each of the 29 measured track runs bought in 8' pieces with a 4' piece for any remainder: 81 x 8' = 648 ft of 8' sections. (Model line id L-0040.)
Added by kelchlin from a suggestion -- quantity 631 ft ESTIMATED from RRE's ratio, not measured: RRE priced this on 3 of 3 past jobs (100%). RRE’s last retail job: 2,001.5 ft of MC luminary 16-2 and 758.6 ft of 12/3 for its 143 whip-fed fixtures (downlights, sconces, emergency, exit, suspended; track heads and strip excluded), measured off the lighting plan as fixture-to-fixture runs. One job so far -- a starting point, not a norm. Recommended: RRE-MC-LUM-12-3, priced as RRE bid it at 0.028 hr/ft.
3 x 125.5 x 1.05 + 6 x 2.6 = 410.9 ft. (Model line id L-0077.)
Added by kelchlin from a suggestion -- quantity 390 ea ESTIMATED from RRE's ratio, not measured: RRE priced this on 3 of 3 past jobs (100%). RRE carries MC connectors in step with its luminary cable. Less the ones its branch MC items already carry, about 478 for 2,760 ft on its last retail job and 141 for 853 ft on its last restaurant job (0.17 a foot). Recommended: RRE-MC-CONNECTOR at 0.05 hr each.
3 x 74.6 x 1.05 + 6 x 2.6 = 250.6 ft. (Model line id L-0075.)
(74.6+125.5) x 1.05 + 4 x 2.6 = 220.5 ft. (Model line id L-0078.)
Sum of the run lengths printed beside each LAL run on E-300: LAL 01 16.67', LAL 02 16.67', LAL 03 15.00', LAL 04 15.00', LAL 5 29.67', LAL 8 60.75' = 153.8 ft. E-800 Table F carries 185 ft (256.6). Lighting note 7: remote LED driver, see millwork lighting plan (not in this set). (Model line id L-0037.) The model also raised 'plan/schedule disagreement', which the contract has no flag for; recorded here rather than dropped.
Added by kelchlin from a suggestion -- quantity 143 ea ESTIMATED from RRE's ratio, not measured: RRE priced this on 3 of 3 past jobs (100%). RRE’s last retail job: 692 ft of track (77 × 8' + 19 × 4'), 1,262.6 ft of 1-5/8" unistrut (2× the 629 ft drawn -- mall rule: supports to the joist, never the deck), 70 trapeze supports with 2 rods each (140 × 3 ft of 3/8" all-thread), one beam clamp per rod. 1 RRE estimate so far -- one job, so treat the ratio as a starting point, not a norm.
Added by kelchlin from a suggestion -- quantity 143 ea ESTIMATED from RRE's ratio, not measured: RRE priced this on 1 of 3 past jobs (33%). RRE’s last retail job: 140 beam clamps for 140 rod drops, one each (item 7522 with saddle washer 5987 and three nuts 5994). Recommended: RRE-BEAM-CLAMP-ROD, priced exactly as RRE bid it: 0.22 hr and $6.78 a clamp.
From MD bar Manhattan to CU-1 (65.7 ft) and CU-2 (59.8 ft), incl. 10 ft rise + 5 ft stub; roof route factor (x1.24) not applied, roof penetration route not drawn - flagged. (Model line id L-0076.) The model also raised 'roof route not drawn', which the contract has no flag for; recorded here rather than dropped.
Sum of the run lengths printed beside each LAF run on E-300: LAF 1 16.33', LAF 2 16.33', LAF 5 16.33', LAF 6 16.33', LAF 6b 16.33', LAF 8 16.33', LAF 10 13.67', LAF 10a 13.67' = 125.3 ft. E-800 Table F carries 141 ft (141.2). Lighting note 7: remote LED driver, see millwork lighting plan (not in this set). (Model line id L-0038.) The model also raised 'plan/schedule disagreement', which the contract has no flag for; recorded here rather than dropped.
Counted 94 'P15.1W' plus 21 'P15.1b' labels (same head, variant lettering in the triangle grid) = 115; E-800 Table F carries 115. Heads mount on tracks 1-7. (Model line id L-0036.)
Counted 95 'P08.1W' type labels in the E-300 plan text layer (architect RCP xref labels beside each fixture). E-800 Table F carries 95. EC furnishes and installs per E-200 EM schedule note. (Model line id L-0029.)
From EXISTING PANEL 'MD' bar (1171,1486) Manhattan at 13.5 pt/ft + 10 ft rise + 5 ft stub: AHU-1 33.1 ft, AHU-2 41.6 ft = 74.6 ft, sized from each unit's own callout. (Model line id L-0074.)
Remainder pieces of the 29 measured track runs: 15 x 4' = 60 ft of 4' sections. (Model line id L-0041.)
Added by kelchlin from a suggestion -- quantity 51 ea ESTIMATED from RRE's ratio, not measured: RRE priced this on 1 of 3 past jobs (33%). RRE’s last retail job: 79 Tenmat FF109-300 covers for its 79 recessed downlights, one each, at 0.10 hr and $8.66. Recommended: RRE-TENMAT, priced as RRE bid it.
3 conductors x 15 ft of the A-38 hub run. (Model line id L-0046.)
Panel A: 18 odd-side 1P20 (1-33, 41) + 20 even-side (2-42 less SPARE 34) = 38. Existing panel: terminations only, no new feeder. (Model line id L-0003.) The model also raised 'existing panel; some circuits may be existing-to-remain - field verify per E-601 EC note 1', which the contract has no flag for; recorded here rather than dropped.
Three data triangles at the cash-wrap stations. av_stub_rule: Retail ceiling 12 ft (job facts) minus 18" box = 10.5 ft x 3 = 31.5 ft at 1" (Power Note 3). LV wiring is by GC per E-200 LV legend; EC boxes/stubs only. (Model line id L-0080.)
Dashed below-floor lines measured at 13.5 pt/ft: cash-wrap run 19.3 ft (along the wrap and down to the wall), sensomatic receptacle run 6.9 ft. Saw-cut/trench and patch by EC per E-200 GN 2 (not a separate line here). The long dashed diagonal at the storefront is lettered 'line of sensomatic below finish floor' and is not taken as EC conduit - flagged under coverage. (Model line id L-0079.)
Counted 26 duplex receptacle symbols by eye on the E-400 power plan: A-4 x3 (sales floor), A-6 x1 (window display), A-2 x3 (fitting rooms), A-8 x2, A-12 x4, A-42 x4 (storage), A-14 x2 (office), A-32 x2 (charging station), and one each at A-40 (IT rack), A-16 (access control), A-18 (burglar alarm), A-20 (IT equipment) in the back-of-house IT corner. The lettering is drawn as outlines, so the symbol scan only returned letter shapes; each position is placed by hand from the page image. Job facts say the IT rack takes (3) quad outlets; the plan draws single symbols at A-16/18/20/40, so the kind there is to confirm. Striking the line removes the general-purpose receptacles. (Model line id L-0053.) The model also raised 'hand_read', 'semantic risk: IT corner may be quad', which the contract has no flag for; recorded here rather than dropped.
Counted 25 'E12.1W' type labels in the E-300 plan text layer (architect RCP xref labels beside each fixture). E-800 Table F carries 26. EC furnishes and installs per E-200 EM schedule note. (Model line id L-0030.) The model also raised 'plan/schedule disagreement', which the contract has no flag for; recorded here rather than dropped.
