Derived from what the read produced, so none of it can drift from the data behind it. A blocker stops a price being presented as complete; it never stops you looking. These definitions are this build’s own — no RRE document specifies them yet.
| Check | Status | What the check found |
|---|---|---|
| Sheet scale | blocker | Scale is UNSET on 1 of 6 plan sheet(s): E-400. Nothing on them has been measured, so there is no raceway and no branch wire — together the largest block of material on a job of this kind. Set the scale from each title block on the Drawings screen. |
| Sheets read for scope | warning | 43 sheet(s) were indexed but not read for scope: A-004, A-008, 000-Copy-of-2498-A-set-2025-0530-Revision-1-p9, 000-Copy-of-2498-A-set-2025-0530-Revision-1-p10, 000-Copy-of-2498-A-set-2025-0530-Revision-1-p11, 000-Copy-of-2498-A-set-2025-0530-Revision-1-p12, 000-Copy-of-2498-A-set-2025-0530-Revision-1-p13, 000-Copy-of-2498-A-set-2025-0530-Revision-1-p14, A-091, A-140, A-420, A-460, A-501, M-100, M-101, M-102, M-200, M-300, M-400, M-500, M-501, M-600, M-601, M-602, P-100, P-101, P-200, P-300, P-301, 004-Copy-of-2498-Revision-1---Notes-_-changes-p1, 004-Copy-of-2498-Revision-1---Notes-_-changes-p3, 004-Copy-of-2498-Revision-1---Notes-_-changes-p4, 004-Copy-of-2498-Revision-1---Notes-_-changes-p5, 004-Copy-of-2498-Revision-1---Notes-_-changes-p6, 004-Copy-of-2498-Revision-1---Notes-_-changes-p7, S-100, S-200, FP-1, 007-rocklinelectric.net-Mail---Fwd_-Mango--...ion---Invitation-to-bid-DUE-05_08_2025-p1, 007-rocklinelectric.net-Mail---Fwd_-Mango--...ion---Invitation-to-bid-DUE-05_08_2025-p2, 007-rocklinelectric.net-Mail---Fwd_-Mango--...ion---Invitation-to-bid-DUE-05_08_2025-p3, E-400, A-425. Looked at by the takeoff and not read: no electrical work on it. Read them, or state the omission on the proposal — the basis of the offer already prints it. |
| Symbol source | pass | A symbol list was found on the drawings: E-200 — SYMBOLS LIST. The project legend is authoritative for this set and outranks everything else — NECA 100-2006 itself allows a drawing to use non-standard symbols provided the legend explains them. NECA 100-2006 stays underneath it for anything the legend leaves silent, and no conventions file exists for the engineering firm. |
| Symbols named | warning | 3 of 894 marks belong to a group nobody has named. An unnamed group buys nothing, so its count cannot reach a price. Name the groups on the Read-drawing screen and point each at a build-up. |
| Every line prices | blocker | 29 line(s) point at no assembly, so nothing prices them: BREAKER - 1-POLE, IN NEW PANEL, BREAKER - NEW CIRCUITS IN EXISTING PANEL MD, BREAKER - NEW CIRCUITS IN EXISTING PANEL A, BREAKER - NEW CIRCUITS IN EXISTING PANEL B, UNISTRUT TRACK-SUSPENSION SUPPORT SYSTEM (P1000 UNISTRUT W/ ELONGATED HOLES, EC FURNISH & INSTALL), LIGHT FIXTURE TYPE MI-1 (schedule MIRROR W/LED)…. They are counted and reported, and they stay outside the total. Attach a build-up from the catalog, or strike the line. |
| Plan and schedule agree | pass | No line has a plan/schedule disagreement. |
| Lines accepted by a person | blocker | Nothing has been accepted. All 122 line(s) are still suggestions, and machine output is a suggestion until a named person accepts it. Accept on the Takeoff screen — 93 line(s) are ready. |
| Engineer conventions known | pass | No engineer-dependent lines. |
| Unsure flags resolved | pass | The model raised no open flags. |
| Cover sheet read | pass | A cover sheet was found and read; its notes parameterise every later pass. |
What the symbol names rest on. The set’s own legend (E-200), which is authoritative for this project.
| Line | Count | Sheet |
|---|---|---|
TRACK LIGHTING RACEWAY/TRACK, LINEAR Track lighting track sections (unistrut-style modular track), current-limited circuits from Panel CL | 227.1 ft | A-130 |
UNISTRUT TRACK-SUSPENSION SUPPORT SYSTEM (P1000 UNISTRUT W/ ELONGATED HOLES, EC FURNISH & INSTALL) Unistrut channel/box that the 2-circuit commercial-grade track system clips into, per Detail 3 'Track Detail: Suspended', sheet A-006. Sheet note states 'UNISTRUT SYSTEM - PROVIDED INSTALLED BY ELECTRICAL CONTRACTOR'. Explicitly excludes the 3/8" threaded hanger rod and the P1001 long-span bracing Unistrut, both of which the same detail marks 'BY GC'. Quantity is a modeled allowance (trapeze_hanger_rule / hanger_hybrid_layer_rule box-point convention), not a plan count -- this detail sheet shows the assembly section only and does not itself carry a track run length or support-point count; the true count/footage lives on the reflected lighting plan (E-300/E-400), which is outside this agent's assigned read set (see job-facts.md and coverage_gaps above). The allowance ties one support point to each track fixture head recorded in job-facts.md's E-800 Table F schedule (P08.1w x95 + P15.1w x115 = 210 heads total, covering BOTH suspended (Detail 3) and surface-mount (Detail 3A) track families combined -- the split between the two mounting types is not shown anywhere in this agent's read set). | 210 ea | A-500 |
EMERGENCY LIGHT/EGRESS DEVICE TAG EM5 Ceiling-mounted emergency/egress device, plan tag 'EM5'; specific device type (concealed emergency light vs. exit-sign variant vs. strobe/horn) not resolved from text alone | 15 ea | A-130 |
EMERGENCY LIGHT/EGRESS DEVICE TAG EM2 Ceiling-mounted emergency/egress device, plan tag 'EM2'; specific device type (concealed emergency light vs. exit-sign variant vs. strobe/horn) not resolved from text alone | 14 ea | A-130 |
Edition: 2022 California Electrical Code, because in force for permits from 2023-01-01, as of the bid date 2025-05-08. City and county amendments are the AHJ’s: check them on any job inside a city that amends the code. “To check” means the code requires it and the drawings do not show it: send an RFI, or make the call. Nothing here is added to the bid on its own.
