Derived from what the read produced, so none of it can drift from the data behind it. A blocker stops a price being presented as complete; it never stops you looking. These definitions are this build’s own — no RRE document specifies them yet.
| Check | Status | What the check found |
|---|---|---|
| Sheet scale | pass | All 4 plan sheet(s) carry a scale, so measurement is available. The other 11 read sheet(s) are specifications, schedules and details — nothing is measured on them, so a scale on one is not needed and a scale missing from one is not a gap. |
| Sheets read for scope | warning | 38 sheet(s) were indexed but not read for scope: 000-Copy-of-Drawings-p1, 000-Copy-of-Drawings-p2, 000-Copy-of-Drawings-p3, 000-Copy-of-Drawings-p4, 000-Copy-of-Drawings-p5, SD0, C1, C2, C3, C4, A1.5, A3.1, A3.2, A5.1, A5.3, 000-Copy-of-Drawings-p24, 000-Copy-of-Drawings-p25, 000-Copy-of-Drawings-p26, 000-Copy-of-Drawings-p27, 000-Copy-of-Drawings-p29, 000-Copy-of-Drawings-p30, SN2, SN3, S1, S2, DS2, DS4, M0.1, M0.3, M0.4, M0.5, P0.1, P0.2, P2.0, P2.1, P3.1, P4.1, P4.2. Looked at by the takeoff and not read: no electrical work on it. Read them, or state the omission on the proposal — the basis of the offer already prints it. |
| Symbol source | pass | A symbol list was found on the drawings: E1.0 — ELECTRICAL GENERAL NOTES, LEGEND & SYMBOLS. The project legend is authoritative for this set and outranks everything else — NECA 100-2006 itself allows a drawing to use non-standard symbols provided the legend explains them. NECA 100-2006 stays underneath it for anything the legend leaves silent, and no conventions file exists for MATRISCOPE ENGINEERING. |
| Symbols named | pass | All 77 marks belong to a named group. |
| Every line prices | blocker | 15 line(s) point at no assembly, so nothing prices them: CIRCUIT BREAKER 200A 3P IN SWITCHBOARD MSB (FEEDER TO PANEL H), CIRCUIT BREAKER 20A 1P BOLT-ON (PANEL H), CIRCUIT BREAKER 30A 3P BOLT-ON (PANEL H, AC-1), CIRCUIT BREAKER 50A 3P BOLT-ON (PANEL H, AC-2), CIRCUIT BREAKER 40A 2P BOLT-ON (PANEL H, EVSE), PLYWOOD BACKBOARD FIRE-TREATED 3/4" (TEL/DATA, FULL WALL LENGTH TO CEILING)…. They are counted and reported, and they stay outside the total. Attach a build-up from the catalog, or strike the line. |
| Plan and schedule agree | pass | No line has a plan/schedule disagreement. |
| Lines accepted by a person | blocker | Nothing has been accepted. All 87 line(s) are still suggestions, and machine output is a suggestion until a named person accepts it. Accept on the Takeoff screen — 72 line(s) are ready. |
| Engineer conventions known | pass | MATRISCOPE ENGINEERING has a conventions file. |
| Unsure flags resolved | pass | The model raised no open flags. |
| Cover sheet read | pass | A cover sheet was found and read; its notes parameterise every later pass. |
What the symbol names rest on. The set’s own legend (E1.0), which is authoritative for this project.
| Line | Count | Sheet |
|---|---|---|
CONDUIT SUPPORT SYSTEM - ROD HANGERS / UNISTRUT TRAPEZE WITH CLAMPS AND ALL-THREAD (SPEC 16050 2.05), PER BOX POINT Hanger layer per interior box point, ~0.30-0.35 hr each plus Unistrut/Caddy/clamps | 33 ea | E7.0 |
3/4" RGS CONDUIT WITH PULL WIRE, SIGNAGE STUB 3/4"C stub from signage WP J-box into ceiling space (SN 12, SN 9 RGS exterior) | 10 ft | E3.0 |
PLYWOOD BACKBOARD FIRE-TREATED 3/4" (TEL/DATA, FULL WALL LENGTH TO CEILING) Tel/data backboard, H-9 | 1 ea | E3.0 |
DUPLEX RECEPTACLE 20A 125V TAMPER-RESISTANT, WALL, DEDICATED (TEL/DATA BACKBOARD) Receptacle H-9 at tel/data backboard | 1 ea | E3.0 |
SWITCHBOARD AND BREAKER OPERATIONAL CHECK AND TORQUE TEST (MSB 800A AND PANEL H), BY INDEPENDENT TESTING LABORATORY Spec 16040 3.02 transformer and breaker operational check: clean, torque connections, verify operation, relay test | 1 ea | E7.0 |
EQUIPMENT RELOCATION - CAR WASH VACUUM / AIR-WATER UNIT, DISCONNECT, EXTEND CIRCUIT & RECONNECT EXISTING POWER (EXTERIOR, WP) Relocated vacuum equipment at north property fence, NE corner of site (SD1 callout, dtl 10/SD3) | 1 ea | SD1 |
JUNCTION BOX, 4" SQUARE, WEATHERPROOF (NEMA 3R) WITH STUB-UP IN RAISED CONCRETE PAD, FOR RELOCATED VACUUM EQUIPMENT |
Edition: 2025 California Electrical Code, because in force for permits from 2026-01-01, as of the bid date 2026-10-02. City and county amendments are the AHJ’s: check them on any job inside a city that amends the code. “To check” means the code requires it and the drawings do not show it: send an RFI, or make the call. Nothing here is added to the bid on its own.
