Derived from what the read produced, so none of it can drift from the data behind it. A blocker stops a price being presented as complete; it never stops you looking. These definitions are this build’s own — no RRE document specifies them yet.
| Check | Status | What the check found |
|---|---|---|
| Sheet scale | blocker | Scale is UNSET on 4 of 8 plan sheet(s): A-004, A-092, A-130, A-150. Nothing on them has been measured, so there is no raceway and no branch wire — together the largest block of material on a job of this kind. Set the scale from each title block on the Drawings screen. |
| Sheets read for scope | warning | 27 sheet(s) were indexed but not read for scope: A-008, A-009, A-010, A-011, A-012, A-013, A-014, A-091, A-110, A-111, A-460, A-501, M-200, M-500, M-501, M-600, M-601, M-602, P-101, P-200, P-300, P-301, S100, FP-1, 007-rocklinelectric.net-Mail---Fwd_-Mango--...ion---Invitation-to-bid-DUE-05_08_2025-p1, 007-rocklinelectric.net-Mail---Fwd_-Mango--...ion---Invitation-to-bid-DUE-05_08_2025-p2, 007-rocklinelectric.net-Mail---Fwd_-Mango--...ion---Invitation-to-bid-DUE-05_08_2025-p3. Looked at by the takeoff and not read: no electrical work on it. Read them, or state the omission on the proposal — the basis of the offer already prints it. |
| Symbol source | pass | A symbol list was found on the drawings: 000-Copy-of-2498-A-set-2025-0530-Revision-1-p1 — COVER PAGE, E-100 — ELECTRICAL SPECIFICATIONS, E-200 — SYMBOLS LIST. The project legend is authoritative for this set and outranks everything else — NECA 100-2006 itself allows a drawing to use non-standard symbols provided the legend explains them. NECA 100-2006 stays underneath it for anything the legend leaves silent, and no conventions file exists for the engineering firm. |
| Symbols named | pass | All 641 marks belong to a named group. |
| Every line prices | pass | Every line points at an assembly. |
| Plan and schedule agree | pass | No line has a plan/schedule disagreement. |
| Lines accepted by a person | blocker | Nothing has been accepted. All 112 line(s) are still suggestions, and machine output is a suggestion until a named person accepts it. Accept on the Takeoff screen — 112 line(s) are ready. |
| Engineer conventions known | pass | No engineer-dependent lines. |
| Unsure flags resolved | pass | The model raised no open flags. |
| Cover sheet read | pass | A cover sheet was found and read; its notes parameterise every later pass. |
What the symbol names rest on. The set’s own legend (000-Copy-of-2498-A-set-2025-0530-Revision-1-p1, E-100, E-200), which is authoritative for this project.
Edition: 2022 California Electrical Code, because in force for permits from 2023-01-01, as of the bid date 2025-05-08. City and county amendments are the AHJ’s: check them on any job inside a city that amends the code. “To check” means the code requires it and the drawings do not show it: send an RFI, or make the call. Nothing here is added to the bid on its own.
| Section | Status | What the code requires | What the takeoff shows | RRE’s practice |
|---|---|---|---|---|
NEC 2020 110.16 Arc-flash warning label on gear | to check | Switchboards, switchgear, panelboards, meter socket enclosures and motor control centers likely to be worked on energized carry a field- or factory-applied arc-flash hazard warning. | In play for PANELBOARD, CURRENT LIMITING, 120V 1PH 2W, 20-POLE, SURFACE (Lighting Control & Design GR 2400 'The Silverbullet') - panel 'CL'. Nothing on the takeoff shows it. | RRE carries phenolic nameplates and labels as their own item where the set calls for them. |
NEC 2020 210.8(B)(2) GFCI on commercial kitchen receptacles | to check | GFCI protection for every receptacle in a commercial kitchen: single-phase up to 50 A and three-phase up to 100 A, 150 V to ground or less. | 1 of 2 in play are not shown with it: TERMINATION, BRANCH CIRCUIT, 20A 1-POLE. | RRE carries a GFCI receptacle at the device where the set calls for GFCI, and adds none on code alone (Mango: no GFCI bid; The Melt: 25 where the set said so). |
NEC 2020 210.8(B)(1) GFCI on bathroom receptacles | to check | GFCI protection for every receptacle in a bathroom: single-phase up to 50 A and three-phase up to 100 A, 150 V to ground or less. | In play for TERMINATION, BRANCH CIRCUIT, 20A 1-POLE; DUPLEX RECEPTACLE 20A 125V, RESTROOM (B-11); RECEPTACLE 20A 125V DUPLEX, DEDICATED, FOR REFRIGERATED DRINKING FOUNTAIN FX-3 (ELKAY EZTL8C + LKAPREZL), IN 4" SQ BOX. Nothing on the takeoff shows it. |
The RRE item carries no price for the part named, so the estimate has the install labor and rough-in only, and the vendor or sub prices the rest. Send the lighting and gear lists from Material list & vendor quotes.