| Section | Status | What the code requires | What the takeoff shows | RRE’s practice |
|---|---|---|---|---|
NEC 2020 210.8(B)(2) GFCI on commercial kitchen receptacles | to check | GFCI protection for every receptacle in a commercial kitchen: single-phase up to 50 A and three-phase up to 100 A, 150 V to ground or less. | A kitchen job (DEDICATED POWER CIRCUIT - REFRIGERATOR (KITCHENETTE); DEDICATED POWER CIRCUIT - MICROWAVE (KITCHENETTE); POWER CONNECTION - CHARGING STATION), and no receptacle line says it is in the kitchen: confirm the kitchen receptacles are GFCI. | RRE carries a GFCI receptacle at the device where the set calls for GFCI, and adds none on code alone (Mango: no GFCI bid; The Melt: 25 where the set said so). |
NEC 2020 210.8(B)(1) GFCI on bathroom receptacles | to check | GFCI protection for every receptacle in a bathroom: single-phase up to 50 A and three-phase up to 100 A, 150 V to ground or less. | In play for RECEPTACLE - DUPLEX, WALL-MOUNTED (RESTROOM LAVATORY COUNTER). Nothing on the takeoff shows it. | RRE carries GFCI at the device where the set calls for it. |
NEC 2020 210.8(B) GFCI near sinks, in locker rooms, wet and damp locations | to check | GFCI protection for receptacles within 6 ft of a sink, in locker rooms with showers, in indoor wet or damp locations, and in garages, service bays and similar areas. | In play for RECEPTACLE - DUPLEX, WALL-MOUNTED (RESTROOM LAVATORY COUNTER). Nothing on the takeoff shows it. |
The RRE item carries no price for the part named, so the estimate has the install labor and rough-in only, and the vendor or sub prices the rest. Send the lighting and gear lists from Material list & vendor quotes.
| Line | Needs a price for | Count | Sheet |
|---|---|---|---|
TRACK FIXTURE TYPE P15.1w (schedule Track) Track head, modular/track fixture (Tracks 2/4/6) | LED TRACK SPOT FIXTURE | 115 ea | E-300 |
TRACK FIXTURE TYPE P08.1w (schedule Track) Track head, modular/track fixture, current-limited (fed via Panel CL, Tracks 1/3/5/7) | LED TRACK SPOT FIXTURE | 95 ea | E-300 |
EMERGENCY LIGHT TAG EM5 (remote head or battery-pack option, unresolved) Standalone 'EM5' red text tag at a fixture/device position with no fixture-family prefix | LED EMERGENCYLIGHT DUAL | 14 ea | A-092 |
EMERGENCY LIGHT TAG EM2 (remote head or battery-pack option, unresolved) Standalone 'EM2' red text tag at a fixture/device position with no fixture-family prefix | LED EMERGENCYLIGHT DUAL | 11 ea | A-092 |
LIGHT FIXTURE TYPE EX01 (schedule EX01) Exit sign, 120V LED, 90-min battery back-up, unswitched (circuit 41) | LED GRN EXIT FIXTURE | 6 ea | E-300 |
13 lines the reader wrote at zero are not listed: they add nothing to the bid.
Summed 8 dimensioned LAL runs printed on the plan: LAL01 16'-8", LAL02 16'-8", LAL03 15'-0", LAL04 15'-0", LAL5 29'-8", LAL6 48'-3", LAL7 56'-5", LAL8 60'-9" = 258.42 ft. Matches job-facts.md Table F's LAL parenthetical of 256.6 within 0.7% -- strong confirmation that Table F's LAL number is total feet, not a luminaire count. Billed in FEET per SKILL.md v2.2. STEP 4.5 TOP-5 LABOR RE-DERIVATION: 258.42 ft was re-checked against A-130's independent measurement of the same LAL run (230.7 ft, L-0093) - the two disagree by ~11%, flagged on this line. Re-measuring from the extracted vector geometry (not re-reading the whole sheet) confirms the E-300 dimension_measurement method is internally consistent with the run segments recorded in job-facts.md; the gap to A-130 is carried as a reconciliation item, not silently averaged. (Model line id L-0019.) The model also raised "cross-sheet check (Step 4.5): A-130 RCP independently read this family as 230.7 vs this line's 258.42 (L-0093); E-300 plan count used per policy, reconcile before bid", 'Step 4.5 top-5-labor re-derivation: see updated narrative', which the contract has no flag for; recorded here rather than dropped.
Summed 9 dimensioned LAF runs printed directly on the plan: LAF1-7 (mirror strips) at 16'-4" each = 114'-4", plus LAF8 18'-5" and LAF9(comitted) 7'-3" = 140.0 ft total. This total lands within 0.9% of job-facts.md Table F's LAF parenthetical of 141.2 (read there as total feet, not luminaire count, given this close a match), confirming these 9 runs are the LAF family and that LAF10/LAF10a (billed separately below) are the distinct 'LAF10 Storefront Lighting' schedule row. Billed in FEET per SKILL.md v2.2 (linear/strip fixtures priced by the foot, not per run). STEP 4.5 TOP-5 LABOR RE-DERIVATION: 140.0 ft cross-checked against A-130's independent read of the same LAF run (L-0094, also 140.0 ft) - exact agreement between two different sheets/methods. This line's footage is confirmed, not just modelled. (Model line id L-0017.) The model also raised 'Step 4.5 top-5-labor re-derivation: see updated narrative', which the contract has no flag for; recorded here rather than dropped.
Text-search hits: 94 upright 'P15.1W' + 21 additional hits read as 'P15.1b' (the rotated/vertical placements of the same tag along diagonal Track 2 runs, where PDF text extraction misreads the rotated 'W' glyph) = 109... corrected to 115 by summing both literal strings (94+21=115), which matches job-facts Table F count for P15.1w exactly (115). Confirmed by visual spot-check on crops/topmid.png and crops/midright.png that 'P15.1b' labels sit on rotated copies of the same track-head block as 'P15.1W'. STEP 4.5 TOP-5 LABOR RE-DERIVATION: re-derived by summing A-130's independent tag read (L-0076 P15.1W=94 + L-0077 P15.1b=21 = 115) against this line's single plan-tag count of 115 - exact match once the P15.1b rotated-tag reads are folded in, which confirms the existing flag's hypothesis (P15.1b hits are rotated P15.1W reads) rather than a distinct fixture type. Quantity 115 stands, confidence held at B pending a straight visual tally. (Model line id L-0009.) The model also raised "confirm the 21 'P15.1b' hits are rotated P15.1W reads, not a distinct tag, on the next pass", 'Step 4.5 top-5-labor re-derivation: see updated narrative', which the contract has no flag for; recorded here rather than dropped.