| Section | Status | What the code requires | What the takeoff shows | RRE’s practice |
|---|---|---|---|---|
NEC 2023 110.24 Available fault current marked at the service | to check | Service equipment in other than dwelling units is field-marked with the maximum available fault current and the date it was calculated. | In play for SWITCHBOARD AND BREAKER OPERATIONAL CHECK AND TORQUE TEST (MSB 800A AND PANEL H), BY INDEPENDENT TESTING LABORATORY. Nothing on the takeoff shows it. | — |
NEC 2023 250.94 Intersystem bonding termination | to check | An intersystem bonding termination at the service equipment or metering, for the communications, CATV and broadband systems to bond to. | In play for SWITCHBOARD AND BREAKER OPERATIONAL CHECK AND TORQUE TEST (MSB 800A AND PANEL H), BY INDEPENDENT TESTING LABORATORY. Nothing on the takeoff shows it. | — |
NEC 2023 625.40, 625.54 EV charging: individual circuit and GFCI | to check | Each outlet for EV charging on an individual branch circuit, receptacles for EV charging GFCI protected, and EVSE over 60 A or 150 V to ground with a lockable disconnect. | 5 of 9 in play are not shown with it: WIRE #6 AWG CU THHN/THWN (EV-1, EV-2 FEEDERS); WIRE #10 AWG CU GROUND (EV FEEDERS); WIRE #8 AWG CU THHN/THWN (EV-3 FEEDER); and 2 more. | — |
The RRE item carries no price for the part named, so the estimate has the install labor and rough-in only, and the vendor or sub prices the rest. Send the lighting and gear lists from Material list & vendor quotes.
| Line | Needs a price for | Count | Sheet |
|---|---|---|---|
LIGHT FIXTURE TYPE C - EXTERIOR WALL SCONCE, LSI XPWS3-WT-LED-48-350-UE-PCI120, 55W exterior wall, west by panel H and south wall, circuit H-5c, photocontrol per SN 8 | LED WALL SCONCE - MED | 2 ea | E4.0 |
LIGHT FIXTURE TYPE D - WALL MOUNTED LIGHT FIXTURE, LSI SW-2-20L-830-UNV, 16W fire riser room / rear door, circuit H-1e | LED WALL SCONCE - MED | 1 ea | E4.0 |
| Line | Needs a price for | Count | Sheet |
|---|---|---|---|
CIRCUIT BREAKER 200A 3P IN SWITCHBOARD MSB (FEEDER TO PANEL H) Distribution breaker for panel H | the gear itself (no RRE item picked yet) | 1 ea | E5.0 |
PANELBOARD H 200A MCB 3P 225A BUS 120/208V 3PH 4W 42 CKT 22KAIC BOLT-ON SURFACE MOUNTED (N) panel H in tenant space beside tel/data backboard | 200/42 120/208V PNL 3PH | 1 ea | E5.0 |
SWITCHBOARD AND BREAKER OPERATIONAL CHECK AND TORQUE TEST (MSB 800A AND PANEL H), BY INDEPENDENT TESTING LABORATORY |
18 lines the reader wrote at zero are not listed: they add nothing to the bid.
Nothing in this tab.