Counted 18 '/EMB' fixture tags on the E-300 page image (41/EMB and 17/EMB). Note 6: EMB fixtures get a 90-minute battery pack and an additional unswitched hot leg. Hand-placed from the image; confirm. (Model line id L-0043.) The model also raised 'image count, confirm', which the contract has no flag for; recorded here rather than dropped.
A-130 schedule row S02 qty 16, Fitting Rooms, 'Power 24VDC', vendor Owner; note 7 'Driver to be installed remotely. Refer to A-425. (2) sconce lights per each transformer (XLG-75 series). GC to provide low voltage wiring between fixtures and transformer.' Not on E-300 lines. (Model line id L-0092.) The model also raised 'schedule_qty', 'furnish: Owner (install only)', which the contract has no flag for; recorded here rather than dropped.
Hub sits beside the assumed panel A location in the BOH; 10 ft rise plus 5 ft stub modelled. Panel location not drawn on E-300. (Model line id L-0045.)
Counted 13 'BA' tags in the back-of-house stockroom (open to deck) on A-130; A-130 lighting schedule row BA qty 13, vendor GC. E-300 carries no BA label (E-300 gap), so taken here. (Model line id L-0087.) The model also raised 'hand_read', 'furnish: schedule vendor GC', which the contract has no flag for; recorded here rather than dropped.
Counted 11 'E10.1W' type labels in the E-300 plan text layer (architect RCP xref labels beside each fixture). E-800 Table F carries none. EC furnishes and installs per E-200 EM schedule note. (Model line id L-0033.) The model also raised 'plan/schedule disagreement', which the contract has no flag for; recorded here rather than dropped.
Counted 11 ST-## tags on A-150 (ST-03, ST-04 x2, ST-05, ST-06, ST-07, ST-08, ST-10, ST-11, ST-12, ST-13), each '30W WHT'. (Model line id L-0096.)
Counted 13 'EM2' and 4 'EM3' tags on the A-004 ADA/Egress plan (text layer decoded, confirmed on crops; marks G-001/G-002). E-300 L-0014 already carries 7 exit signs; Rev 1 transmittal says extra EM-2 exit signs were added on A-004 per building department comment and E-300 Rev 1 says final light locations are per the architectural set. Takes the 10 A-004 positions no E sheet shows. (Model line id L-0083.) The model also raised 'reconcile_with_E-300_L-0014', 'type_definition_conflict_E-200_vs_A-004_legend', which the contract has no flag for; recorded here rather than dropped.
E-900 switching information table: 9 rows RMJS-PNE-DV. E-200: Lutron purchase via national distributor; E-900 GC note 2 contractor installs all Lutron devices & wiring. (Model line id L-0026.) The model also raised 'plan agents: do not double-count PowPak modules', which the contract has no flag for; recorded here rather than dropped.
Counted 9 'E05W' type labels in the E-300 plan text layer (architect RCP xref labels beside each fixture). E-800 Table F carries 8 (tag 9). EC furnishes and installs per E-200 EM schedule note. (Model line id L-0032.) The model also raised 'plan/schedule disagreement', which the contract has no flag for; recorded here rather than dropped.
Three cash-wrap stations tagged #26, #28, #30, each drawn with three receptacle symbols in the millwork (dedicated cash register circuits per panel A schedule). Fed by the dashed underfloor conduit to the wall. Striking removes the cash-wrap receptacles. (Model line id L-0058.) The model also raised 'hand_read', which the contract has no flag for; recorded here rather than dropped.
Counted 8 'SA' boxed symbols along the fitting rooms on the E-300 image. Symbol is not defined on this sheet; taken as a Vive wireless sensor accessory per note 4. Confirm with E-200 legend / E-900. (Model line id L-0049.) The model also raised 'symbol meaning unconfirmed', which the contract has no flag for; recorded here rather than dropped.
A-420 section 7 (M3-Fitting Rooms Section) dimensions a junction box at 4'-7" (1.40m) AFF on the mirror light bar and marks it 'Junction box TYP'. The section and plan 1 show 8 fitting rooms (7 standard with FF-54 benches plus the ADA room), so 1 box per room = 8. The E sheets count the S02 mirror bars (16) as fixtures, not this box. If the estimator's S02 assembly already carries a box, strike this line. (Model line id L-0104.) The model also raised 'hand_read', 'verify_with_E-300', 'possible_overlap_with_fixture_assembly', which the contract has no flag for; recorded here rather than dropped.
CL schedule: 7 active 1P positions (TRACK #1-#7); A-29 feeds both TRACK #4 and #7. (Model line id L-0002.)
Counted 7 '41/EX' exit tags on the E-300 page image (circuit A-41, lock-on breaker). E-800 Table F carries EX01 6 + EX02 1 = 7. Lighting note 5: 120V LED with 90-minute battery. (Model line id L-0042.)
Counted 7 tags AP-001..AP-007 with WIFI symbol on A-150 plan (retail and stockroom). LV notes 2-4: wiring by GC, GC pulls all wire, equipment by vendor -- rough-in (box/stub) stays with EC per house rule. (Model line id L-0095.)
Counted 6 'E11.1W' type labels in the E-300 plan text layer (architect RCP xref labels beside each fixture). E-800 Table F carries 6. EC furnishes and installs per E-200 EM schedule note. (Model line id L-0031.)
Counted 6 magenta CCTV camera symbols on A-150: 2 at cash counter/fitting wall, 2 at entry vestibule, 1 in QA/office, 1 in rear egress hallway (confirmed on 150-200 dpi crops). (Model line id L-0099.)
Counted 6 wired-device tags EQ-17a/17b/17b/17e/17e/17f at the entry vestibule on A-150. Plan tags read EQ-17x while legend reads EQ-20x; matched by letter suffix -- see coverage gap. (Model line id L-0100.) The model also raised 'tag_legend_mismatch', which the contract has no flag for; recorded here rather than dropped.
Panel B schedule rows 1,3,5,6,11. (Model line id L-0004.)
Five J + $T symbols tagged B#5 (panel B-5 'motorized damper / CV'): at the condensate pump (CP) of AHU-1 and AHU-2, at EX-TX-1, and WP at CU-1 and CU-2 on the roof. Two are weatherproof (roof). (Model line id L-0063.) The model also raised 'hand_read', which the contract has no flag for; recorded here rather than dropped.
The $T drawn with each of the five B#5 J-boxes. (Model line id L-0064.) The model also raised 'hand_read', which the contract has no flag for; recorded here rather than dropped.
One per panel touched (A, B, MD, CL). (Model line id L-0012.)
Counted 4 'P01W' type labels in the E-300 plan text layer (architect RCP xref labels beside each fixture). E-800 Table F carries none. EC furnishes and installs per E-200 EM schedule note. (Model line id L-0034.) The model also raised 'plan/schedule disagreement', which the contract has no flag for; recorded here rather than dropped.
Counted 4 'P02W' type labels in the E-300 plan text layer (architect RCP xref labels beside each fixture). E-800 Table F carries none. EC furnishes and installs per E-200 EM schedule note. (Model line id L-0035.) The model also raised 'plan/schedule disagreement', which the contract has no flag for; recorded here rather than dropped.