| Line | Needs a price for | Count | Sheet |
|---|---|---|---|
LIGHT FIXTURE TYPE LAL (schedule LAL) - LED strip / millwork linear, remote driver LIGHT FIXTURE TYPE LAL (schedule LAL) - LED strip / millwork linear, remote driver | LED REMOTE DRIVER | 153.8 ft | E-300 |
LIGHT FIXTURE TYPE LAF (schedule LAF) - LED strip / millwork linear, remote driver LIGHT FIXTURE TYPE LAF (schedule LAF) - LED strip / millwork linear, remote driver | LED REMOTE DRIVER | 125.3 ft | E-300 |
LIGHT FIXTURE TYPE P15.1W (schedule P15.1w) - track head LIGHT FIXTURE TYPE P15.1W (schedule P15.1w) - track head | LED TRACK SPOT FIXTURE | 115 ea | E-300 |
LIGHT FIXTURE TYPE P08.1W (schedule P08.1w) - track head LIGHT FIXTURE TYPE P08.1W (schedule P08.1w) - track head | LED TRACK SPOT FIXTURE | 95 ea | E-300 |
EMERGENCY BATTERY PACK, 90-MIN, FIELD-INSTALLED IN FIXTURE (tag /EMB, lighting note 6) EMERGENCY BATTERY PACK, 90-MIN, FIELD-INSTALLED IN FIXTURE (tag /EMB, lighting note 6) | LED EMERGENCYLIGHT DUAL | 18 ea |
9 lines the reader wrote at zero are not listed: they add nothing to the bid.
Nothing in this tab.
| RRE carries GFCI at the device where the set calls for it. |
NEC 2020 210.8(B) GFCI near sinks, in locker rooms, wet and damp locations | to check | GFCI protection for receptacles within 6 ft of a sink, in locker rooms with showers, in indoor wet or damp locations, and in garages, service bays and similar areas. | In play for TERMINATION, BRANCH CIRCUIT, 20A 1-POLE. Nothing on the takeoff shows it. | — |
NEC 2020 210.63 Service receptacle at HVAC equipment | to check | A 125-volt, 15- or 20-ampere receptacle on the same level and within 25 ft of heating, air-conditioning and refrigeration equipment, not on the load side of the equipment disconnect. | In play for #6 THHN CU WIRE, AHU FEEDS; #10 THHN CU WIRE, EQUIPMENT GROUND (AHU/CU); 3/4" EMT CONDUIT, CU FEEDS (ROOF); and 11 more. Nothing on the takeoff shows it. | RRE carries the roof receptacle where the set draws one (reading check 11). |
NEC 2020 300.21 Firestopping at rated penetrations | to check | Electrical penetrations of fire-resistance-rated walls, partitions, floors or ceilings firestopped by an approved method that keeps the rating. | In play for TENMAT FIRE-RATED COVER OVER RECESSED DOWNLIGHT. Nothing on the takeoff shows it. | — |
NEC 2020 300.11, 410.36(B) Support in suspended ceilings | to check | Raceways, cables and boxes above a suspended ceiling are supported independently of the ceiling grid, or by identified support wires; lay-in luminaires are fastened to the grid framing. | In play for LIGHT FIXTURE TYPE QA (schedule QA); LIGHT FIXTURE TYPE QA/EM (schedule QA/EM). Nothing on the takeoff shows it. | RRE carries the fixture support wire as its own item where the ceiling is a grid. |
NEC 2020 422.5(A) GFCI on drinking water coolers, bottle fillers and vending machines | to check | GFCI protection for the appliances 422.5(A) lists, among them drinking water coolers, bottle fill stations, vending machines and high-pressure spray washers. | In play for RECEPTACLE 20A 125V DUPLEX, DEDICATED, FOR REFRIGERATED DRINKING FOUNTAIN FX-3 (ELKAY EZTL8C + LKAPREZL), IN 4" SQ BOX. Nothing on the takeoff shows it. | — |
NEC 2020 210.62 Receptacles in show windows | shown | At least one 125-volt receptacle within 18 in. of the top of a show window for each 12 linear ft of show window. | In play for RECEPTACLE AT WINDOW DISPLAY, LABELLED CLG / FLR (A-6). Shown: RECEPTACLE AT WINDOW DISPLAY, LABELLED CLG / FLR (A-6). | — |