Counted every 'P08.1W' text tag on E-300 via exact word-search on the live PDF text layer (95 hits, page-wide, deduplicated) -- these sit beside the small rectangular track-head marks drawn along TRACK 1, 3, 5 and 7. Matches job-facts.md Table F count for P08.1w exactly (95), so all 95 schedule luminaires of this type live on this sheet. Track heads are billed per-head; track-length footage (8'/4' sections) was NOT separately measured this pass -- see coverage_gaps. STEP 4.5 TOP-5 LABOR RE-DERIVATION: cross-checked against A-130's independent tag read of the same family (L-0075, 95) - exact match. Two sheets, two agents, same count; quantity 95 confirmed, band raised to A on this evidence. (Model line id L-0008.) The model also raised 'Step 4.5 top-5-labor re-derivation: see updated narrative', which the contract has no flag for; recorded here rather than dropped.
28 'E06W' text tags counted on E-300 (exact word-search, page-wide). Matches job-facts.md Table F count for E06W exactly (28) -- all schedule luminaires of this type are on this sheet, drawn as the small pendant/drop-style icon along the 'LAF 9' strip and storefront run. (Model line id L-0010.)
Two dimensioned runs tagged 'LAF10: 13'-8"' and 'LAF10a: 13'-8"' sum to 27'-4" (27.33 ft). job-facts.md Table F lists 'LAF10 Storefront Lighting' as a separate schedule row from generic LAF (count 28 luminaires) -- billed here in feet per policy since it is a strip/linear fixture, not per-luminaire. (Model line id L-0018.) The model also raised 'Table F bills LAF10 by luminaire count (28); this line bills the same tag by measured feet (27.33 ft) per the linear-fixture-in-feet policy -- reconcile units before pricing', which the contract has no flag for; recorded here rather than dropped.
25 'E12.1W' text tags counted on E-300. job-facts.md Table F lists E12.1w(26) -- one short. Per SKILL.md v2.2 policy the PLAN COUNT governs the line quantity; the schedule is the cross-check. Flagging the 1-unit disagreement rather than silently reconciling to the schedule number -- the missing unit may be a duplicate/overlapping glyph the word-search folded into an adjacent tag, or may genuinely live on E-400. (Model line id L-0011.) The model also raised 'plan count (25) vs Table F schedule count (26) disagree by 1 -- flagged per policy, plan count used', which the contract has no flag for; recorded here rather than dropped.
Each of the 3 Point-of-Sale plan symbols shows '(6) DATA LINES (CAT 6A)' per the A-120 legend; 3 positions x 6 lines = 18. Cable spec and punch-down slack note per legend's 'Data Line' row (RJ45/Cat 6A/plenum rated, min 6' left for punch-down). (Model line id L-0071.) The model also raised 'no_priced_assembly', which the contract has no flag for; recorded here rather than dropped.
Counted 14 standalone 'EM5' tags across the full sheet (200-dpi render, 6 non-overlapping tiles) -- the most frequent of the three, scattered through the fitting-room area and the open sales floor. Same unresolved-meaning caveat as EM2/EM3 above -- no legend on this sheet. This is the largest-quantity line on this sheet and carries the most dollar risk if it turns out to double-count fixtures already priced on E-300/E-400. (Model line id L-0059.) The model also raised 'UNSURE whether this is new EC scope or an option flag on an already-counted fixture -- see coverage_gaps', 'no legend on this sheet defines the EM+digit convention', 'highest-quantity line on this sheet -- priority for reconciliation against E-300/E-400', which the contract has no flag for; recorded here rather than dropped.
Note 26-12.22a mandates conduit feed to the cash-counter outlet with exposed conduit painted to match; no homerun tag, panel location, or dimensioned conduit run appears anywhere on this millwork sheet (it has no power plan). Per house policy (stub_assembly_rule, v1.9), a 12-ft jbox+stub allowance is carried at every device connection point until the E-series power plan or riser gives an actual run length. Striking this line would carry the outlet in L-0001 with zero raceway, which understates scope. (Model line id L-0114.) The model also raised 'modelled_allowance', 'no_measurable_footage_on_this_sheet', 'verify_against_E-series_power_plan_or_riser', which the contract has no flag for; recorded here rather than dropped.
11 'E10.1W' text tags counted on E-300 (exterior recessed cans tagged '10,k' along the storefront/canopy edge). This exact tag does NOT appear anywhere in job-facts.md's Table F fixture schedule (which runs E11.1W, E12.1W, E06W, E05W but has no E10.1W row) -- either Table F has an omitted row, or E10.1W is a legend-only variant this pass could not settle against a schedule. assembly_id withheld pending schedule reconciliation. (Model line id L-0014.) The model also raised 'fixture tag E10.1W has no Table F schedule entry -- confirm against E-800/E-801 Table F for a missed row before pricing', which the contract has no flag for; recorded here rather than dropped.
11 'BA' text tags counted on E-300 (back-of-house aisle fixtures tagged '11,f', drawn as a circle-with-X suspended-fixture icon). job-facts.md Table F lists BA(13) -- 2 short of the schedule total. One tag ('BA/EM') was seen combined with an emergency designator and may already be one of the 11 counted rather than an additional unit; the remaining 2-unit gap may sit on E-400. Flagged rather than padded to 13. (Model line id L-0015.) The model also raised 'plan count (11) vs Table F schedule count (13) disagree by 2 -- flagged, plan count used per policy; check E-400 for the remainder', "cross-sheet check (Step 4.5): A-130 RCP independently read this family as 13 vs this line's 11 (L-0079); E-300 plan count used per policy, reconcile before bid", which the contract has no flag for; recorded here rather than dropped.
Counted 11 standalone 'EM2' tags across the full sheet (200-dpi render, 6 non-overlapping tiles: 3 in the fitting-rooms/office quadrant, 2 in the storefront diagonal bump-out, 3 near the stockroom, 3 near sales-floor perimeter). No legend or keyed note on A-092 (or in this run's read set) defines what the digit '2' means -- possibly a remote emergency-head wattage/model class distinct from the numbered EM3/EM5 tags, possibly a battery-pack VA rating on an unlabelled main fixture. Carried as its own line rather than merged with EM3/EM5 because the tag text is visibly distinct on the sheet; see coverage_gaps for the double-count risk against E-300/E-400. (Model line id L-0057.) The model also raised 'UNSURE whether this is new EC scope (remote emergency head + wiring) or an option flag on an already-counted E-300/E-400 fixture -- see coverage_gaps', 'no legend on this sheet defines the EM+digit convention', which the contract has no flag for; recorded here rather than dropped.
9 'E05W' text tags counted on E-300 (fitting-room recessed cans tagged '9,e'). job-facts.md already flagged this exact tag/schedule disagreement: the Table F tag suffix reads 'E05W(9)' but the Table F Total-Number-of-Luminaires column reads 8. This sheet's plan count (9) agrees with the tag-suffix reading, not the column-07 count -- per SKILL.md's plan-count-governs rule this line carries 9, with the schedule's 8 flagged as the disagreement to resolve. (Model line id L-0013.) The model also raised "plan count (9) vs Table F 'Total Number of Luminaires' column (8) disagree -- flagged in job-facts.md, plan count used per policy", which the contract has no flag for; recorded here rather than dropped.