Counted 4 'VS' boxed symbols on the E-300 image (fitting-room corridor and BOH). Taken as Lutron Vive Pico wall controls per lighting note 4; confirm against E-900. (Model line id L-0048.) The model also raised 'named from reference, confirm', which the contract has no flag for; recorded here rather than dropped.
Four hard-wired HVAC units on MD drawn on this sheet: AHU-1, AHU-2 (interior) and CU-1, CU-2 (roof). Each gets its connection at the disconnect. (Model line id L-0069.)
Counted 3 circled 'OS' sensor symbols in the BOH on the E-300 image. Lutron hardware purchased by national distributor (E-200); EC installs (E-900 GC note 2). Wireless: no box or wiring. (Model line id L-0047.) The model also raised 'named from symbol, confirm', which the contract has no flag for; recorded here rather than dropped.
Three receptacles the plan calls GFCI by tag: B#6,GFCI at the break-room counter and #22,GFI / #24,GFI at EQ-14/EQ-15 (see note 5). Carried at the device per RRE practice. (Model line id L-0055.) The model also raised 'hand_read', which the contract has no flag for; recorded here rather than dropped.
Three 'ELECTRICAL EQUIPMENT (SIGNAGE)' positions each drawn as J + $T: one on B#1 at the storefront, two on B#4 at the mall signage. Panel B schedule lists B-4 as SPARE, so the B#4 signs need the circuit confirmed. $T named from NECA reference, confirm (motor/thermal-rated switch). (Model line id L-0061.) The model also raised 'hand_read', 'B-4 spare on schedule', which the contract has no flag for; recorded here rather than dropped.
The $T drawn beside each of the three signage J-boxes, counted as its own device. (Model line id L-0062.) The model also raised 'hand_read', which the contract has no flag for; recorded here rather than dropped.
Three data triangles, one per register station. (Model line id L-0081.) The model also raised 'hand_read', which the contract has no flag for; recorded here rather than dropped.
Counted 3 'BA/EM' tags in BOH on A-130; schedule row BA/EM qty 3, 'GC Provide and installed. 90 min battery backup'. Not counted on E-300. (Model line id L-0088.) The model also raised 'hand_read', 'emergency: own circuit per schedule note 4', which the contract has no flag for; recorded here rather than dropped.
Counted 3 'QA' tags in the BOH office/staff rooms on A-130 (Rev 1 blue row). Schedule row QA says qty 2 -- plan and schedule disagree by 1; plan count carried. Not on E-300 lines. (Model line id L-0089.) The model also raised 'hand_read', 'plan_schedule_conflict', which the contract has no flag for; recorded here rather than dropped.
Panel MD clouded Rev-1 rows: AHU-1, AHU-2 3P 15A, 800W/ph. (Model line id L-0006.)
Panel MD clouded Rev-1 rows: CU-1, CU-2 3P 20A, 2,607W/ph. (Model line id L-0007.)
Two receptacles labelled CLK 54"AFF: one on A-4 at the entry column, one on A-6 (clouded Rev 1) at the storefront window. Striking the line removes both clock outlets. (Model line id L-0056.) The model also raised 'hand_read', which the contract has no flag for; recorded here rather than dropped.
Two CP circles beside AHU-1 and AHU-2, each connected from the B#5 J-box. (Model line id L-0065.) The model also raised 'hand_read', which the contract has no flag for; recorded here rather than dropped.
CU-1 and CU-2 each drawn with a WP disconnect lettered 3/30A (Rev 1 cloud), LOCATED ON ROOF. STEP 4.5 disconnect sizing: CU-1 and CU-2 are not listed in any equipment schedule read (output/work/equipment has A-090, A-140, P-100 only), so no MOCP is available; the line keeps the drawn 3/30A WP switch, sized at 30A on the 20A 3P MD breaker, NEMA 3R because both units are on the roof, non-fused because no fuse is shown. Coverage gap raised. (Model line id L-0066.)
AHU-1 and AHU-2 each drawn with a disconnect lettered 3/30A and WP. STEP 4.5 disconnect sizing: AHU-1 and AHU-2 are not listed in any equipment schedule read, so no MOCP is available; kept at the drawn 3/30A WP (30A on the 15A 3P MD breaker), non-fused as drawn. Coverage gap raised. (Model line id L-0067.)
A-120 legend: green receptacle tagged CLK = 'POWER: HARD WIRE - FOR ILLUMINATED MIRRORS'. The plan draws 4 CLK 54"AFF positions, each on a wall mirror: accessible fitting room wall, sales-area column, the long diagonal wall, and the south wall by the office/staff rooms. E-400 counts only 2 CLK outlets ('entry column' and 'storefront window'), so the other 2 are taken here. I took the fitting-room wall and south wall ones as the new ones because they are neither at a column nor at the storefront. Striking this line removes the 2 extra mirror outlets. Branch circuit, box and stub are not drawn (see coverage). (Model line id L-0085.) The model also raised 'hand_read', 'cross_sheet_conflict', 'verify_with_E-400', which the contract has no flag for; recorded here rather than dropped.
Counted 2 'S0' symbols (clouded, delta 1) in the BOH stockroom on A-130. Legend: 'HARDWIRE SMOKE DETECTORS AND CARBON MONOXIDE DETECTORS'. No E sheet read counts them. Circuit not given. (Model line id L-0094.) The model also raised 'hand_read', 'scope: may be FA/LL vendor', which the contract has no flag for; recorded here rather than dropped.
Counted 2 SS-## tags (SS-01, SS-02, '7.5W') on A-150. (Model line id L-0097.)
M-100 section H 'Wiring' note 1: mechanical trade furnishes and delivers 'wall-mounted electrical contacting thermostats, etc.' for mounting and connection by the electrical trade. Quantity 2 from M-102 schedule note 2 ('24 hour/7 day programmable thermostat for each unit', 2 units AHU-1/AHU-2) and ductwork note 3 (remote flush button sensor at 4'-6" AFF per AHU). Low-voltage control wiring stays with MC (H.3). (Model line id L-0109.) The model also raised 'spec-derived quantity - verify thermostat locations on M-300', 'EC install only, material by MC', which the contract has no flag for; recorded here rather than dropped.
E-601 'NEW CURRENT LIMITING PANEL "CL"' 20 poles, 120V 1Ø2W, surface; E-600 shows it as the only NEW gear (solid line) fed by feed-thru circuits. (Model line id L-0001.)
Panel B 7,9 2P 20A EWH 2,500W. (Model line id L-0005.)
E-601 titles panel A EXISTING (B: 'SUB-PANEL', E-600 'EXISTING PANEL B'); E-600 feeders all 'EXISTING ... TO REMAIN'. (Model line id L-0008.)
E-601 titles panel B EXISTING (B: 'SUB-PANEL', E-600 'EXISTING PANEL B'); E-600 feeders all 'EXISTING ... TO REMAIN'. (Model line id L-0009.)
E-601 titles panel MD EXISTING (B: 'SUB-PANEL', E-600 'EXISTING PANEL B'); E-600 feeders all 'EXISTING ... TO REMAIN'. (Model line id L-0010.)
E-601 panel legend '*': provide lock-on device on circuit breaker serving emergency lighting (A-41 '20(*)'). (Model line id L-0011.)
Outdoor flex whip at each outdoor unit (firm rule). (Model line id L-0016.)
Outdoor flex whip at each outdoor unit (firm rule). (Model line id L-0018.)