NEC 2020 408.4(A) Circuit directory at every panel | shown | Every circuit and circuit modification legibly identified as to its clear, evident and specific purpose on a circuit directory at the panel. | In play for PANELBOARD, CURRENT LIMITING, 120V 1PH 2W, 20-POLE, SURFACE (Lighting Control & Design GR 2400 'The Silverbullet') - panel 'CL'. Shown: PANEL DIRECTORY, TYPED. | RRE carries a panel directory update where circuits land in an existing panel. |
NEC 2020 440.14 Disconnect within sight of HVAC equipment | shown | A disconnecting means within sight from, and readily accessible from, air-conditioning and refrigerating equipment. It may be on or in the unit. | In play for #6 THHN CU WIRE, AHU FEEDS; #10 THHN CU WIRE, EQUIPMENT GROUND (AHU/CU); 3/4" EMT CONDUIT, CU FEEDS (ROOF); and 11 more. Shown: DISCONNECT SWITCH, 30A 3-POLE 480V NON-FUSED, NEMA 3R - CU-1, CU-2 (roof); DISCONNECT SWITCH, 30A 3-POLE 480V NON-FUSED, NEMA 3R (drawn WP) - AHU-1, AHU-2; EQUIPMENT CONNECTION, OUTDOOR, LIQUIDTIGHT FLEX WHIP 3/4" W/ 3#12 + #12G - CU-1; and 1 more. | RRE priced this on 5 of 5 past jobs (100%). RRE carries a disconnect at every unit with a disconnect symbol or note, sized from its circuit. |
NEC 2020 422.31, 424.19, 430.102 Disconnect for water heaters, heaters, fans and motor loads | shown | A disconnect within sight of the appliance, heater or motor, or a branch-circuit breaker that can be locked in the open position. | In play for JUNCTION BOX 4" SQ, WITH $T MOTOR-RATED SWITCH (B-5 MOTORIZED DAMPER / CV); MOTOR-RATED SWITCH $T WITH THERMAL OVERLOAD; EQUIPMENT CONNECTION, CONDENSATE PUMP (CP); and 4 more. Shown: DISCONNECT SWITCH, MOTOR-RATED TOGGLE, 1-POLE 20A 120V - EX-FX-1; DISCONNECT SWITCH, 30A 2-POLE 240V NON-FUSED, NEMA 1 (indoor) - EWH / WH-1 (AO Smith DEL-10, 2.5 kW 208V 1PH). | A lockable breaker answers it as well as a switch: check the panel schedule before adding a disconnect. |
NEC 2020 600.5(A) Sign outlet at each tenant entrance | shown | At least one outlet at each entrance to each tenant space accessible to pedestrians, for a sign, on a 20-ampere branch circuit that supplies no other load. | Shown: TERMINATION, BRANCH CIRCUIT, 20A 1-POLE; JUNCTION BOX 4" SQ AT SIGNAGE, WITH $T SWITCH; TOGGLE SWITCH, $T (SIGNAGE). | RRE prices "power to building signage" where the set shows it; the matrix row is left blank where it does not. |
NEC 2020 600.6 Disconnect within sight of a sign | shown | Each sign or outline lighting system, or its feeder, has an externally operable disconnect within sight of the sign, or one capable of being locked in the open position. | In play for TERMINATION, BRANCH CIRCUIT, 20A 1-POLE; JUNCTION BOX 4" SQ AT SIGNAGE, WITH $T SWITCH; TOGGLE SWITCH, $T (SIGNAGE). Shown: DISCONNECT SWITCH, 30A 3-POLE 480V NON-FUSED, NEMA 3R - CU-1, CU-2 (roof); DISCONNECT SWITCH, 30A 3-POLE 480V NON-FUSED, NEMA 3R (drawn WP) - AHU-1, AHU-2; BREAKER LOCK-ON DEVICE; and 4 more. | RRE prices a WP switch at signage as a fused disconnect assembly (firm practice wp_switch_mapping). |
NEC 2020 Chapter 9 Table 1, 358.22 Conduit fill | shown | Over two conductors, a raceway is filled to no more than 40 % of its internal area (Chapter 9 Tables 1, 4 and 5; THHN conductors, EMT). | All 4 callouts naming conductors and conduit are within it. | — |
A takeoff cannot settle every article: load calculations and coordination are the engineer of record’s, and workmanship is the inspector’s. Each is listed so nothing is silently skipped. “Waiting on a code read” means the article is in play and this job’s drawing read has not been checked against the code yet: re-run the read, or check it on the drawings.