Text layer of A-150 (decoded custom glyph encoding, +29 shift) contains exactly 8 in-plan instances of the word 'WIFI' (ellipse device tag, legend-column instances excluded by x-position < 620pt). Visual zoom crops directly confirmed 6 of the 8 numbered tags: AP-001 (near the storefront/rack wall, top of sales floor), AP-002 (mid sales floor), AP-004 (near the fitting-room row), AP-005 (rear storage aisle), AP-006 (QA/office area), AP-007 (center of sales floor). Per general note 1 on this sheet ('EACH DEVICE A HOME RUN') and note 5 (LAN switch/router lives in the stockroom rack), each of the 8 access points gets its own Cat 6A home run to the rack; general notes 2-3 assign the actual wire pull to GC (=EC per the house default and the A-090 Div 27 matrix, which flagged its own AP-cabling schedule row as needing this sheet's instance count). Striking this line drops the AP cabling multiplier back to A-090's uncounted placeholder of 1. (Model line id L-0096.) The model also raised 'no_priced_assembly', 'resolves_A-090_L-0001_multiplier', which the contract has no flag for; recorded here rather than dropped.
6 'E11.1W' text tags counted on E-300 (aisle recessed cans tagged '7,d'). Matches job-facts.md Table F count for E11.1w exactly (6). (Model line id L-0012.)
6 'EX1' text tags counted on E-300 (small square ceiling-mount exit-sign symbol). Matches job-facts.md Table F count for EX01 exactly (6). A second, visually distinct bold black bar-shaped exit/emergency symbol repeatedly labelled '41/EX' also appears on this sheet, but that label is a CAD block with curve-drawn text (0 hits in the PDF text layer for 'EX' outside the 'EX1'/'EXT.'/'EXISTING' words already accounted for) and was not exhaustively tallied within this pass's time budget -- see coverage_gaps. EX02(1) from Table F was not identified as a distinct symbol on this sheet either. (Model line id L-0016.) The model also raised "EX02 (schedule qty 1) and the black-bar '41/EX' wall-mount exit/emergency symbol were not reconciled to a count this pass -- see coverage_gaps", which the contract has no flag for; recorded here rather than dropped.
Equipment Schedule IT Rack row: Low Voltage cabling column '(6) Cat 6A', 4' length, keyed note 2. Explicit count of 6. (Model line id L-0034.) The model also raised 'no_priced_assembly', which the contract has no flag for; recorded here rather than dropped.
Counted 5 standalone 'EM3' tags across the full sheet (200-dpi render, 6 non-overlapping tiles), clustered around the stockroom/restroom/back-of-house area. Same unresolved-meaning caveat as EM2 above -- no legend on this sheet. (Model line id L-0058.) The model also raised 'UNSURE whether this is new EC scope or an option flag on an already-counted fixture -- see coverage_gaps', 'no legend on this sheet defines the EM+digit convention', which the contract has no flag for; recorded here rather than dropped.
Counted 4 'P01W' text spans on the A-130 RCP, each adjacent to a stand-alone 'S' text tag. No 'P01W' row exists in the E-800 Title-24 Table F schedule captured in job-facts.md. Counted and carried with assembly_id null pending schedule/legend confirmation. (Model line id L-0087.) The model also raised '{\'code\': \'no_schedule_match\', \'note\': "P01W not found in the read E-800 fixture schedule. Adjacent \'S\' tag suggests a switch or spot designation -- confirm against E-300/E-400 or a cutsheet."}', which the contract has no flag for; recorded here rather than dropped.
Counted 4 'P02W' text spans on the A-130 RCP, each adjacent to a stand-alone 'F' text tag. No 'P02W' row exists in the E-800 Title-24 Table F schedule captured in job-facts.md. Counted and carried with assembly_id null pending schedule/legend confirmation. (Model line id L-0088.) The model also raised '{\'code\': \'no_schedule_match\', \'note\': "P02W not found in the read E-800 fixture schedule. Adjacent \'F\' tag suggests a fixed or flood designation -- confirm against E-300/E-400 or a cutsheet."}', which the contract has no flag for; recorded here rather than dropped.
Counted 3 'BA EM' red text tags across a full-sheet visual sweep of A-092 (200-dpi render, 6 non-overlapping tiles, no double-count risk). This ties to the same 'BA' suspended-4' fixture family the E-300 sheet agent counted (11 of a Table F total of 13) -- these 3 units are the ones this job's designer flagged for the emergency battery-pack option on the photometric plan. Striking this line drops the only record on this run of which BA fixtures carry emergency power; it does NOT add new fixture bodies (those are already counted on E-300). (Model line id L-0055.) The model also raised 'cross-check against E-300/E-400 BA count -- this is the EM subset of that same family, not an addition to it', which the contract has no flag for; recorded here rather than dropped.
Counted 3 'Point of Sales' legend symbols along the cash-wrap millwork run (labelled EQ-1a/EQ-1d in plan, matching A-090 Equipment Schedule POS Station rows), one per millwork bay. A-120 Power & Low Voltage legend defines this symbol as '(1) QUADRUPLEX WHITE'. This plan count settles the A-090 coverage gap that carried POS as 1 unverified instance - actual count is 3. (Model line id L-0070.) The model also raised 'no_priced_assembly', which the contract has no flag for; recorded here rather than dropped.
Counted 3 'Cash Counter' legend symbols, one per cash-wrap millwork bay, adjacent to but distinct from the Point-of-Sale symbol in the same bay (legend: Cash Counter = '(1) QUADRUPLEX/WHITE', no data lines). Matches A-090's separate 'POS Station Power' schedule rows describing a white quad plus a dedicated-breaker red quad per counter - this sheet's plan symbol does not distinguish white vs red quad, carried here as 1 general quad per counter position pending A-090 cross-check for the dedicated-circuit variant. (Model line id L-0072.) The model also raised 'no_priced_assembly', 'variant_needs_A-090_cross_check', which the contract has no flag for; recorded here rather than dropped.
Visually located 3 instances of the 'CLK / 54"AFF' hardwire symbol across the plan (near the BOH/kitchenette corridor, at the storefront entry facade, and along a mid-floor demising wall). Legend explicitly defines this symbol as hardwire power for illuminated mirrors. Exact mirror locations/count not cross-checked against interior elevations - see coverage_gaps. (Model line id L-0073.) The model also raised 'no_priced_assembly', 'location_purpose_unconfirmed', 'quantity_needs_full_symbol_scan', which the contract has no flag for; recorded here rather than dropped.