EX-FX-1 360W on B-3; E-200 motor note 1P 20A 2#12 & 1#12G 3/4"C; thermal disconnect switch symbol ($T) in legend. (Model line id L-0020.) The model also raised 'confirm $T or disconnect symbol at EX-FX-1 on plans', which the contract has no flag for; recorded here rather than dropped.
Hard-wired equipment on panel schedule (no plug configuration). (Model line id L-0025.)
E-900 switching table row 1. (Model line id L-0027.)
E-900 Vive system detail: J-box 120V circuit above drop ceiling; A-38 scheduled. (Model line id L-0028.)
E-300 callout: '#38 (LUTRON VIVE HUB) 2#12 & 1#12G IN 3/4" C' in the BOH. Hub hardware itself is already a _job.json line; this is its J-box (hardwired_equipment_jbox). (Model line id L-0044.)
One receptacle tagged B#11 in the restroom. The plan does not mark it GFCI, so it is not carried as GFCI (no GFCI added from code alone); flag for the estimator. (Model line id L-0054.) The model also raised 'hand_read', 'restroom without GFCI mark', which the contract has no flag for; recorded here rather than dropped.
One receptacle symbol inside the Rev-1 cloud at the angled window display on A-6, lettered CLG and FLR. Whether it is a ceiling or a floor receptacle (or one of each) is not settled by the plan; carried as one, flagged. (Model line id L-0057.) The model also raised 'hand_read', 'semantic risk', which the contract has no flag for; recorded here rather than dropped.
"PLACE SENSOMATIC RECEPTACLE IN ACCESS PANEL" on A-36, fed by the dashed below-floor line to the storefront column. (Model line id L-0059.) The model also raised 'hand_read', which the contract has no flag for; recorded here rather than dropped.
One J symbol tagged #36 at the end of the dashed 'line of sensomatic below finish floor' by the storefront. (Model line id L-0060.) The model also raised 'hand_read', which the contract has no flag for; recorded here rather than dropped.
EWH (Rev 1 cloud) drawn with a disconnect lettered 2/30A, 2.5KW, B#(7,9), 2#12 & 1#12G in 3/4"C. STEP 4.5 disconnect sizing from the P-100 Electric Water Heater Schedule unit WH-1: 12.0 A, 2.5 kW, 208V 1PH; the schedule gives no MCA/MOCP and no disconnect note, so the switch is sized from the 20A 2P branch breaker (B-7,9): the next standard size at or above it is 30A. It is indoor, so NEMA 1, and non-fused because the drawing shows no fuse. (Model line id L-0068.)
EWH hard-wired per job facts, connection at its disconnect. (Model line id L-0070.)
EX-TX-1 is drawn and lettered EXISTING B#3; its existing circuit is kept, only the connection and the B-5 J/$T beside it are new. Flag: confirm whether this is EX-FX-1 of the panel schedule. (Model line id L-0071.) The model also raised 'hand_read', which the contract has no flag for; recorded here rather than dropped.
A-001 (cover page) Mall Notes, item 30 ELECTRICAL a: tenant to install one electric meter for the main electrical system, Quadlogic RSM5 or S20. One meter per note; no meter appears on the E-600 riser, so it is taken off here. (Model line id L-0082.) The model also raised 'verify with landlord whether meter is furnished by landlord or tenant; CT sizing for 400A 480V MD; comms line to landlord metering system not shown', which the contract has no flag for; recorded here rather than dropped.
A-090 Equipment Schedule row EQ-2b 'Speaker Control Relay', provider GC, installer GC, model 'RDL Stick-on Series', location IT Rack, comment 'GC to to provide and install relay. Relay to shut in store music off when Fire alarm or building alarm is activated. Coordinate with LL'. One row = one relay. No E sheet read shows it. The FA side is 'LL Required Vendor' per the matrix; this line is the relay only. (Model line id L-0084.) The model also raised 'hand_read', 'scope: GC item, may be LV or FA vendor', which the contract has no flag for; recorded here rather than dropped.
A-120 plumbing fixture schedule: FX-3 Drinking Fountain, Elkay EZTL8C + LKAPREZL, qty 1, Back of House, Notes 4. Note 4: 'Drinking Fountain provided and installed by GC ... Provide 120 V power.' The EZTL8C is a refrigerated bi-level cooler that needs 120V. The plan draws the bi-level fountain by the restroom corridor, but none of the E sheets read shows an outlet there. Taken as 1 outlet position. Striking this line leaves the fountain unpowered. The circuit is not drawn (see coverage). (Model line id L-0086.) The model also raised 'hand_read', 'not_on_E_sheets', 'verify', which the contract has no flag for; recorded here rather than dropped.
Counted 1 'QA/EM' tag in BOH on A-130; schedule row QA/EM qty 1, 'GC Provide and installed. 90 min battery backup'. (Model line id L-0090.) The model also raised 'hand_read', which the contract has no flag for; recorded here rather than dropped.
Counted 1 SW-02 'SUB' tag at the sales floor rear wall on A-150; plan note 'SUBWOOFER TO BE INSTALLED ON WALLS, GC TO PROVIDE ACCESS PANELS, TYP.' (Model line id L-0098.)
Door schedule row 05 remarks 'Notes: 1,2,7A,10,12'; note 7A 'Door from Retail to Back of House - GC to coordinate with tenant alarm company and to provide the necessary wiring and power. Provide Key pad connected to local alarm on sales side.' Schedule and notes are raster on this sheet; read from 200-dpi crops. 1 position. (Model line id L-0105.) The model also raised 'note_7A_7C_names_GC_for_wiring_and_power_confirm_EC_carries_rough_in', 'device_and_cable_by_tenant_alarm_company', which the contract has no flag for; recorded here rather than dropped.
Note 7A (referenced by door 05 remarks): 'Provide push alarm release on empoyee side.' 1 position. Read from the 200-dpi crop of the notes table. (Model line id L-0106.) The model also raised 'note_7A_7C_names_GC_for_wiring_and_power_confirm_EC_carries_rough_in', 'device_and_cable_by_tenant_alarm_company', which the contract has no flag for; recorded here rather than dropped.
Door schedule row EX-01 (existing 90-min rated door, VIF): Stop = 'Electromagnetic Holder', remarks 'Notes: 7C,9,10,12 (90 min rated exisitng door)'; note 2 ties hold-openers to the fire alarm. 1 position. Holder may be existing (door and closer are marked existing) - field verify. (Model line id L-0107.) The model also raised 'fire_alarm_interface_confirm_by_FA_contractor', 'existing_door_VIF', which the contract has no flag for; recorded here rather than dropped.
Added by kelchlin from a suggestion: RRE priced this on 3 of 3 past jobs (100%). RRE’s last retail job and last restaurant job carried these items at identical quantities -- a fixed allowance, not a count (33.4 hr, $732). Recommended: RRE-HOUSE-KIT, once per job.