| 90 | Introduction | general | Scope and definitions: nothing to check on a job. |
| 100 | Definitions | general | Scope and definitions: nothing to check on a job. |
| 110 | Requirements for Electrical Installations | to check | 1 section checked against the takeoff, 1 to check: 110.16. |
| 200 | Use and Identification of Grounded Conductors | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 210 | Branch Circuits | to check | 5 sections checked against the takeoff, 4 to check: 210.8(B)(2), 210.8(B)(1), 210.8(B), 210.63. |
| 215 | Feeders | checked | In play; none of its checked sections applies to these lines. |
| 220 | Branch-Circuit, Feeder, and Service Load Calculations | design | The engineer of record’s: sizing, calculation or coordination, not checked against a takeoff. |
| 225 | Outside Branch Circuits and Feeders | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 230 | Services | checked | In play; none of its checked sections applies to these lines. |
| 240 | Overcurrent Protection | checked | In play; none of its checked sections applies to these lines. |
| 242 | Overvoltage Protection | not in play | Nothing on this takeoff puts it in play. |
| 250 | Grounding and Bonding | checked | In play; none of its checked sections applies to these lines. |
| 300 | General Requirements for Wiring Methods and Materials | to check | 2 sections checked against the takeoff, 2 to check: 300.21, 300.11, 410.36(B). |
| 310 | Conductors for General Wiring | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 311 | Medium Voltage Conductors and Cable | not in play | Nothing on this takeoff puts it in play. |
| 312 | Cabinets, Cutout Boxes, and Meter Socket Enclosures | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 314 | Outlet, Device, Pull, and Junction Boxes; Conduit Bodies; Fittings; and Handhole Enclosures | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 320 | Armored Cable: Type AC | not in play | Nothing on this takeoff puts it in play. |
| 322 | Flat Cable Assemblies: Type FC | not in play | Nothing on this takeoff puts it in play. |
| 324 | Flat Conductor Cable: Type FCC | not in play | Nothing on this takeoff puts it in play. |
| 326 | Integrated Gas Spacer Cable: Type IGS | not in play | Nothing on this takeoff puts it in play. |
| 400 | Flexible Cords and Flexible Cables | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 402 | Fixture Wires | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 404 | Switches | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 406 | Receptacles, Cord Connectors, and Attachment Plugs (Caps) | checked | In play; none of its checked sections applies to these lines. |
| 408 | Switchboards, Switchgear, and Panelboards | checked | 1 section checked against the takeoff, all shown. |
| 409 | Industrial Control Panels | not in play | Nothing on this takeoff puts it in play. |
| 410 | Luminaires, Lampholders, and Lamps | checked | In play; none of its checked sections applies to these lines. |
| 411 | Low-Voltage Lighting | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 422 | Appliances | to check | 2 sections checked against the takeoff, 1 to check: 422.5(A). |
| 500 | Hazardous (Classified) Locations, Classes I, II, and III, Divisions 1 and 2 | not in play | Nothing on this takeoff puts it in play. |
| 501 | Class I Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 502 | Class II Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 503 | Class III Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 504 | Intrinsically Safe Systems | not in play | Nothing on this takeoff puts it in play. |
| 505 | Zone 0, 1, and 2 Locations | not in play | Nothing on this takeoff puts it in play. |
| 506 | Zone 20, 21, and 22 Locations for Combustible Dusts or Ignitible Fibers/Flyings | not in play | Nothing on this takeoff puts it in play. |
| 510 | Hazardous (Classified) Locations — Specific | not in play | Nothing on this takeoff puts it in play. |