Counted 3 'BA/EM' text spans on the A-130 RCP, in addition to the 13 plain 'BA' tags (L-0005). The E-800 schedule totals BA at 13 with no separate emergency-variant line, so the plan's total of 16 BA-family fixtures (13+3) disagrees with the schedule's 13. Per SKILL.md plan_count_governs_fixture_lines, the plan count (3, additive to L-0005) is carried; the disagreement is flagged rather than resolved. (Model line id L-0080.) The model also raised "{'code': 'plan_schedule_disagreement', 'note': 'Schedule (E-800 Table F) shows BA(13) total; plan shows 13 plain BA + 3 BA/EM = 16. Confirm whether BA/EM are additional fixtures or a re-tag of 3 of the 13 onto the emergency circuit (Panel A ckt 41, lock-on breaker per E-601 keyed note).'}", which the contract has no flag for; recorded here rather than dropped.
Mall Note 11 states 'INTERLOCK EXHAUST FAN WITH BATHROOM LIGHT SWITCHES.' This mandates a control/wiring task at each restroom light switch (tie the fan's neutral/switch-leg to the same switch as the light, or add a relay), which normally falls to the EC. Quantity of 2 is inferred from this sheet's own Scope of Work line 'EXISTING OFFICE AND BOTH RESTROOMS TO BE REUSED' (2 restrooms), not from a plan count - no restroom plan or fan schedule was in this agent's read set. Striking this line would drop the only interlock-wiring requirement found on this sheet. Quantity is inferred, not counted; verify against A-005/A-006 and the M-set exhaust fan schedule. (Model line id L-0022.) The model also raised 'no_priced_assembly', 'quantity_inferred_verify_restroom_count', 'cross_check_mechanical_fan_schedule', which the contract has no flag for; recorded here rather than dropped.
General note item 3 in the description block and the 'UPPER LED WHEN CEILING IS>13'-0"' callout on detail 4 both describe a second LED run added above the base run, conditional on ceiling height exceeding 13'-0", and both say 'Refer to Lighting plan' for where it applies. Quantity of 2 is carried paired with the 2 base-run instances in L-0001 (one possible upper run per panel type documented on this sheet), but this sheet gives no ceiling heights by location, so whether this condition is ever triggered on the actual job cannot be confirmed here - flagged UNSURE and carried as a conditional allowance rather than dropped, since striking it silently would hide a real scope trigger from whoever prices the lighting plan. (Model line id L-0028.) The model also raised 'no_priced_assembly', 'conditional_on_ceiling_height_not_shown_on_this_sheet', 'verify_against_E-300_lighting_plan_or_RCP_ceiling_heights', 'owner_furnished_fixture_ec_install_labor_only', which the contract has no flag for; recorded here rather than dropped.
Detail 2 elevation view explicitly calls out 'PROVIDE TWO QUAD POWER OUTLETS @ 36" AFF. ON CENTER' with two 4-opening receptacle symbols drawn side by side inside the shelf-unit outline; the same count and mounting height are repeated in text under both furnish options (a) and (b) ('Power outlets mounted @ 36" AFF between the top and bottom shelf'). Both the drawn symbol count (2) and the note text ('TWO') agree. Striking this line drops the only EC device scope this detail sheet carries. (Model line id L-0030.) The model also raised 'assembly_id_null_needs_catalog_entry_quad_receptacle', 'reconcile_with_panel_A_ckt32_charging_station_recorded_on_E-601', 'homerun_conduit_wire_to_this_device_not_on_this_sheet_see_coverage_gaps', 'grommet_furnish_responsibility_UNSURE_see_coverage_gaps', which the contract has no flag for; recorded here rather than dropped.
Equipment Schedule EQ-12 'Camera' (Mini-Dome Camera, Retail): '(1) Cat 6A', keyed note 2, 2MP Varifocal IP; 'Camera Screen' (Office): '(1) Cat 6A', keyed note 2. Two Cat 6A drops total. Matrix confirms 'SECURITY CAMERAS WIRING' is G.C.(EC) supply+install while the cameras themselves are Mango supply+install. (Model line id L-0037.) The model also raised 'no_priced_assembly', which the contract has no flag for; recorded here rather than dropped.
Equipment Schedule EQ-17a 'Power Pack' AMS-9060, Entry Door: '(1) Duplex 110V'; EQ-17h 'CapBox', Sensomatic, Sales Area: '(1) Duplex 110V', comment 'GC to coordinate power as necessary'. Two duplex receptacles. (Model line id L-0041.) The model also raised 'no_priced_assembly', which the contract has no flag for; recorded here rather than dropped.
Equipment Schedule EQ-20 Invonics rows: two rows list Low Voltage cabling '4/18awg' with comment 'GC provide and install all wiring' (door opener, door release). (Model line id L-0044.) The model also raised 'no_priced_assembly', which the contract has no flag for; recorded here rather than dropped.
Equipment Schedule EQ-30a/EQ-30b 'Sign - Illuminated', Mango(owner) provider, GC installer, Entrance location, power '110 V' each, keyed note 10. Matches responsibility matrix 'CONNECTION OF SIGNAGE BOXES' = G.C.(EC) supply+install. (Model line id L-0046.) The model also raised 'no_priced_assembly', which the contract has no flag for; recorded here rather than dropped.
Equipment Schedule rows 'Speaker on track' (Owner device, GC wire, '16/2 (V-...' Voltive V-1215, plenum rated wire, keyed note 7) and 'Surface Speakers' (Owner device, Owner install, GC wire, Voltive V-1215 plenum rated). Two 16/2 wire runs, Sales Area. (Model line id L-0049.) The model also raised 'no_priced_assembly', which the contract has no flag for; recorded here rather than dropped.
Counted the text tag 'APPROXIMATE TRENCHING LOCATION' (decoded from the sheet's shifted encoding) on the A-110 plan (detail 1): two distinct rotated call-outs, at page-point centroids approximately (1133, 1160) and (1401, 935), each with a leader to a hatched trench zone. Keyed note 02-42.53 assigns the trenching conduit burial (both low- and line-voltage) as EC/Division 26-28 raceway scope, coordinated with the GC and landlord for the cut. Two locations counted -- see marks/A-110.json. (Model line id L-0067.) The model also raised 'no_dimensioned_length_this_sheet', 'no_assembly_match', which the contract has no flag for; recorded here rather than dropped.
E-601 panel schedule block titled 'NEW CURRENT LIMITING PANEL CL' - 20 poles, 120V, 1Ø/2W, service FEED-THRU, mounting SURFACE, location 'GR 2400 THE SILVERBULLET'. Confirmed as the only NEW gear on this job by the E-600 riser, which shows MSB-South, Panel MB, the 45kVA transformer, Panel A and Panel B all drawn dashed/labelled EXISTING, while CL is the one box fed by a labelled feeder terminating in new equipment. Striking this line removes the only new panel on the job. (Model line id L-0001.)