| 1 ea |
| SD3 |
EQUIPMENT CONNECTION, RTU 208V 3PH 46A - 1" LIQUIDTIGHT FLEX (24" MIN) DISCONNECT TO UNIT WITH FITTINGS Final connection AC-1, AC-2 (SN 5, E1.0 GN 6, GN 9) | 0 ea | E3.0 |
PANELBOARD 'H' 200A MCB 3P, 225A BUS, 120/208V 3PH 4W, 22 KAIC, 42 CKT, BOLT-ON, SURFACE MOUNT (with breakers: (8) 20A-1P, (1) 30A-3P, (1) 50A-3P, (3) 40A-2P per schedule) (N) Panel H in tenant space by tel/data backboard | 0 ea | E5.0 |
NEC 2023 110.16 Arc-flash warning label on gear |
| shown |
| Switchboards, switchgear, panelboards, meter socket enclosures and motor control centers likely to be worked on energized carry a field- or factory-applied arc-flash hazard warning. |
| In play for PANELBOARD H 200A MCB 3P 225A BUS 120/208V 3PH 4W 42 CKT 22KAIC BOLT-ON SURFACE MOUNTED; SWITCHBOARD AND BREAKER OPERATIONAL CHECK AND TORQUE TEST (MSB 800A AND PANEL H), BY INDEPENDENT TESTING LABORATORY. Shown: ARC-FLASH HAZARD WARNING LABEL (CEC 110.16); PANEL DIRECTORY TYPEWRITTEN AND LAMINATED NAMEPLATE. |
| RRE carries phenolic nameplates and labels as their own item where the set calls for them. |
NEC 2023 210.8(B), 406.9(B) GFCI, weather-resistant, in-use cover outdoors and on the roof | shown | Rooftop and outdoor receptacles GFCI protected, weather-resistant type, with an extra-duty in-use cover in wet locations. | In play for 3/4" RGS CONDUIT ON ROOF SLEEPERS (H-11 ROOF GFCI RECEPTACLE CIRCUIT); GFCI DUPLEX RECEPTACLE 20A 125V, WEATHERPROOF WITH IN-USE COVER, ROOF (HVAC SERVICE); WEATHERPROOF CAST BOX (FS/FD) FOR ROOF GFCI RECEPTACLE. Shown: 3/4" RGS CONDUIT ON ROOF SLEEPERS (H-11 ROOF GFCI RECEPTACLE CIRCUIT); GFCI DUPLEX RECEPTACLE 20A 125V, WEATHERPROOF WITH IN-USE COVER, ROOF (HVAC SERVICE); WEATHERPROOF CAST BOX (FS/FD) FOR ROOF GFCI RECEPTACLE. | RRE carries roof and patio receptacles as WR GFCI with an in-use cover where they are drawn (The Melt: 3). |
NEC 2023 210.62 Receptacles in show windows | shown | At least one 125-volt receptacle within 18 in. of the top of a show window for each 12 linear ft of show window. | In play for DUPLEX RECEPTACLE 20A 125V TAMPER-RESISTANT, CEILING-MOUNTED (SHOW WINDOW). Shown: DUPLEX RECEPTACLE 20A 125V TAMPER-RESISTANT, CEILING-MOUNTED (SHOW WINDOW). | — |
NEC 2023 210.63(A) Service receptacle at HVAC equipment | shown | A 125-volt, 15- or 20-ampere receptacle on the same level and within 25 ft of heating, air-conditioning and refrigeration equipment, not on the load side of the equipment disconnect. | In play for #4 THHN/THWN-2 CU WIRE (RTU FEEDERS); #10 THHN/THWN-2 CU WIRE, GREEN (RTU FEEDER GROUNDS); 1" RGS CONDUIT ON ROOF SLEEPERS (RTU FEEDERS AC-1, AC-2); and 2 more. Shown: 3/4" RGS CONDUIT ON ROOF SLEEPERS (H-11 ROOF GFCI RECEPTACLE CIRCUIT); GFCI DUPLEX RECEPTACLE 20A 125V, WEATHERPROOF WITH IN-USE COVER, ROOF (HVAC SERVICE); WEATHERPROOF CAST BOX (FS/FD) FOR ROOF GFCI RECEPTACLE. | RRE carries the roof receptacle where the set draws one (reading check 11). |
NEC 2023 210.63(B) Receptacle at indoor service equipment | shown | A 125-volt, 15- or 20-ampere receptacle within 50 ft of indoor electrical service equipment (other than one- and two-family dwellings). | In play for SWITCHBOARD AND BREAKER OPERATIONAL CHECK AND TORQUE TEST (MSB 800A AND PANEL H), BY INDEPENDENT TESTING LABORATORY. Shown: GFCI DUPLEX RECEPTACLE 20A 125V, WEATHERPROOF WITH IN-USE COVER, ROOF (HVAC SERVICE). | — |