Added by kelchlin from a suggestion: RRE priced this on 3 of 4 past jobs (75%). RRE carried these at exactly these quantities on its two larger jobs (22.0 hr, $150), and about an eighth of them, with no backboard, on its smallest. Recommended: RRE-HOUSE-KIT-LOOSE on a job of restaurant or larger-retail size; leave it off a small fit-out.
| RRE carries GFCI at the device where the set calls for it. |
NEC 2020 210.8(B) GFCI near sinks, in locker rooms, wet and damp locations | to check | GFCI protection for receptacles within 6 ft of a sink, in locker rooms with showers, in indoor wet or damp locations, and in garages, service bays and similar areas. | In play for TERMINATION, BRANCH CIRCUIT, 20A 1-POLE. Nothing on the takeoff shows it. | — |
NEC 2020 210.63 Service receptacle at HVAC equipment | to check | A 125-volt, 15- or 20-ampere receptacle on the same level and within 25 ft of heating, air-conditioning and refrigeration equipment, not on the load side of the equipment disconnect. | In play for #6 THHN CU WIRE, AHU FEEDS; #10 THHN CU WIRE, EQUIPMENT GROUND (AHU/CU); 3/4" EMT CONDUIT, CU FEEDS (ROOF); and 11 more. Nothing on the takeoff shows it. | RRE carries the roof receptacle where the set draws one (reading check 11). |
NEC 2020 300.21 Firestopping at rated penetrations | to check | Electrical penetrations of fire-resistance-rated walls, partitions, floors or ceilings firestopped by an approved method that keeps the rating. | In play for TENMAT FIRE-RATED COVER OVER RECESSED DOWNLIGHT. Nothing on the takeoff shows it. | — |
NEC 2020 300.11, 410.36(B) Support in suspended ceilings | to check | Raceways, cables and boxes above a suspended ceiling are supported independently of the ceiling grid, or by identified support wires; lay-in luminaires are fastened to the grid framing. | In play for LIGHT FIXTURE TYPE QA (schedule QA); LIGHT FIXTURE TYPE QA/EM (schedule QA/EM). Nothing on the takeoff shows it. | RRE carries the fixture support wire as its own item where the ceiling is a grid. |
NEC 2020 422.5(A) GFCI on drinking water coolers, bottle fillers and vending machines | to check | GFCI protection for the appliances 422.5(A) lists, among them drinking water coolers, bottle fill stations, vending machines and high-pressure spray washers. | In play for RECEPTACLE 20A 125V DUPLEX, DEDICATED, FOR REFRIGERATED DRINKING FOUNTAIN FX-3 (ELKAY EZTL8C + LKAPREZL), IN 4" SQ BOX. Nothing on the takeoff shows it. | — |
NEC 2020 210.62 Receptacles in show windows | shown | At least one 125-volt receptacle within 18 in. of the top of a show window for each 12 linear ft of show window. | In play for RECEPTACLE AT WINDOW DISPLAY, LABELLED CLG / FLR (A-6). Shown: RECEPTACLE AT WINDOW DISPLAY, LABELLED CLG / FLR (A-6). | — |
NEC 2020 408.4(A) Circuit directory at every panel | shown | Every circuit and circuit modification legibly identified as to its clear, evident and specific purpose on a circuit directory at the panel. | In play for PANELBOARD, CURRENT LIMITING, 120V 1PH 2W, 20-POLE, SURFACE (Lighting Control & Design GR 2400 'The Silverbullet') - panel 'CL'. Shown: PANEL DIRECTORY, TYPED. | RRE carries a panel directory update where circuits land in an existing panel. |
NEC 2020 440.14 Disconnect within sight of HVAC equipment | shown | A disconnecting means within sight from, and readily accessible from, air-conditioning and refrigerating equipment. It may be on or in the unit. | In play for #6 THHN CU WIRE, AHU FEEDS; #10 THHN CU WIRE, EQUIPMENT GROUND (AHU/CU); 3/4" EMT CONDUIT, CU FEEDS (ROOF); and 11 more. Shown: DISCONNECT SWITCH, 30A 3-POLE 480V NON-FUSED, NEMA 3R - CU-1, CU-2 (roof); DISCONNECT SWITCH, 30A 3-POLE 480V NON-FUSED, NEMA 3R (drawn WP) - AHU-1, AHU-2; EQUIPMENT CONNECTION, OUTDOOR, LIQUIDTIGHT FLEX WHIP 3/4" W/ 3#12 + #12G - CU-1; and 1 more. | RRE priced this on 5 of 5 past jobs (100%). RRE carries a disconnect at every unit with a disconnect symbol or note, sized from its circuit. |
NEC 2020 422.31, 424.19, 430.102 Disconnect for water heaters, heaters, fans and motor loads | shown | A disconnect within sight of the appliance, heater or motor, or a branch-circuit breaker that can be locked in the open position. | In play for JUNCTION BOX 4" SQ, WITH $T MOTOR-RATED SWITCH (B-5 MOTORIZED DAMPER / CV); MOTOR-RATED SWITCH $T WITH THERMAL OVERLOAD; EQUIPMENT CONNECTION, CONDENSATE PUMP (CP); and 4 more. Shown: DISCONNECT SWITCH, MOTOR-RATED TOGGLE, 1-POLE 20A 120V - EX-FX-1; DISCONNECT SWITCH, 30A 2-POLE 240V NON-FUSED, NEMA 1 (indoor) - EWH / WH-1 (AO Smith DEL-10, 2.5 kW 208V 1PH). | A lockable breaker answers it as well as a switch: check the panel schedule before adding a disconnect. |
NEC 2020 600.5(A) Sign outlet at each tenant entrance | shown | At least one outlet at each entrance to each tenant space accessible to pedestrians, for a sign, on a 20-ampere branch circuit that supplies no other load. | Shown: TERMINATION, BRANCH CIRCUIT, 20A 1-POLE; JUNCTION BOX 4" SQ AT SIGNAGE, WITH $T SWITCH; TOGGLE SWITCH, $T (SIGNAGE). | RRE prices "power to building signage" where the set shows it; the matrix row is left blank where it does not. |
NEC 2020 600.6 Disconnect within sight of a sign | shown | Each sign or outline lighting system, or its feeder, has an externally operable disconnect within sight of the sign, or one capable of being locked in the open position. | In play for TERMINATION, BRANCH CIRCUIT, 20A 1-POLE; JUNCTION BOX 4" SQ AT SIGNAGE, WITH $T SWITCH; TOGGLE SWITCH, $T (SIGNAGE). Shown: DISCONNECT SWITCH, 30A 3-POLE 480V NON-FUSED, NEMA 3R - CU-1, CU-2 (roof); DISCONNECT SWITCH, 30A 3-POLE 480V NON-FUSED, NEMA 3R (drawn WP) - AHU-1, AHU-2; BREAKER LOCK-ON DEVICE; and 4 more. | RRE prices a WP switch at signage as a fused disconnect assembly (firm practice wp_switch_mapping). |
NEC 2020 Chapter 9 Table 1, 358.22 Conduit fill | shown | Over two conductors, a raceway is filled to no more than 40 % of its internal area (Chapter 9 Tables 1, 4 and 5; THHN conductors, EMT). | All 4 callouts naming conductors and conduit are within it. | — |
A takeoff cannot settle every article: load calculations and coordination are the engineer of record’s, and workmanship is the inspector’s. Each is listed so nothing is silently skipped. “Waiting on a code read” means the article is in play and this job’s drawing read has not been checked against the code yet: re-run the read, or check it on the drawings.