E-600 riser shows a feeder labelled 'EXISTING 4#4 & 1#8 GND. IN 1-1/4" C.' running from the existing 45kVA transformer secondary to the new Current Limiting Panel box. The conduit/conductor run itself is drawn dashed (existing-to-remain per the sheet legend) so no new raceway or wire is taken off for it here; the only EC work this line captures is the physical termination of those existing conductors onto the new panel's lugs/bus, which is unavoidable new labor regardless of the conduit's age. See coverage_gaps for the risk that this feeder is not actually pre-existing at this exact run. (Model line id L-0003.) The model also raised 'UNSURE - confirm the feeder is truly an existing/reused run and not new conduit+wire mislabelled', which the contract has no flag for; recorded here rather than dropped.
House standard mandates a disconnect at every tenant-wired electric water heater (knowledge/estimators/house.json gear_musts) regardless of whether the schedule shows one explicitly; the EWH circuit itself is read directly off Panel B ckt7/9. This is the house policy line, not a drawn disconnect - it has caused a real miss (NUYO blind #5) when omitted. (Model line id L-0007.)
One 'HUB' tag found on E-300 at the back-of-house wall, with keyed note '#38 (LUTRON VIVE HUB) 2#12 & 1#12 GND. IN 3/4" C.' and a leader to 'LUTRON VIVE SYSTEM: CENTRAL HUB, SEE WIRING DIAGRAM... SEE LIGHTING KEY NOTE 4.' Controls hardware is vendor-quote/labor-only per house default (Lutron via Thea Enterprises, per job-facts.md) -- carried here as a countable device with assembly pending vendor quote. (Model line id L-0020.) The model also raised 'controls hardware furnished-by is UNSURE per job-facts.md (no cover sheet this run) -- hub itself may be vendor-supplied, EC installs', which the contract has no flag for; recorded here rather than dropped.
Cover-sheet Electrical note 30.a states 'TENANT TO INSTALL AN ELECTRIC METER FOR THE MAIN ELECTRICAL SYSTEM. SHOULD BE EITHER QUADLOGIC RSM5 OR S20 METER.' Note 30.b immediately follows with 'FINAL CONNECTION OF TENANTS ELECTRICAL SERVICE SHALL BE BY THE LL CONSTRACTOR,' meaning the EC/tenant sets the meter but the landlord's contractor makes the final service tie-in. No meter location, socket type, or CT-cabinet detail is drawn on this cover sheet; this is a single note-driven allowance, one meter, until the riser (E-600) or A-090 responsibility matrix confirms it. Striking this line would drop the only meter-install item found in this read set. (Model line id L-0021.) The model also raised 'no_priced_assembly', 'unsure_furnish_vs_install', 'verify_against_E-600_riser_and_A-090_matrix', which the contract has no flag for; recorded here rather than dropped.
Read keyed note 06-22.30 'Mirror Panel', item g: 'Provide clock outlet.' This is a millwork/architectural detail sheet (Cortland Morgan Architect A-set), not an E-sheet, but the note mandates a device (a recessed power outlet for a wall clock behind the mirror) that is Division 26/EC scope -- per this run's ec_scope_on_other_disciplines process, EC-scope items found on non-electrical sheets are still taken off. Counted as 1 per the single mirror-panel detail shown on this sheet; the true building-wide count depends on how many fitting-room mirrors of this type exist, which is not shown here (see coverage_gaps). (Model line id L-0024.) The model also raised 'cross_discipline_source_sheet', 'quantity_multiplier_unresolved_pending_floor_plan', 'no_assembly_match', which the contract has no flag for; recorded here rather than dropped.
Equipment Schedule row 'AP-# WiFi Cabling': Owner-provider, G.C. installer, '(1) Cat 6A', 4' length, keyed note 2 'Each a home run to the rack'. Counted as 1 instance; actual AP count is on the power/LV plan, not this schedule. (Model line id L-0031.) The model also raised 'no_priced_assembly', 'quantity_needs_plan_count', which the contract has no flag for; recorded here rather than dropped.
Equipment Schedule EQ-2b 'Speaker Control Relay': GC provider and installer, model RDL Stick-on Series, IT Rack. Comment: 'GC to provide and install relay. Relay to shut in store music off when Fire alam or building alarm is activated. Coordinate with LL.' (Model line id L-0035.) The model also raised 'no_priced_assembly', which the contract has no flag for; recorded here rather than dropped.
Equipment Schedule 'Camera Screen' row, model K5A38AA#ABA, Office: power column '(1) Duplex 110V', keyed note 2. (Model line id L-0036.) The model also raised 'no_priced_assembly', which the contract has no flag for; recorded here rather than dropped.
Equipment Schedule EQ-14 'Refrigerator', Frigidair FFPE3322UM, SS finish, Kitchenette, power '110 V', comment 'GC provided and installed'. (Model line id L-0038.) The model also raised 'no_priced_assembly', which the contract has no flag for; recorded here rather than dropped.
Equipment Schedule EQ-15 'Microwave', Frigidaire FFCM0934LS, SS finish, Kitchenette, power 'Dedicated 110 V', comment 'GC provided and installed'. (Model line id L-0039.) The model also raised 'no_priced_assembly', which the contract has no flag for; recorded here rather than dropped.
Equipment Schedule EQ-17b 'Security Antennas', Sensormatic Concealed, Entry Door: keyed note 5A 'Provide 3/4" conduit below finish floor'. Counted as 1 pedestal location; number of entry doors carrying this device not given on this sheet. (Model line id L-0040.) The model also raised 'no_priced_assembly', 'quantity_needs_plan_count', which the contract has no flag for; recorded here rather than dropped.
Equipment Schedule row 'Façade Flag Sign', GC installer, Façade location, power '110 V', comment 'GC to permit and Install - Ensure that signage is on a timer clock.' Ties to job-facts Sub-Panel B ckt1 SIGNAGE controlled via Lutron Vive time clock (E-900). (Model line id L-0047.) The model also raised 'no_priced_assembly', which the contract has no flag for; recorded here rather than dropped.
Equipment Schedule EQ-38B 'Blade: Illuminated', GC provider AND installer (unlike the other sign rows, which are Owner-provided/GC-installed only). (Model line id L-0048.) The model also raised 'no_priced_assembly', 'furnish_scope_unusual_confirm', which the contract has no flag for; recorded here rather than dropped.
Equipment Schedule 'Subwoofer' row, Ecler Trail SB6T, White, Sales Area, low voltage '14/2 (V-...', 4' length, keyed note 8. (Model line id L-0050.) The model also raised 'no_priced_assembly', which the contract has no flag for; recorded here rather than dropped.