| 511 | Commercial Garages, Repair and Storage | not in play | Nothing on this takeoff puts it in play. |
| 513 | Aircraft Hangars | not in play |
| 600 | Electric Signs and Outline Lighting | checked | 2 sections checked against the takeoff, all shown. |
| 604 | Manufactured Wiring Systems | not in play | Nothing on this takeoff puts it in play. |
| 605 | Office Furnishings | not in play | Nothing on this takeoff puts it in play. |
| 610 | Cranes and Hoists | not in play | Nothing on this takeoff puts it in play. |
| 620 | Elevators, Dumbwaiters, Escalators, Moving Walks, Platform Lifts, and Stairway Chairlifts | not in play | Nothing on this takeoff puts it in play. |
| 625 | Electric Vehicle Power Transfer System | not in play | Nothing on this takeoff puts it in play. |
| 626 | Electrified Truck Parking Spaces | not in play | Nothing on this takeoff puts it in play. |
| 630 | Electric Welders | not in play | Nothing on this takeoff puts it in play. |
| 640 | Audio Signal Processing, Amplification, and Reproduction Equipment | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 645 | Information Technology Equipment |
| 700 | Emergency Systems | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 701 | Legally Required Standby Systems | not in play | Nothing on this takeoff puts it in play. |
| 702 | Optional Standby Systems | not in play | Nothing on this takeoff puts it in play. |
| 705 | Interconnected Electric Power Production Sources | not in play | Nothing on this takeoff puts it in play. |
| 706 | Energy Storage Systems | not in play | Nothing on this takeoff puts it in play. |
| 708 | Critical Operations Power Systems (COPS) | not in play | Nothing on this takeoff puts it in play. |
| 710 | Stand-Alone Systems | not in play | Nothing on this takeoff puts it in play. |
| 712 | Direct Current Microgrids | not in play | Nothing on this takeoff puts it in play. |
| 720 | Circuits and Equipment Operating at Less Than 50 Volts | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 725 | Class 1, Class 2, and Class 3 Remote-Control, Signaling, and Power-Limited Circuits |
| 800 | General Requirements for Communications Systems | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 805 | Communications Circuits | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 810 | Radio and Television Antenna Equipment | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 820 | Community Antenna Television and Radio Distribution Systems | not in play | Nothing on this takeoff puts it in play. |
| 830 | Network-Powered Broadband Communications Systems | not in play | Nothing on this takeoff puts it in play. |
| 840 | Premises-Powered Broadband Communications Systems | not in play | Nothing on this takeoff puts it in play. |
| Ch. 9 | Tables: conduit fill, conductor properties, power-limited sources | checked | 1 section checked against the takeoff, all shown. |
| E-300 |
EXIT SIGN / EMERGENCY LIGHT, LED, 120V, 90-MIN BATTERY, TYPE EM2/EM3 PER A-004 (Rev 1 additional positions beyond E-300) Exit / emergency units drawn on A-004 Rev 1 egress plan in excess of the 7 exit signs counted on E-300: 13 EM2 + 4 EM3 = 17 drawn, less 7 on E-300 = 10. Furnish & install per E-200 EM schedule; unswitched on emergency circuit A-41. | LED GRN EXIT FIXTURE | 10 ea | A-004 |
EXIT SIGN, LED, 120V, 90-MIN BATTERY (schedule EX01/EX02, E-200 EM2/EM4) EXIT SIGN, LED, 120V, 90-MIN BATTERY (schedule EX01/EX02, E-200 EM2/EM4) | LED GRN EXIT FIXTURE | 7 ea | E-300 |
LIGHT FIXTURE TYPE BA/EM (schedule BA/EM) 4' suspended LED linear, 120V, with 90-min emergency battery, Bartco BSS210-...-WH+ED, back of house | LED EMERGENCYLIGHT DUAL | 3 ea | A-130 |
LIGHT FIXTURE TYPE QA/EM (schedule QA/EM) Recessed LED 2x2 flat panel, 120V, 31W, with 90-min emergency battery backup, C-Light C-TR-C-FP22-37L-35K-Wh | LED EMERGENCYLIGHT DUAL | 1 ea | A-130 |
Read off the schedules and notes. RRE buys none of the material named here. Check each against the responsibility matrix on the proposal: these are what it should say is by others.