NEC 2023 250.50, 250.24, 250.104 Grounding electrode system at a new service | shown | A new service bonds every grounding electrode present (building steel, concrete-encased electrode, water pipe, rods) into one system, with a grounding electrode conductor to the service, and bonds the metal water and gas piping. | In play for SWITCHBOARD AND BREAKER OPERATIONAL CHECK AND TORQUE TEST (MSB 800A AND PANEL H), BY INDEPENDENT TESTING LABORATORY. Shown: GROUND ROD 3/4" x 10' COPPER-CLAD WITH ACORN CLAMP; GROUND CLAMP - #3/0 GEC TO METALLIC COLD WATER PIPE; GROUND CONNECTION - #3/0 GEC TO BUILDING STRUCTURAL STEEL (EXOTHERMIC); and 1 more. | — |
NEC 2023 300.11, 410.36(B) Support in suspended ceilings | shown | Raceways, cables and boxes above a suspended ceiling are supported independently of the ceiling grid, or by identified support wires; lay-in luminaires are fastened to the grid framing. | In play for LIGHT FIXTURE TYPE A - 1X4 SUSPENDED LED, DIMMABLE, LSI SW-4-60L-840-UNV-EM, 44W 120V. Shown: CONDUIT SUPPORT SYSTEM - ROD HANGERS / UNISTRUT TRAPEZE WITH CLAMPS AND ALL-THREAD (SPEC 16050 2.05), PER BOX POINT. | RRE carries the fixture support wire as its own item where the ceiling is a grid. |
NEC 2023 408.4(A) Circuit directory at every panel | shown | Every circuit and circuit modification legibly identified as to its clear, evident and specific purpose on a circuit directory at the panel. | In play for PANELBOARD H 200A MCB 3P 225A BUS 120/208V 3PH 4W 42 CKT 22KAIC BOLT-ON SURFACE MOUNTED; SWITCHBOARD AND BREAKER OPERATIONAL CHECK AND TORQUE TEST (MSB 800A AND PANEL H), BY INDEPENDENT TESTING LABORATORY. Shown: PANEL DIRECTORY TYPEWRITTEN AND LAMINATED NAMEPLATE. | RRE carries a panel directory update where circuits land in an existing panel. |
NEC 2023 440.14 Disconnect within sight of HVAC equipment | shown | A disconnecting means within sight from, and readily accessible from, air-conditioning and refrigerating equipment. It may be on or in the unit. | In play for #4 THHN/THWN-2 CU WIRE (RTU FEEDERS); #10 THHN/THWN-2 CU WIRE, GREEN (RTU FEEDER GROUNDS); 1" RGS CONDUIT ON ROOF SLEEPERS (RTU FEEDERS AC-1, AC-2); and 2 more. Shown: 1" RGS CONDUIT ON ROOF SLEEPERS (RTU FEEDERS AC-1, AC-2); DISCONNECT SWITCH 60A 3P 240V HEAVY DUTY FUSED NEMA 3R (AC-1, AC-2 ROOFTOP UNITS, FUSED AT MOCP 60A). | RRE priced this on 5 of 5 past jobs (100%). RRE carries a disconnect at every unit with a disconnect symbol or note, sized from its circuit. |
NEC 2023 600.5(A) Sign outlet at each tenant entrance | shown | At least one outlet at each entrance to each tenant space accessible to pedestrians, for a sign, on a 20-ampere branch circuit that supplies no other load. | Shown: 10/2 MC EQUIPMENT DROPS; 3/4" RGS CONDUIT WITH PULL WIRE, SIGNAGE STUB; WEATHERPROOF J-BOX, EXTERIOR WALL, SIGNAGE. | RRE prices "power to building signage" where the set shows it; the matrix row is left blank where it does not. |
NEC 2023 600.6 Disconnect within sight of a sign | shown | Each sign or outline lighting system, or its feeder, has an externally operable disconnect within sight of the sign, or one capable of being locked in the open position. | In play for 10/2 MC EQUIPMENT DROPS; 3/4" RGS CONDUIT WITH PULL WIRE, SIGNAGE STUB; WEATHERPROOF J-BOX, EXTERIOR WALL, SIGNAGE. Shown: 1" RGS CONDUIT ON ROOF SLEEPERS (RTU FEEDERS AC-1, AC-2); FUSE 60A CLASS RK5 DUAL ELEMENT CURRENT LIMITING (AC DISCONNECTS); FUSE 40A CLASS RK5 CURRENT LIMITING (EV DISCONNECTS); and 4 more. | RRE prices a WP switch at signage as a fused disconnect assembly (firm practice wp_switch_mapping). |
A takeoff cannot settle every article: load calculations and coordination are the engineer of record’s, and workmanship is the inspector’s. Each is listed so nothing is silently skipped. “Waiting on a code read” means the article is in play and this job’s drawing read has not been checked against the code yet: re-run the read, or check it on the drawings.