Responsibility Matrix Div 26 row 'LINE WIRE CONNECTION & WIRING OF CASHWRAP': G.C. Supply = X, G.C. Install = X. No length/count given on this sheet; carried as 1 allowance item pending cross-check against the power/telecom plan. (Model line id L-0051.) The model also raised 'no_priced_assembly', 'quantity_needs_plan_count', which the contract has no flag for; recorded here rather than dropped.
Responsibility Matrix Div 27 row 'LOW VOLTAGE DATA PUNCH DOWN': only G.C. Install = X marked (no supply column marked). Carried as 1 allowance item; drop count not given on this sheet. (Model line id L-0052.) The model also raised 'no_priced_assembly', 'quantity_needs_plan_count', which the contract has no flag for; recorded here rather than dropped.
Responsibility Matrix Div 27 rows 'ENTRY DOOR LOOP PRE INSTALLATION COORDINATION' (comment: Sensomatic site survey) and 'ENTRY DOOR LOOP TRENCHING' (comment: Coordinate w/Sensomatic): both G.C. Supply = X, G.C. Install = X. No trench length given on this sheet. (Model line id L-0053.) The model also raised 'no_priced_assembly', 'quantity_needs_plan_count', which the contract has no flag for; recorded here rather than dropped.
Responsibility Matrix Div 27 rows 'LOW VOLTAGE FROM MAIN UTILITY CLOSET TO RETAIL SPACE' and 'CONDUIT FOR ALL LOW VOLTAGE WIRING': both G.C. Supply = X, G.C. Install = X. No route length given on this sheet - the LV/telecom riser plan (A-150, not in this agent's assigned pages per SKILL.md v2.2 note) would carry the footage. (Model line id L-0054.) The model also raised 'no_priced_assembly', 'quantity_needs_plan_count', 'needs_A-150', which the contract has no flag for; recorded here rather than dropped.
One 'QA EM' red text tag found near the stockroom/restroom corridor on A-092. 'QA' does not match any of the 13 fixture types in job-facts.md's Table F (BA, E12.1W, E06W, S02, E05W, E11.1W, LAL, LAF, P08.1w, P15.1w, EX01, EX02, LAF10) -- either an uncatalogued fixture type this run's schedule pages missed, or a mislabel. assembly_id withheld until reconciled. (Model line id L-0056.) The model also raised "fixture family 'QA' has no matching Table F row -- confirm against E-800 pp.1-6 or E-400 before pricing", 'semantic risk: name read from the sheet with no legend/schedule confirmation', which the contract has no flag for; recorded here rather than dropped.
Read keyed note 02-42.52 ('Sensormatic slab scribe'). This is EC/low-voltage scope per house default (LV cabling/raceway = EC pulls, raceway by EC) even though the note is written under the GC-coordinated demolition/slab-work section -- the conduit itself and its antenna-to-wall/ceiling run are electrical material and labor. No footage or antenna-pedestal count is shown on A-110; carried as a lump-sum system allowance pending the security/EAS equipment plan. (Model line id L-0066.) The model also raised 'lump_sum_no_plan_quantity', 'lv_responsibility_unsure_per_job_facts', 'no_assembly_match', which the contract has no flag for; recorded here rather than dropped.
Read keyed note 02-42.60 ('Slab Core Drill'): low voltage and line voltage must be in separate conduits through each core-drilled penetration; conduit sizing is GC-coordinated but the conduit itself is EC material/labor. No specific penetration count or location is shown on A-110 -- carried as a lump-sum coordination/material allowance. (Model line id L-0068.) The model also raised 'lump_sum_no_plan_quantity', 'no_assembly_match', which the contract has no flag for; recorded here rather than dropped.
A-120 labels one location 'CHARGING STATION' in plan, adjacent to the kitchenette sink/hot-water-heater (FX-4/FX-20). This ties to job-facts Panel A's revision-clouded new circuit block (ckt32/34/36/38/40/42) which includes a 'CHARGING STATION' breaker position - confirms this is a new TI device connection, not existing. No receptacle count/type is printed at this tag on A-120 itself; carried as 1 connection pending the power plan's device schedule or a receptacle-count cross-check. (Model line id L-0074.) The model also raised 'no_priced_assembly', 'quantity_needs_plan_count', which the contract has no flag for; recorded here rather than dropped.
Legend row EQ-12 'CCTV Mini Domo: Provide CAT 6A home run to rack. At office camera must point to safe Box.' The matching magenta camera-bubble icon was located once on plan, next to an 'EM3' tag beside the QA/office room cluster in the bottom-left of the floor plate - one confirmed instance. A second, undifferentiated 'CCTV: provide CAT6A home run to rack' icon is also in the legend (implying a retail-floor camera per A-090's EQ-12 'Retail' schedule row) but was not located in the crops read this pass - see coverage_gaps. (Model line id L-0097.) The model also raised 'no_priced_assembly', 'likely_undercount_see_coverage_gaps', which the contract has no flag for; recorded here rather than dropped.
Legend row (tag EQ-20g in the crop, keyed icon) 'Video Recorder+Screen: CAT 6A, and 120V power. Wall-mounted Cabinet.' One legend entry, one wall-mounted cabinet implied; exact ceiling/wall plan position of the cabinet itself was not pinpointed in the crops read (the legend icon column shows the symbol, not a located instance on the floor plan). (Model line id L-0098.) The model also raised 'no_priced_assembly', which the contract has no flag for; recorded here rather than dropped.
Legend row immediately below 'EQ-25 Safe Box': 'Video Recorder: CAT 6A, and 120V power. Wall-mounted Cabinet.' Read as the recorder that watches the safe box (consistent with EQ-12's note that the office camera must point at the safe box) - one instance, power and data both EC scope. (Model line id L-0099.) The model also raised 'no_priced_assembly', which the contract has no flag for; recorded here rather than dropped.
Detail callout '4 = EQ-35: Mango Sign Interior' on A-150 shows a photo of backlit 'MANGO' letters on a wood-slat wall - the only one of the four interior sign details on this sheet (EQ-33, EQ-34, EQ-35, EQ-36c) that visually reads as illuminated. Note 'FOR SIGNAGE SCHEDULE REFER TO A-090' on this sheet means the actual circuit/VA spec lives there; carried here as a 1-count placeholder pending that cross-check (see coverage_gaps). (Model line id L-0100.) The model also raised 'no_priced_assembly', 'illumination_unconfirmed', which the contract has no flag for; recorded here rather than dropped.
View 3 (Existing Storefront Window Section, 1"=1'-0") on A-210 carries the keyed note 'POWER ELECT. PASS THRU KIT' directly beside 'MANGO EQ-30a SIGN FASTENED AND SECURED TO THE FACE OF THE WALL', at the display-area side of the storefront frame. This names the physical fitting the EC installs to bring power through the wall to the sign cabinet. Read visually and by text extraction (page text is in the PDF's pre-rotation coordinate space; positions transformed via the page's rotation matrix to match the displayed sheet). Cross-references A-200's sign elevation, which shows the same EQ-30a tag and already carries an EC connection-point line (L-0002) pending this sheet's detail - see coverage_gaps for the possible-duplicate flag between the two sheets. (Model line id L-0104.) The model also raised 'no_priced_assembly', 'assembly_id_unmapped', 'possible_duplicate_with_A-200_signage_lines', which the contract has no flag for; recorded here rather than dropped.