| 90 | Introduction | general | Scope and definitions: nothing to check on a job. |
| 100 | Definitions | general | Scope and definitions: nothing to check on a job. |
| 110 | Requirements for Electrical Installations | to check | 1 section checked against the takeoff, 1 to check: 110.16. |
| 200 | Use and Identification of Grounded Conductors | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 210 | Branch Circuits | to check | 5 sections checked against the takeoff, 4 to check: 210.8(B)(2), 210.8(B)(1), 210.8(B), 210.63. |
| 215 | Feeders | checked | In play; none of its checked sections applies to these lines. |
| 220 | Branch-Circuit, Feeder, and Service Load Calculations | design | The engineer of record’s: sizing, calculation or coordination, not checked against a takeoff. |
| 225 | Outside Branch Circuits and Feeders | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 230 | Services | checked | In play; none of its checked sections applies to these lines. |
| 240 | Overcurrent Protection | checked | In play; none of its checked sections applies to these lines. |
| 242 | Overvoltage Protection | not in play | Nothing on this takeoff puts it in play. |
| 250 | Grounding and Bonding | checked | In play; none of its checked sections applies to these lines. |
| 300 | General Requirements for Wiring Methods and Materials | to check | 2 sections checked against the takeoff, 2 to check: 300.21, 300.11, 410.36(B). |
| 310 | Conductors for General Wiring | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 311 | Medium Voltage Conductors and Cable | not in play | Nothing on this takeoff puts it in play. |
| 312 | Cabinets, Cutout Boxes, and Meter Socket Enclosures | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 314 | Outlet, Device, Pull, and Junction Boxes; Conduit Bodies; Fittings; and Handhole Enclosures | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 320 | Armored Cable: Type AC | not in play | Nothing on this takeoff puts it in play. |
| 322 | Flat Cable Assemblies: Type FC | not in play | Nothing on this takeoff puts it in play. |
| 324 | Flat Conductor Cable: Type FCC | not in play | Nothing on this takeoff puts it in play. |
| 326 | Integrated Gas Spacer Cable: Type IGS | not in play | Nothing on this takeoff puts it in play. |
| 400 | Flexible Cords and Flexible Cables | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 402 | Fixture Wires | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 404 | Switches | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 406 | Receptacles, Cord Connectors, and Attachment Plugs (Caps) | checked | In play; none of its checked sections applies to these lines. |
| 408 | Switchboards, Switchgear, and Panelboards | checked | 1 section checked against the takeoff, all shown. |
| 409 | Industrial Control Panels | not in play | Nothing on this takeoff puts it in play. |
| 410 | Luminaires, Lampholders, and Lamps | checked | In play; none of its checked sections applies to these lines. |
| 411 | Low-Voltage Lighting | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 422 | Appliances | to check | 2 sections checked against the takeoff, 1 to check: 422.5(A). |
| 500 | Hazardous (Classified) Locations, Classes I, II, and III, Divisions 1 and 2 | not in play | Nothing on this takeoff puts it in play. |
| 501 | Class I Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 502 | Class II Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 503 | Class III Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 504 | Intrinsically Safe Systems | not in play | Nothing on this takeoff puts it in play. |
| 505 | Zone 0, 1, and 2 Locations | not in play | Nothing on this takeoff puts it in play. |
| 506 | Zone 20, 21, and 22 Locations for Combustible Dusts or Ignitible Fibers/Flyings | not in play | Nothing on this takeoff puts it in play. |
| 510 | Hazardous (Classified) Locations — Specific | not in play | Nothing on this takeoff puts it in play. |
| 511 | Commercial Garages, Repair and Storage | not in play | Nothing on this takeoff puts it in play. |
| 513 | Aircraft Hangars | not in play |
| 600 | Electric Signs and Outline Lighting | checked | 2 sections checked against the takeoff, all shown. |
| 604 | Manufactured Wiring Systems | not in play | Nothing on this takeoff puts it in play. |
| 605 | Office Furnishings | not in play | Nothing on this takeoff puts it in play. |
| 610 | Cranes and Hoists | not in play | Nothing on this takeoff puts it in play. |
| 620 | Elevators, Dumbwaiters, Escalators, Moving Walks, Platform Lifts, and Stairway Chairlifts | not in play | Nothing on this takeoff puts it in play. |
| 625 | Electric Vehicle Power Transfer System | not in play | Nothing on this takeoff puts it in play. |
| 626 | Electrified Truck Parking Spaces | not in play | Nothing on this takeoff puts it in play. |
| 630 | Electric Welders | not in play | Nothing on this takeoff puts it in play. |
| 640 | Audio Signal Processing, Amplification, and Reproduction Equipment | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 645 | Information Technology Equipment |
| 700 | Emergency Systems | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 701 | Legally Required Standby Systems | not in play | Nothing on this takeoff puts it in play. |
| 702 | Optional Standby Systems | not in play | Nothing on this takeoff puts it in play. |
| 705 | Interconnected Electric Power Production Sources | not in play | Nothing on this takeoff puts it in play. |
| 706 | Energy Storage Systems | not in play | Nothing on this takeoff puts it in play. |
| 708 | Critical Operations Power Systems (COPS) | not in play | Nothing on this takeoff puts it in play. |
| 710 | Stand-Alone Systems | not in play | Nothing on this takeoff puts it in play. |
| 712 | Direct Current Microgrids | not in play | Nothing on this takeoff puts it in play. |
| 720 | Circuits and Equipment Operating at Less Than 50 Volts | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 725 | Class 1, Class 2, and Class 3 Remote-Control, Signaling, and Power-Limited Circuits |
| 800 | General Requirements for Communications Systems | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 805 | Communications Circuits | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 810 | Radio and Television Antenna Equipment | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 820 | Community Antenna Television and Radio Distribution Systems | not in play | Nothing on this takeoff puts it in play. |
| 830 | Network-Powered Broadband Communications Systems | not in play | Nothing on this takeoff puts it in play. |
| 840 | Premises-Powered Broadband Communications Systems | not in play | Nothing on this takeoff puts it in play. |
| Ch. 9 | Tables: conduit fill, conductor properties, power-limited sources | checked | 1 section checked against the takeoff, all shown. |
| E-300 |
EXIT SIGN / EMERGENCY LIGHT, LED, 120V, 90-MIN BATTERY, TYPE EM2/EM3 PER A-004 (Rev 1 additional positions beyond E-300) Exit / emergency units drawn on A-004 Rev 1 egress plan in excess of the 7 exit signs counted on E-300: 13 EM2 + 4 EM3 = 17 drawn, less 7 on E-300 = 10. Furnish & install per E-200 EM schedule; unswitched on emergency circuit A-41. | LED GRN EXIT FIXTURE | 10 ea | A-004 |
EXIT SIGN, LED, 120V, 90-MIN BATTERY (schedule EX01/EX02, E-200 EM2/EM4) EXIT SIGN, LED, 120V, 90-MIN BATTERY (schedule EX01/EX02, E-200 EM2/EM4) | LED GRN EXIT FIXTURE | 7 ea | E-300 |
LIGHT FIXTURE TYPE BA/EM (schedule BA/EM) 4' suspended LED linear, 120V, with 90-min emergency battery, Bartco BSS210-...-WH+ED, back of house | LED EMERGENCYLIGHT DUAL | 3 ea | A-130 |
LIGHT FIXTURE TYPE QA/EM (schedule QA/EM) Recessed LED 2x2 flat panel, 120V, 31W, with 90-min emergency battery backup, C-Light C-TR-C-FP22-37L-35K-Wh | LED EMERGENCYLIGHT DUAL | 1 ea | A-130 |
Read off the schedules and notes. RRE buys none of the material named here. Check each against the responsibility matrix on the proposal: these are what it should say is by others.