| 90 | Introduction | general | Scope and definitions: nothing to check on a job. |
| 100 | Definitions | general | Scope and definitions: nothing to check on a job. |
| 110 | Requirements for Electrical Installations | to check | 2 sections checked against the takeoff, 1 to check: 110.24. |
| 200 | Use and Identification of Grounded Conductors | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 210 | Branch Circuits | checked | 4 sections checked against the takeoff, all shown. |
| 215 | Feeders | checked | In play; none of its checked sections applies to these lines. |
| 220 | Branch-Circuit, Feeder, and Service Load Calculations | design | The engineer of record’s: sizing, calculation or coordination, not checked against a takeoff. |
| 225 | Outside Branch Circuits and Feeders | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 230 | Services | checked | In play; none of its checked sections applies to these lines. |
| 235 | Branch Circuits, Feeders, and Services Over 1000 Volts ac, 1500 Volts dc | not in play | Nothing on this takeoff puts it in play. |
| 240 | Overcurrent Protection | checked | In play; none of its checked sections applies to these lines. |
| 242 | Overvoltage Protection | not in play | Nothing on this takeoff puts it in play. |
| 245 | Overcurrent Protection for Systems Rated Over 1000 Volts ac, 1500 Volts dc | not in play | Nothing on this takeoff puts it in play. |
| 250 | Grounding and Bonding | to check | 2 sections checked against the takeoff, 1 to check: 250.94. |
| 300 | General Requirements for Wiring Methods and Materials | checked | 1 section checked against the takeoff, all shown. |
| 305 | General Requirements for Wiring Methods and Materials for Systems Rated Over 1000 Volts ac, 1500 Volts dc | not in play | Nothing on this takeoff puts it in play. |
| 310 | Conductors for General Wiring | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 312 | Cabinets, Cutout Boxes, and Meter Socket Enclosures | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 314 | Outlet, Device, Pull, and Junction Boxes; Conduit Bodies; Fittings; and Handhole Enclosures | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 315 | Medium Voltage Conductors, Cable, Cable Joints, and Cable Terminations | not in play | Nothing on this takeoff puts it in play. |
| 320 | Armored Cable: Type AC | not in play | Nothing on this takeoff puts it in play. |
| 322 | Flat Cable Assemblies: Type FC | not in play | Nothing on this takeoff puts it in play. |
| 324 | Flat Conductor Cable: Type FCC | not in play |
| 400 | Flexible Cords and Flexible Cables | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 402 | Fixture Wires | not in play | Nothing on this takeoff puts it in play. |
| 404 | Switches | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 406 | Receptacles, Cord Connectors, and Attachment Plugs (Caps) | checked | In play; none of its checked sections applies to these lines. |
| 408 | Switchboards, Switchgear, and Panelboards | checked | 1 section checked against the takeoff, all shown. |
| 409 | Industrial Control Panels | not in play | Nothing on this takeoff puts it in play. |
| 410 | Luminaires, Lampholders, and Lamps | checked | In play; none of its checked sections applies to these lines. |
| 411 | Low-Voltage Lighting | not in play | Nothing on this takeoff puts it in play. |
| 422 | Appliances | checked | In play; none of its checked sections applies to these lines. |
| 424 | Fixed Electric Space-Heating Equipment |
| 500 | Hazardous (Classified) Locations, Classes I, II, and III, Divisions 1 and 2 | not in play | Nothing on this takeoff puts it in play. |
| 501 | Class I Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 502 | Class II Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 503 | Class III Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 504 | Intrinsically Safe Systems | not in play | Nothing on this takeoff puts it in play. |
| 505 | Zone 0, 1, and 2 Locations | not in play | Nothing on this takeoff puts it in play. |
| 506 | Zone 20, 21, and 22 Locations for Combustible Dusts or Ignitible Fibers/Flyings | not in play | Nothing on this takeoff puts it in play. |
| 510 | Hazardous (Classified) Locations — Specific | not in play | Nothing on this takeoff puts it in play. |
| 511 | Commercial Garages, Repair and Storage | not in play | Nothing on this takeoff puts it in play. |
| 513 | Aircraft Hangars | not in play |
| 600 | Electric Signs and Outline Lighting | checked | 2 sections checked against the takeoff, all shown. |
| 604 | Manufactured Wiring Systems | not in play | Nothing on this takeoff puts it in play. |
| 605 | Office Furnishings | not in play | Nothing on this takeoff puts it in play. |
| 610 | Cranes and Hoists | not in play | Nothing on this takeoff puts it in play. |
| 620 | Elevators, Dumbwaiters, Escalators, Moving Walks, Platform Lifts, and Stairway Chairlifts | not in play | Nothing on this takeoff puts it in play. |