| Line | Furnished by | Installed by | RRE’s part | Sheet |
|---|---|---|---|---|
1" CONDUIT STUB, LOW VOLTAGE DATA AT CASH WRAP The drawings say “by gc”. | GC | not stated | RRE installs / connects only | E-400 |
LIGHT FIXTURE TYPE S02 (schedule S02) The drawings say “owner furnished”. | Owner | not stated | RRE installs / connects only | A-130 |
LOW VOLTAGE BACKBOX, 4-SQ WITH SINGLE-GANG MUD RING AND 3/4" EMT STUB, TRACK-MOUNT SPEAKER (ST) CONNECTION POINT The drawings say “by gc.”. | GC | not stated | RRE installs / connects only | A-150 |
LUTRON VIVE POWPAK PHASE-SELECT MODULE RMJS-PNE-DV, INSTALL ONLY (vendor-furnished), ON 4-SQ J-BOX The drawings say “vendor-furnished”. | Vendor | not stated | RRE installs / connects only | E-900 |
LOW VOLTAGE BACKBOX, 4-SQ 2-1/8" DEEP WITH SINGLE-GANG MUD RING AND 3/4" EMT STUB TO ACCESSIBLE CEILING, WIFI ACCESS POINT (CEILING) The drawings say “by gc.”. | GC | not stated | RRE installs / connects only | A-150 |
LOW VOLTAGE BACKBOX, 4-SQ WITH SINGLE-GANG MUD RING AND 3/4" EMT STUB, CCTV CAMERA (CEILING) The drawings say “by gc”. | GC | not stated | RRE installs / connects only | A-150 |
LUTRON PICO WIRELESS DIMMER/SWITCH ('VS' symbol) - install on wall box/mount, vendor furnished The drawings say “vendor furnished”. | Vendor | not stated | RRE installs / connects only | E-300 |
LUTRON VIVE WIRELESS OCCUPANCY SENSOR, CEILING (OS symbol) - install only, vendor furnished The drawings say “vendor furnished”. | Vendor | not stated | RRE installs / connects only | E-300 |
LUTRON VIVE POWPAK RELAY MODULE RMJS-16R-DV-B, INSTALL ONLY (vendor-furnished), ON 4-SQ J-BOX The drawings say “vendor-furnished”. | Vendor | not stated | RRE installs / connects only | E-900 |
LUTRON VIVE HUB HJS-1, INSTALL ONLY (vendor-furnished), ON 4X4 J-BOX W/ 120V FEED The drawings say “vendor-furnished”. | Vendor | not stated | RRE installs / connects only | E-900 |
TENANT ELECTRIC SUBMETER, QUADLOGIC RSM5 OR S20 (landlord-specified), for main tenant electrical system The drawings say “furnished by landlord or tenant”. | Landlord | not stated | RRE installs / connects only | 000-Copy-of-2498-A-set-2025-0530-Revision-1-p1 |
RECEPTACLE 20A 125V DUPLEX, DEDICATED, FOR REFRIGERATED DRINKING FOUNTAIN FX-3 (ELKAY EZTL8C + LKAPREZL), IN 4" SQ BOX The drawings say “installed by gc”. | GC | GC | RRE installs / connects only | A-120 |
LOW VOLTAGE BACKBOX, SINGLE-GANG WITH 3/4" EMT STUB, SUBWOOFER (SW) CONNECTION POINT The drawings say “by gc”. | GC | not stated | RRE installs / connects only | A-150 |
BACKBOX, 4" SQUARE x 2-1/8" DEEP WITH 1-GANG MUD RING, WITH 3/4" EMT STUB TO ACCESSIBLE CEILING, PULL STRING - ALARM KEYPAD AT DOOR 05 (SALES SIDE) The drawings say “by tenant”. | Tenant | not stated | RRE installs / connects only | A-500 |
TRACK, LINE-VOLTAGE 120V SINGLE-CIRCUIT, SURFACE/SUSPENDED (tracks 1-7) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E-300 |
LIGHT FIXTURE TYPE E06W (schedule E06w) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | Owner | not stated | Struck: not in this bid | A-130 |
LED DRIVER / TRANSFORMER 75W 24VDC CLASS 2, REMOTE MOUNT (XLG-75 series) FOR S02 SCONCES, WITH J-BOX Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | A-130 |
TRANSFORMER / REMOTE LED DRIVER (spec 26-50.23), CONCEALED ABOVE DISPLAY CEILING IN TAPED-IN ACCESS PANEL - INSTALL & CONNECT, WITH 4" SQ J-BOX AND FLEX WHIP Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | GC | not stated | Struck: not in this bid | A-210 |
EXISTING DUCT SMOKE DETECTOR RECONNECTION TO NEW AHU (UNIT SHUTDOWN INTERLOCK), EXISTING DETECTOR TO REMAIN Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | M-300 |
LED REMOTE TRANSFORMER / DRIVER, CLASS 2, CONCEALED IN MILLWORK CABINET (spec 26-50.23) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | A-410 |
JUNCTION BOX 4" SQ, 120V FEED TO REMOTE LED TRANSFORMER IN MILLWORK Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | A-410 |
| 330 | Metal-Clad Cable: Type MC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 332 | Mineral-Insulated, Metal-Sheathed Cable: Type MI | not in play | Nothing on this takeoff puts it in play. |
| 334 | Nonmetallic-Sheathed Cable: Types NM and NMC | not in play | Nothing on this takeoff puts it in play. |
| 336 | Power and Control Tray Cable: Type TC | not in play | Nothing on this takeoff puts it in play. |
| 337 | Type P Cable | not in play | Nothing on this takeoff puts it in play. |