| Line | Furnished by | Installed by | RRE’s part | Sheet |
|---|---|---|---|---|
1" CONDUIT STUB, LOW VOLTAGE DATA AT CASH WRAP The drawings say “by gc”. | GC | not stated | RRE installs / connects only | E-400 |
LIGHT FIXTURE TYPE S02 (schedule S02) The drawings say “owner furnished”. | Owner | not stated | RRE installs / connects only | A-130 |
LOW VOLTAGE BACKBOX, 4-SQ WITH SINGLE-GANG MUD RING AND 3/4" EMT STUB, TRACK-MOUNT SPEAKER (ST) CONNECTION POINT The drawings say “by gc.”. | GC | not stated | RRE installs / connects only | A-150 |
LUTRON VIVE POWPAK PHASE-SELECT MODULE RMJS-PNE-DV, INSTALL ONLY (vendor-furnished), ON 4-SQ J-BOX The drawings say “vendor-furnished”. | Vendor | not stated | RRE installs / connects only | E-900 |
LOW VOLTAGE BACKBOX, 4-SQ 2-1/8" DEEP WITH SINGLE-GANG MUD RING AND 3/4" EMT STUB TO ACCESSIBLE CEILING, WIFI ACCESS POINT (CEILING) The drawings say “by gc.”. | GC | not stated | RRE installs / connects only | A-150 |
LOW VOLTAGE BACKBOX, 4-SQ WITH SINGLE-GANG MUD RING AND 3/4" EMT STUB, CCTV CAMERA (CEILING) The drawings say “by gc”. | GC | not stated | RRE installs / connects only | A-150 |
LUTRON PICO WIRELESS DIMMER/SWITCH ('VS' symbol) - install on wall box/mount, vendor furnished The drawings say “vendor furnished”. | Vendor | not stated | RRE installs / connects only | E-300 |
LUTRON VIVE WIRELESS OCCUPANCY SENSOR, CEILING (OS symbol) - install only, vendor furnished The drawings say “vendor furnished”. | Vendor | not stated | RRE installs / connects only | E-300 |
LUTRON VIVE POWPAK RELAY MODULE RMJS-16R-DV-B, INSTALL ONLY (vendor-furnished), ON 4-SQ J-BOX The drawings say “vendor-furnished”. | Vendor | not stated | RRE installs / connects only | E-900 |
LUTRON VIVE HUB HJS-1, INSTALL ONLY (vendor-furnished), ON 4X4 J-BOX W/ 120V FEED The drawings say “vendor-furnished”. | Vendor | not stated | RRE installs / connects only | E-900 |
TENANT ELECTRIC SUBMETER, QUADLOGIC RSM5 OR S20 (landlord-specified), for main tenant electrical system The drawings say “furnished by landlord or tenant”. | Landlord | not stated | RRE installs / connects only | 000-Copy-of-2498-A-set-2025-0530-Revision-1-p1 |
RECEPTACLE 20A 125V DUPLEX, DEDICATED, FOR REFRIGERATED DRINKING FOUNTAIN FX-3 (ELKAY EZTL8C + LKAPREZL), IN 4" SQ BOX The drawings say “installed by gc”. | GC | GC | RRE installs / connects only | A-120 |
LOW VOLTAGE BACKBOX, SINGLE-GANG WITH 3/4" EMT STUB, SUBWOOFER (SW) CONNECTION POINT The drawings say “by gc”. | GC | not stated | RRE installs / connects only | A-150 |
BACKBOX, 4" SQUARE x 2-1/8" DEEP WITH 1-GANG MUD RING, WITH 3/4" EMT STUB TO ACCESSIBLE CEILING, PULL STRING - ALARM KEYPAD AT DOOR 05 (SALES SIDE) The drawings say “by tenant”. | Tenant | not stated | RRE installs / connects only | A-500 |
TRACK, LINE-VOLTAGE 120V SINGLE-CIRCUIT, SURFACE/SUSPENDED (tracks 1-7) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E-300 |
LIGHT FIXTURE TYPE E06W (schedule E06w) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | Owner | not stated | Struck: not in this bid | A-130 |
LED DRIVER / TRANSFORMER 75W 24VDC CLASS 2, REMOTE MOUNT (XLG-75 series) FOR S02 SCONCES, WITH J-BOX Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | A-130 |
TRANSFORMER / REMOTE LED DRIVER (spec 26-50.23), CONCEALED ABOVE DISPLAY CEILING IN TAPED-IN ACCESS PANEL - INSTALL & CONNECT, WITH 4" SQ J-BOX AND FLEX WHIP Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | GC | not stated | Struck: not in this bid | A-210 |
EXISTING DUCT SMOKE DETECTOR RECONNECTION TO NEW AHU (UNIT SHUTDOWN INTERLOCK), EXISTING DETECTOR TO REMAIN Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | M-300 |
LED REMOTE TRANSFORMER / DRIVER, CLASS 2, CONCEALED IN MILLWORK CABINET (spec 26-50.23) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | A-410 |
JUNCTION BOX 4" SQ, 120V FEED TO REMOTE LED TRANSFORMER IN MILLWORK Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | A-410 |
| 330 | Metal-Clad Cable: Type MC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 332 | Mineral-Insulated, Metal-Sheathed Cable: Type MI | not in play | Nothing on this takeoff puts it in play. |
| 334 | Nonmetallic-Sheathed Cable: Types NM and NMC | not in play | Nothing on this takeoff puts it in play. |
| 336 | Power and Control Tray Cable: Type TC | not in play | Nothing on this takeoff puts it in play. |
| 337 | Type P Cable | not in play | Nothing on this takeoff puts it in play. |
| 338 | Service-Entrance Cable: Types SE and USE | not in play | Nothing on this takeoff puts it in play. |
| 340 | Underground Feeder and Branch-Circuit Cable: Type UF | not in play | Nothing on this takeoff puts it in play. |
| 342 | Intermediate Metal Conduit: Type IMC | not in play | Nothing on this takeoff puts it in play. |
| 344 | Rigid Metal Conduit: Type RMC | not in play | Nothing on this takeoff puts it in play. |
| 348 | Flexible Metal Conduit: Type FMC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 350 | Liquidtight Flexible Metal Conduit: Type LFMC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 352 | Rigid Polyvinyl Chloride Conduit: Type PVC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 353 | High Density Polyethylene Conduit: Type HDPE Conduit | not in play | Nothing on this takeoff puts it in play. |
| 354 | Nonmetallic Underground Conduit with Conductors: Type NUCC | not in play | Nothing on this takeoff puts it in play. |
| 355 | Reinforced Thermosetting Resin Conduit: Type RTRC | not in play | Nothing on this takeoff puts it in play. |
| 356 | Liquidtight Flexible Nonmetallic Conduit: Type LFNC | not in play | Nothing on this takeoff puts it in play. |
| 358 | Electrical Metallic Tubing: Type EMT | checked | In play; none of its checked sections applies to these lines. |
| 360 | Flexible Metallic Tubing: Type FMT | not in play | Nothing on this takeoff puts it in play. |
| 362 | Electrical Nonmetallic Tubing: Type ENT | not in play | Nothing on this takeoff puts it in play. |
| 366 | Auxiliary Gutters | not in play | Nothing on this takeoff puts it in play. |
| 368 | Busways | not in play | Nothing on this takeoff puts it in play. |
| 369 | Insulated Bus Pipe (IBP)/Tubular Covered Conductors (TCC) Systems | not in play | Nothing on this takeoff puts it in play. |
| 370 | Cablebus | not in play | Nothing on this takeoff puts it in play. |
| 371 | Flexible Bus Systems | not in play | Nothing on this takeoff puts it in play. |
| 372 | Cellular Concrete Floor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 374 | Cellular Metal Floor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 376 | Metal Wireways | not in play | Nothing on this takeoff puts it in play. |
| 378 | Nonmetallic Wireways | not in play | Nothing on this takeoff puts it in play. |