| 625 | Electric Vehicle Power Transfer System | to check | 1 section checked against the takeoff, 1 to check: 625.40, 625.54. |
| 626 | Electrified Truck Parking Spaces | not in play | Nothing on this takeoff puts it in play. |
| 630 | Electric Welders | not in play | Nothing on this takeoff puts it in play. |
| 640 | Audio Signal Processing, Amplification, and Reproduction Equipment | not in play | Nothing on this takeoff puts it in play. |
| 645 | Information Technology Equipment | not in play |
| 700 | Emergency Systems | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 701 | Legally Required Standby Systems | not in play | Nothing on this takeoff puts it in play. |
| 702 | Optional Standby Systems | not in play | Nothing on this takeoff puts it in play. |
| 705 | Interconnected Electric Power Production Sources | not in play | Nothing on this takeoff puts it in play. |
| 706 | Energy Storage Systems | not in play | Nothing on this takeoff puts it in play. |
| 708 | Critical Operations Power Systems (COPS) | not in play | Nothing on this takeoff puts it in play. |
| 710 | Stand-Alone Systems | not in play | Nothing on this takeoff puts it in play. |
| 712 | Direct Current Microgrids | not in play | Nothing on this takeoff puts it in play. |
| 722 | Cables for Power-Limited Circuits and Fault-Managed Power Circuits | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 724 | Class 1 Power-Limited Circuits and Class 1 Power-Limited Remote-Control and Signaling Circuits |
| 800 | General Requirements for Communications Systems | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 805 | Communications Circuits | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 810 | Radio and Television Antenna Equipment | not in play | Nothing on this takeoff puts it in play. |
| 820 | Community Antenna Television and Radio Distribution Systems | not in play | Nothing on this takeoff puts it in play. |
| 830 | Network-Powered Broadband Communications Systems | not in play | Nothing on this takeoff puts it in play. |
| 840 | Premises-Powered Broadband Communications Systems | not in play | Nothing on this takeoff puts it in play. |
| Ch. 9 | Tables: conduit fill, conductor properties, power-limited sources | checked | In play; none of its checked sections applies to these lines. |
| the gear itself (no RRE item picked yet) |
| 1 ea |
| E7.0 |
Read off the schedules and notes. RRE buys none of the material named here. Check each against the responsibility matrix on the proposal: these are what it should say is by others.
| Line | Furnished by | Installed by | RRE’s part | Sheet |
|---|---|---|---|---|
EQUIPMENT CONNECTION EVSE 208V 1PH 30A (CHARGEPOINT CT4011-GW1) The drawings say “owner/vendor furnished”. | Owner | not stated | RRE installs / connects only | E1.1 |
WEATHERPROOF J-BOX, EXTERIOR WALL, SIGNAGE RRE carries the line; the read says “sign itself by others”. | Others | not stated | RRE carries it; a part is by others | E3.0 |
EV CHARGER CONNECTION - CHARGEPOINT CT4011-GW1 EVSE 208V 1PH 30A (OFCI, EC INSTALL & CONNECT) The drawings say “ofci”. | Owner | EC | RRE installs / connects only | E1.1 |
CONDUIT 1" (EV FEEDERS, UNDERGROUND PVC SCH 40 WITH RGS ELBOWS/RISERS) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E5.0 |
#3/0 AWG BARE CU GROUNDING ELECTRODE CONDUCTOR (GEC) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E5.0 |
FEEDER CONDUIT 2" (MSB TO PANEL H; UNDERGROUND PVC SCH 40 WITH RGS ELBOWS PER E1.1 SN 1) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E5.0 |
5" PVC SCH 40 CONDUIT UNDERGROUND - PG&E SERVICE SECONDARY Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E1.1 |
1" RGS PVC-COATED ELBOW / RISER Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E1.1 |
5" RGS PVC-COATED ELBOW Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E1.1 |
CONCRETE WEDGE ANCHOR 3/8" DIA. SIMPSON STRONG-BOLT 2, 2-1/2" NOMINAL EMBED, SWITCHBOARD TO HOUSEKEEPING PAD Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | DS1 |
2" RGS PVC-COATED ELBOW / RISER Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E5.0 |
JUNCTION BOX WEATHERPROOF AT EV CHARGER (HARD-WIRED EQUIPMENT CONNECTION) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E1.1 |
LIQUIDTIGHT FLEXIBLE METAL CONDUIT WHIP 1" MIN 24" WITH CONNECTORS (AC UNIT CONNECTION) Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E3.0 |
MAIN SWITCHBOARD MSB 800A 208Y/120V 3PH 4W NEMA 3R 65KAIC WITH 800A 3P 100% RATED MAIN BREAKER, UTILITY METERING SECTION Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E5.0 |
MAIN SWITCHBOARD 800A 208Y/120V 3PH 4W NEMA 3R 65KAIC, 800A 3P 100% MAIN, UTILITY METERING Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E1.1 |
FUSE 40A 250V CURRENT-LIMITING CLASS RK1/J Struck by kelchlin: Not in this bid: answered on the drawing instead of a RRE Components item. | — | not stated | Struck: not in this bid | E1.1 |