| 338 | Service-Entrance Cable: Types SE and USE | not in play | Nothing on this takeoff puts it in play. |
| 340 | Underground Feeder and Branch-Circuit Cable: Type UF | not in play | Nothing on this takeoff puts it in play. |
| 342 | Intermediate Metal Conduit: Type IMC | not in play | Nothing on this takeoff puts it in play. |
| 344 | Rigid Metal Conduit: Type RMC | not in play | Nothing on this takeoff puts it in play. |
| 348 | Flexible Metal Conduit: Type FMC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 350 | Liquidtight Flexible Metal Conduit: Type LFMC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 352 | Rigid Polyvinyl Chloride Conduit: Type PVC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 353 | High Density Polyethylene Conduit: Type HDPE Conduit | not in play | Nothing on this takeoff puts it in play. |
| 354 | Nonmetallic Underground Conduit with Conductors: Type NUCC | not in play | Nothing on this takeoff puts it in play. |
| 355 | Reinforced Thermosetting Resin Conduit: Type RTRC | not in play | Nothing on this takeoff puts it in play. |
| 356 | Liquidtight Flexible Nonmetallic Conduit: Type LFNC | not in play | Nothing on this takeoff puts it in play. |
| 358 | Electrical Metallic Tubing: Type EMT | checked | In play; none of its checked sections applies to these lines. |
| 360 | Flexible Metallic Tubing: Type FMT | not in play | Nothing on this takeoff puts it in play. |
| 362 | Electrical Nonmetallic Tubing: Type ENT | not in play | Nothing on this takeoff puts it in play. |
| 366 | Auxiliary Gutters | not in play | Nothing on this takeoff puts it in play. |
| 368 | Busways | not in play | Nothing on this takeoff puts it in play. |
| 369 | Insulated Bus Pipe (IBP)/Tubular Covered Conductors (TCC) Systems | not in play | Nothing on this takeoff puts it in play. |
| 370 | Cablebus | not in play | Nothing on this takeoff puts it in play. |
| 371 | Flexible Bus Systems | not in play | Nothing on this takeoff puts it in play. |
| 372 | Cellular Concrete Floor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 374 | Cellular Metal Floor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 376 | Metal Wireways | not in play | Nothing on this takeoff puts it in play. |
| 378 | Nonmetallic Wireways | not in play | Nothing on this takeoff puts it in play. |
| 380 | Multioutlet Assembly | not in play | Nothing on this takeoff puts it in play. |
| 382 | Nonmetallic Extensions | not in play | Nothing on this takeoff puts it in play. |
| 384 | Strut-Type Channel Raceway | not in play | Nothing on this takeoff puts it in play. |
| 386 | Surface Metal Raceways | not in play | Nothing on this takeoff puts it in play. |
| 388 | Surface Nonmetallic Raceways | not in play | Nothing on this takeoff puts it in play. |
| 390 | Underfloor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 392 | Cable Trays | not in play | Nothing on this takeoff puts it in play. |
| 393 | Low-Voltage Suspended Ceiling Power Distribution Systems | not in play | Nothing on this takeoff puts it in play. |
| 394 | Concealed Knob-and-Tube Wiring | not in play | Nothing on this takeoff puts it in play. |
| 396 | Messenger-Supported Wiring | not in play | Nothing on this takeoff puts it in play. |
| 398 | Open Wiring on Insulators | not in play | Nothing on this takeoff puts it in play. |
| 399 | Outdoor, Overhead Conductors over 1000 Volts | not in play | Nothing on this takeoff puts it in play. |
| 424 |
| Fixed Electric Space-Heating Equipment |
| not in play |
| Nothing on this takeoff puts it in play. |
| 425 | Fixed Resistance and Electrode Industrial Process Heating Equipment | not in play | Nothing on this takeoff puts it in play. |
| 426 | Fixed Outdoor Electric Deicing and Snow-Melting Equipment | not in play | Nothing on this takeoff puts it in play. |
| 427 | Fixed Electric Heating Equipment for Pipelines and Vessels | not in play | Nothing on this takeoff puts it in play. |
| 430 | Motors, Motor Circuits, and Controllers | checked | In play; none of its checked sections applies to these lines. |
| 440 | Air-Conditioning and Refrigerating Equipment | checked | 1 section checked against the takeoff, all shown. |
| 445 | Generators | not in play | Nothing on this takeoff puts it in play. |
| 450 | Transformers and Transformer Vaults (Including Secondary Ties) | not in play | Nothing on this takeoff puts it in play. |
| 455 | Phase Converters | not in play | Nothing on this takeoff puts it in play. |
| 460 | Capacitors | not in play | Nothing on this takeoff puts it in play. |