| 380 | Multioutlet Assembly | not in play | Nothing on this takeoff puts it in play. |
| 382 | Nonmetallic Extensions | not in play | Nothing on this takeoff puts it in play. |
| 384 | Strut-Type Channel Raceway | not in play | Nothing on this takeoff puts it in play. |
| 386 | Surface Metal Raceways | not in play | Nothing on this takeoff puts it in play. |
| 388 | Surface Nonmetallic Raceways | not in play | Nothing on this takeoff puts it in play. |
| 390 | Underfloor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 392 | Cable Trays | not in play | Nothing on this takeoff puts it in play. |
| 393 | Low-Voltage Suspended Ceiling Power Distribution Systems | not in play | Nothing on this takeoff puts it in play. |
| 394 | Concealed Knob-and-Tube Wiring | not in play | Nothing on this takeoff puts it in play. |
| 396 | Messenger-Supported Wiring | not in play | Nothing on this takeoff puts it in play. |
| 398 | Open Wiring on Insulators | not in play | Nothing on this takeoff puts it in play. |
| 399 | Outdoor, Overhead Conductors over 1000 Volts | not in play | Nothing on this takeoff puts it in play. |
| 424 |
| Fixed Electric Space-Heating Equipment |
| not in play |
| Nothing on this takeoff puts it in play. |
| 425 | Fixed Resistance and Electrode Industrial Process Heating Equipment | not in play | Nothing on this takeoff puts it in play. |
| 426 | Fixed Outdoor Electric Deicing and Snow-Melting Equipment | not in play | Nothing on this takeoff puts it in play. |
| 427 | Fixed Electric Heating Equipment for Pipelines and Vessels | not in play | Nothing on this takeoff puts it in play. |
| 430 | Motors, Motor Circuits, and Controllers | checked | In play; none of its checked sections applies to these lines. |
| 440 | Air-Conditioning and Refrigerating Equipment | checked | 1 section checked against the takeoff, all shown. |
| 445 | Generators | not in play | Nothing on this takeoff puts it in play. |
| 450 | Transformers and Transformer Vaults (Including Secondary Ties) | not in play | Nothing on this takeoff puts it in play. |
| 455 | Phase Converters | not in play | Nothing on this takeoff puts it in play. |
| 460 | Capacitors | not in play | Nothing on this takeoff puts it in play. |
| 470 | Resistors and Reactors | not in play | Nothing on this takeoff puts it in play. |
| 480 | Stationary Standby Batteries | not in play | Nothing on this takeoff puts it in play. |
| 490 | Equipment Over 1000 Volts, Nominal | not in play | Nothing on this takeoff puts it in play. |
| Nothing on this takeoff puts it in play. |
| 514 | Motor Fuel Dispensing Facilities | not in play | Nothing on this takeoff puts it in play. |
| 515 | Bulk Storage Plants | not in play | Nothing on this takeoff puts it in play. |
| 516 | Spray Application, Dipping, Coating, and Printing Processes | not in play | Nothing on this takeoff puts it in play. |
| 517 | Health Care Facilities | not in play | Nothing on this takeoff puts it in play. |
| 518 | Assembly Occupancies | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 520 | Theaters, Audience Areas of Motion Picture and Television Studios, Performance Areas, and Similar Locations | not in play | Nothing on this takeoff puts it in play. |
| 522 | Control Systems for Permanent Amusement Attractions | not in play | Nothing on this takeoff puts it in play. |
| 525 | Carnivals, Circuses, Fairs, and Similar Events | not in play | Nothing on this takeoff puts it in play. |
| 530 | Motion Picture and Television Studios and Similar Locations | not in play | Nothing on this takeoff puts it in play. |
| 540 | Motion Picture Projection Rooms | not in play | Nothing on this takeoff puts it in play. |
| 545 | Manufactured Buildings and Relocatable Structures | not in play | Nothing on this takeoff puts it in play. |
| 547 | Agricultural Buildings | not in play | Nothing on this takeoff puts it in play. |
| 550 | Mobile Homes, Manufactured Homes, and Mobile Home Parks | not in play | Nothing on this takeoff puts it in play. |
| 551 | Recreational Vehicles and Recreational Vehicle Parks | not in play | Nothing on this takeoff puts it in play. |
| 552 | Park Trailers | not in play | Nothing on this takeoff puts it in play. |
| 555 | Marinas, Boatyards, Floating Buildings, and Commercial and Noncommercial Docking Facilities | not in play | Nothing on this takeoff puts it in play. |
| 590 | Temporary Installations | not in play | Nothing on this takeoff puts it in play. |
| Nothing on this takeoff puts it in play. |
| 646 | Modular Data Centers | not in play | Nothing on this takeoff puts it in play. |
| 647 | Sensitive Electronic Equipment | not in play | Nothing on this takeoff puts it in play. |
| 650 | Pipe Organs | not in play | Nothing on this takeoff puts it in play. |
| 660 | X-Ray Equipment | not in play | Nothing on this takeoff puts it in play. |
| 665 | Induction and Dielectric Heating Equipment | not in play | Nothing on this takeoff puts it in play. |
| 668 | Electrolytic Cells | not in play | Nothing on this takeoff puts it in play. |
| 669 | Electroplating | not in play | Nothing on this takeoff puts it in play. |
| 670 | Industrial Machinery | not in play | Nothing on this takeoff puts it in play. |
| 675 | Electrically Driven or Controlled Irrigation Machines | not in play | Nothing on this takeoff puts it in play. |
| 680 | Swimming Pools, Fountains, and Similar Installations | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 682 | Natural and Artificially Made Bodies of Water | not in play | Nothing on this takeoff puts it in play. |
| 685 | Integrated Electrical Systems | not in play | Nothing on this takeoff puts it in play. |
| 690 | Solar Photovoltaic (PV) Systems | not in play | Nothing on this takeoff puts it in play. |
| 691 | Large-Scale Photovoltaic (PV) Electric Supply Stations | not in play | Nothing on this takeoff puts it in play. |
| 692 | Fuel Cell Systems | not in play | Nothing on this takeoff puts it in play. |
| 694 | Wind Electric Systems | not in play | Nothing on this takeoff puts it in play. |
| 695 | Fire Pumps | not in play | Nothing on this takeoff puts it in play. |
| not read yet |
| In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 727 | Instrumentation Tray Cable: Type ITC | not in play | Nothing on this takeoff puts it in play. |
| 728 | Fire-Resistive Cable Systems | not in play | Nothing on this takeoff puts it in play. |
| 750 | Energy Management Systems | not in play | Nothing on this takeoff puts it in play. |
| 760 | Fire Alarm Systems | checked | In play; none of its checked sections applies to these lines. |
| 770 | Optical Fiber Cables | not in play | Nothing on this takeoff puts it in play. |