| Nothing on this takeoff puts it in play. |
| 326 | Integrated Gas Spacer Cable: Type IGS | not in play | Nothing on this takeoff puts it in play. |
| 330 | Metal-Clad Cable: Type MC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 332 | Mineral-Insulated, Metal-Sheathed Cable: Type MI | not in play | Nothing on this takeoff puts it in play. |
| 334 | Nonmetallic-Sheathed Cable: Types NM and NMC | not in play | Nothing on this takeoff puts it in play. |
| 335 | Instrumentation Tray Cable: Type ITC | not in play | Nothing on this takeoff puts it in play. |
| 336 | Power and Control Tray Cable: Type TC | not in play | Nothing on this takeoff puts it in play. |
| 337 | Type P Cable | not in play | Nothing on this takeoff puts it in play. |
| 338 | Service-Entrance Cable: Types SE and USE | not in play | Nothing on this takeoff puts it in play. |
| 340 | Underground Feeder and Branch-Circuit Cable: Type UF | not in play | Nothing on this takeoff puts it in play. |
| 342 | Intermediate Metal Conduit: Type IMC | not in play | Nothing on this takeoff puts it in play. |
| 344 | Rigid Metal Conduit: Type RMC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 348 | Flexible Metal Conduit: Type FMC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 350 | Liquidtight Flexible Metal Conduit: Type LFMC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 352 | Rigid Polyvinyl Chloride Conduit: Type PVC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 353 | High Density Polyethylene Conduit: Type HDPE Conduit | not in play | Nothing on this takeoff puts it in play. |
| 354 | Nonmetallic Underground Conduit with Conductors: Type NUCC | not in play | Nothing on this takeoff puts it in play. |
| 355 | Reinforced Thermosetting Resin Conduit: Type RTRC | not in play | Nothing on this takeoff puts it in play. |
| 356 | Liquidtight Flexible Nonmetallic Conduit: Type LFNC | not in play | Nothing on this takeoff puts it in play. |
| 358 | Electrical Metallic Tubing: Type EMT | checked | In play; none of its checked sections applies to these lines. |
| 360 | Flexible Metallic Tubing: Type FMT | not in play | Nothing on this takeoff puts it in play. |
| 362 | Electrical Nonmetallic Tubing: Type ENT | not in play | Nothing on this takeoff puts it in play. |
| 366 | Auxiliary Gutters | not in play | Nothing on this takeoff puts it in play. |
| 368 | Busways | not in play | Nothing on this takeoff puts it in play. |
| 369 | Insulated Bus Pipe (IBP)/Tubular Covered Conductors (TCC) Systems | not in play | Nothing on this takeoff puts it in play. |
| 370 | Cablebus | not in play | Nothing on this takeoff puts it in play. |
| 371 | Flexible Bus Systems | not in play | Nothing on this takeoff puts it in play. |
| 372 | Cellular Concrete Floor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 374 | Cellular Metal Floor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 376 | Metal Wireways | not in play | Nothing on this takeoff puts it in play. |
| 378 | Nonmetallic Wireways | not in play | Nothing on this takeoff puts it in play. |
| 380 | Multioutlet Assembly | not in play | Nothing on this takeoff puts it in play. |
| 382 | Nonmetallic Extensions | not in play | Nothing on this takeoff puts it in play. |
| 384 | Strut-Type Channel Raceway | not in play | Nothing on this takeoff puts it in play. |
| 386 | Surface Metal Raceways | not in play | Nothing on this takeoff puts it in play. |
| 388 | Surface Nonmetallic Raceways | not in play | Nothing on this takeoff puts it in play. |
| 390 | Underfloor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 392 | Cable Trays | not in play | Nothing on this takeoff puts it in play. |
| 393 | Low-Voltage Suspended Ceiling Power Distribution Systems | not in play | Nothing on this takeoff puts it in play. |
| 394 | Concealed Knob-and-Tube Wiring | not in play | Nothing on this takeoff puts it in play. |
| 395 | Outdoor Overhead Conductors over 1000 Volts | not in play | Nothing on this takeoff puts it in play. |
| 396 | Messenger-Supported Wiring | not in play | Nothing on this takeoff puts it in play. |
| 398 | Open Wiring on Insulators | not in play | Nothing on this takeoff puts it in play. |
| not in play |
| Nothing on this takeoff puts it in play. |
| 425 | Fixed Resistance and Electrode Industrial Process Heating Equipment | not in play | Nothing on this takeoff puts it in play. |
| 426 | Fixed Outdoor Electric Deicing and Snow-Melting Equipment | not in play | Nothing on this takeoff puts it in play. |
| 427 | Fixed Electric Heating Equipment for Pipelines and Vessels | not in play | Nothing on this takeoff puts it in play. |
| 430 | Motors, Motor Circuits, and Controllers | not in play | Nothing on this takeoff puts it in play. |
| 440 | Air-Conditioning and Refrigerating Equipment | checked | 1 section checked against the takeoff, all shown. |
| 445 | Generators | not in play | Nothing on this takeoff puts it in play. |