| 470 | Resistors and Reactors | not in play | Nothing on this takeoff puts it in play. |
| 480 | Stationary Standby Batteries | not in play | Nothing on this takeoff puts it in play. |
| 490 | Equipment Over 1000 Volts, Nominal | not in play | Nothing on this takeoff puts it in play. |
| Nothing on this takeoff puts it in play. |
| 514 | Motor Fuel Dispensing Facilities | not in play | Nothing on this takeoff puts it in play. |
| 515 | Bulk Storage Plants | not in play | Nothing on this takeoff puts it in play. |
| 516 | Spray Application, Dipping, Coating, and Printing Processes | not in play | Nothing on this takeoff puts it in play. |
| 517 | Health Care Facilities | not in play | Nothing on this takeoff puts it in play. |
| 518 | Assembly Occupancies | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 520 | Theaters, Audience Areas of Motion Picture and Television Studios, Performance Areas, and Similar Locations | not in play | Nothing on this takeoff puts it in play. |
| 522 | Control Systems for Permanent Amusement Attractions | not in play | Nothing on this takeoff puts it in play. |
| 525 | Carnivals, Circuses, Fairs, and Similar Events | not in play | Nothing on this takeoff puts it in play. |
| 530 | Motion Picture and Television Studios and Similar Locations | not in play | Nothing on this takeoff puts it in play. |
| 540 | Motion Picture Projection Rooms | not in play | Nothing on this takeoff puts it in play. |
| 545 | Manufactured Buildings and Relocatable Structures | not in play | Nothing on this takeoff puts it in play. |
| 547 | Agricultural Buildings | not in play | Nothing on this takeoff puts it in play. |
| 550 | Mobile Homes, Manufactured Homes, and Mobile Home Parks | not in play | Nothing on this takeoff puts it in play. |
| 551 | Recreational Vehicles and Recreational Vehicle Parks | not in play | Nothing on this takeoff puts it in play. |
| 552 | Park Trailers | not in play | Nothing on this takeoff puts it in play. |
| 555 | Marinas, Boatyards, Floating Buildings, and Commercial and Noncommercial Docking Facilities | not in play | Nothing on this takeoff puts it in play. |
| 590 | Temporary Installations | not in play | Nothing on this takeoff puts it in play. |
| Nothing on this takeoff puts it in play. |
| 646 | Modular Data Centers | not in play | Nothing on this takeoff puts it in play. |
| 647 | Sensitive Electronic Equipment | not in play | Nothing on this takeoff puts it in play. |
| 650 | Pipe Organs | not in play | Nothing on this takeoff puts it in play. |
| 660 | X-Ray Equipment | not in play | Nothing on this takeoff puts it in play. |
| 665 | Induction and Dielectric Heating Equipment | not in play | Nothing on this takeoff puts it in play. |
| 668 | Electrolytic Cells | not in play | Nothing on this takeoff puts it in play. |
| 669 | Electroplating | not in play | Nothing on this takeoff puts it in play. |
| 670 | Industrial Machinery | not in play | Nothing on this takeoff puts it in play. |
| 675 | Electrically Driven or Controlled Irrigation Machines | not in play | Nothing on this takeoff puts it in play. |
| 680 | Swimming Pools, Fountains, and Similar Installations | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 682 | Natural and Artificially Made Bodies of Water | not in play | Nothing on this takeoff puts it in play. |
| 685 | Integrated Electrical Systems | not in play | Nothing on this takeoff puts it in play. |
| 690 | Solar Photovoltaic (PV) Systems | not in play | Nothing on this takeoff puts it in play. |
| 691 | Large-Scale Photovoltaic (PV) Electric Supply Stations | not in play | Nothing on this takeoff puts it in play. |
| 692 | Fuel Cell Systems | not in play | Nothing on this takeoff puts it in play. |
| 694 | Wind Electric Systems | not in play | Nothing on this takeoff puts it in play. |
| 695 | Fire Pumps | not in play | Nothing on this takeoff puts it in play. |
| not read yet |
| In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 727 | Instrumentation Tray Cable: Type ITC | not in play | Nothing on this takeoff puts it in play. |
| 728 | Fire-Resistive Cable Systems | not in play | Nothing on this takeoff puts it in play. |
| 750 | Energy Management Systems | not in play | Nothing on this takeoff puts it in play. |
| 760 | Fire Alarm Systems | checked | In play; none of its checked sections applies to these lines. |
| 770 | Optical Fiber Cables | not in play | Nothing on this takeoff puts it in play. |