| 450 | Transformers and Transformer Vaults (Including Secondary Ties) | checked | In play; none of its checked sections applies to these lines. |
| 455 | Phase Converters | not in play | Nothing on this takeoff puts it in play. |
| 460 | Capacitors | not in play | Nothing on this takeoff puts it in play. |
| 470 | Resistors and Reactors | not in play | Nothing on this takeoff puts it in play. |
| 480 | Stationary Standby Batteries | not in play | Nothing on this takeoff puts it in play. |
| 490 | Equipment Over 1000 Volts, Nominal | not in play | Nothing on this takeoff puts it in play. |
| Nothing on this takeoff puts it in play. |
| 514 | Motor Fuel Dispensing Facilities | not in play | Nothing on this takeoff puts it in play. |
| 515 | Bulk Storage Plants | not in play | Nothing on this takeoff puts it in play. |
| 516 | Spray Application, Dipping, Coating, and Printing Processes | not in play | Nothing on this takeoff puts it in play. |
| 517 | Health Care Facilities | not in play | Nothing on this takeoff puts it in play. |
| 518 | Assembly Occupancies | not in play | Nothing on this takeoff puts it in play. |
| 520 | Theaters, Audience Areas of Motion Picture and Television Studios, Performance Areas, and Similar Locations | not in play | Nothing on this takeoff puts it in play. |
| 522 | Control Systems for Permanent Amusement Attractions | not in play | Nothing on this takeoff puts it in play. |
| 525 | Carnivals, Circuses, Fairs, and Similar Events | not in play | Nothing on this takeoff puts it in play. |
| 530 | Motion Picture and Television Studios and Similar Locations | not in play | Nothing on this takeoff puts it in play. |
| 540 | Motion Picture Projection Rooms | not in play | Nothing on this takeoff puts it in play. |
| 545 | Manufactured Buildings and Relocatable Structures | not in play | Nothing on this takeoff puts it in play. |
| 547 | Agricultural Buildings | not in play | Nothing on this takeoff puts it in play. |
| 550 | Mobile Homes, Manufactured Homes, and Mobile Home Parks | not in play | Nothing on this takeoff puts it in play. |
| 551 | Recreational Vehicles and Recreational Vehicle Parks | not in play | Nothing on this takeoff puts it in play. |
| 552 | Park Trailers | not in play | Nothing on this takeoff puts it in play. |
| 555 | Marinas, Boatyards, Floating Buildings, and Commercial and Noncommercial Docking Facilities | not in play | Nothing on this takeoff puts it in play. |
| 590 | Temporary Installations | not in play | Nothing on this takeoff puts it in play. |
| Nothing on this takeoff puts it in play. |
| 646 | Modular Data Centers | not in play | Nothing on this takeoff puts it in play. |
| 647 | Sensitive Electronic Equipment | not in play | Nothing on this takeoff puts it in play. |
| 650 | Pipe Organs | not in play | Nothing on this takeoff puts it in play. |
| 660 | X-Ray Equipment | not in play | Nothing on this takeoff puts it in play. |
| 665 | Induction and Dielectric Heating Equipment | not in play | Nothing on this takeoff puts it in play. |
| 668 | Electrolytic Cells | not in play | Nothing on this takeoff puts it in play. |
| 669 | Electroplating | not in play | Nothing on this takeoff puts it in play. |
| 670 | Industrial Machinery | not in play | Nothing on this takeoff puts it in play. |
| 675 | Electrically Driven or Controlled Irrigation Machines | not in play | Nothing on this takeoff puts it in play. |
| 680 | Swimming Pools, Fountains, and Similar Installations | not in play | Nothing on this takeoff puts it in play. |
| 682 | Natural and Artificially Made Bodies of Water | not in play | Nothing on this takeoff puts it in play. |
| 685 | Integrated Electrical Systems | not in play | Nothing on this takeoff puts it in play. |
| 690 | Solar Photovoltaic (PV) Systems | not in play | Nothing on this takeoff puts it in play. |
| 691 | Large-Scale Photovoltaic (PV) Electric Supply Stations | not in play | Nothing on this takeoff puts it in play. |
| 692 | Fuel Cell Systems | not in play | Nothing on this takeoff puts it in play. |
| 694 | Wind Electric Systems | not in play | Nothing on this takeoff puts it in play. |
| 695 | Fire Pumps | not in play | Nothing on this takeoff puts it in play. |
| not in play |
| Nothing on this takeoff puts it in play. |
| 725 | Class 1, Class 2, and Class 3 Remote-Control, Signaling, and Power-Limited Circuits | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 726 | Class 4 (CL4) Fault-Managed Power Systems | not in play | Nothing on this takeoff puts it in play. |
| 728 | Fire-Resistive Cable Systems | not in play | Nothing on this takeoff puts it in play. |
| 750 | Energy Management Systems | not in play | Nothing on this takeoff puts it in play. |
| 760 | Fire Alarm Systems | not in play | Nothing on this takeoff puts it in play. |
| 770 | Optical Fiber Cables | not in play | Nothing on this takeoff puts it in play. |