View 1 (Storefront Window Display Section, 1"=1'-0") on A-210 carries the keyed note 'POWER ELECT. PASS THRU KIT' directly beside 'MANGO EQ-30b SIGN FASTENED AND SECURED TO THE FACE OF THE WALL'. Same fitting/scope as L-0001, at the second (display-platform) storefront bay. Cross-references A-200's sign elevation (EQ-30b tag, existing line L-0001 on that sheet) - see coverage_gaps for the possible-duplicate flag. (Model line id L-0105.) The model also raised 'no_priced_assembly', 'assembly_id_unmapped', 'possible_duplicate_with_A-200_signage_lines', which the contract has no flag for; recorded here rather than dropped.
View 1 (Storefront Window Display Section) shows the new built-up platform display (06-50, 06-50C 3/4" plywood over flooring, non-illuminated logo at angled surface) with the note 'GC TO PROVIDE POWER AS INDICATED IN SHEET A-120.00'. This is the only power note on the sheet naming 'GC' rather than 'EC'; carried here as one EC connection point per house convention (GC notes for power on architectural finish/equipment sheets are typically executed by the electrical subcontractor), but the responsibility is not confirmed by a matrix on this sheet and A-120.00 (the sheet the note points to) was not in this agent's assigned page set - see coverage_gaps. (Model line id L-0107.) The model also raised 'no_priced_assembly', 'assembly_id_unmapped', 'responsibility_unconfirmed_GC_vs_EC', 'referenced_sheet_A-120.00_not_in_read_set', which the contract has no flag for; recorded here rather than dropped.
Interior Section/Elevation 6 (A-300, top-left of sheet) draws a pictorial wall-mounted exit sign - a rounded-cabinet box with a hanging bracket and the word 'EXIT' legible inside it - directly above the head of a door leading out of the back-of-house corridor. No alphanumeric fixture tag (EX01/EX02) is printed beside the icon on this sheet; job-facts' E-800 Title-24 fixture schedule carries EX01(6 luminaires) and EX02(1 luminaire) for the whole project (7 total exit signs), and the tag-to-instance mapping for this specific door is expected on the E-300/E-400 lighting plan, not on this elevation sheet. Counted as one confirmed exit-sign fixture instance visible on A-300; not a substitute for the E-800 schedule total. Read visually at 8-10x zoom crops because the page's text layer is garbled (same failure mode as A-200). (Model line id L-0108.) The model also raised 'no_priced_assembly', 'schedule_tag_not_on_this_sheet', 'circuit_routing_off_sheet', which the contract has no flag for; recorded here rather than dropped.
On A-310 (page 28), one of six 'Interior Section/Elevation' details shows a wall-mounted EXIT sign pictogram drawn as vector line-art (rendered 'EXIT' lettering, not a text-layer tag) sitting on a visible standoff bracket - two circular mounting fasteners top and bottom holding the sign fixture proud of the finished wall, positioned high on the wall near a ceiling soffit line above a door/opening. Confirmed by rendering the page (set to unrotated/raw coordinate space to match the PDF text layer, mediabox 1728x2592) at 14x zoom over raw rect (680,290)-(780,360) and reading the crop directly. This detail is evidence for the EC's exit-sign INSTALL condition (a bracket-mounted, standoff sign rather than a simple surface box) at at least one of the job's 7 exit-sign locations; the fixture count itself is not re-counted here (see coverage_gaps) - striking this line removes the bracket/support labor and material for that mounting condition, leaving only the bare fixture connection assumed elsewhere. (Model line id L-0110.) The model also raised 'no_priced_assembly', 'new_no_blind_evidence', 'cross_reference_E-800_do_not_duplicate_fixture_count', 'quantity_may_need_scaling_to_all_7_exit_signs_pending_E-300/E-400_mount_type_check', which the contract has no flag for; recorded here rather than dropped.
Hall Elevation (view 7), sheet A-320, 400dpi crop review: a circle-EXIT-circle exit-sign icon is drawn on the corridor wall above the door, at roughly 3'-0" AFF relative to the 9'-5" ceiling line. No adjacent plan tag was legible on this sheet (the sheet's text layer uses a non-standard glyph encoding that defeated text search, and no printed tag is visible on the rendered icon itself). Counted as one exit-sign device toward the job-wide EX01/EX02 total on the E-800 T-24 schedule (7 units total); striking this line does not change the job total by itself since the schedule count already governs, but the sheet confirms one physical location for that total. (Model line id L-0111.) The model also raised 'assembly_id_null_needs_catalog_entry_exit_sign', 'fixture_tag_not_shown_on_this_sheet_reconcile_with_E-800_EX01_EX02_schedule_and_E-300/E-400_plan', 'possible_duplicate_of_count_already_taken_from_E-800_schedule_by_another_sheet_agent', which the contract has no flag for; recorded here rather than dropped.
Restroom Elevation (view 2), sheet A-320, 400/600dpi crop review: a standard duplex-receptacle symbol (two-slot rectangle) is drawn on the wall directly above the lavatory sink (FX-4), left of the mirror/paper-towel dispenser group. This is the only receptacle symbol this agent found across the sheet's seven elevations within the read window; the other restroom elevation (view 3) shows no comparable symbol at the equivalent wall. No panel/circuit/homerun text accompanies it on this sheet -- device count only, to be reconciled against the E-series power plan's own symbol count for this room per coverage_gaps. (Model line id L-0112.) The model also raised 'assembly_id_null_needs_catalog_entry_duplex_receptacle', 'reconcile_against_E-series_power_plan_symbol_count_avoid_double_count', 'branch_circuit_wire_conduit_to_this_device_not_on_this_sheet', which the contract has no flag for; recorded here rather than dropped.
Detail 3 'M-1: Section at Cash Counter' (bottom-left of the sheet) shows a rounded-square device symbol with a dashed centerline crosshair set into the counter's side-wall base, roughly 4" AFF next to the B-10/05-26.1d edge-band callout. This is the recessed outlet mandated by keyed note 26-12.23 and coordinated per 26-12.22. The sheet draws exactly one instance of this symbol; the true count of cash-counter positions (and therefore of this device) is governed by the number of POS positions per counter, which this sheet explicitly defers to A-120/A-140 (see coverage_gaps). Quantity is carried here as 1 representative unit per the typical detail; striking this line drops the only recessed-outlet device found on this sheet. (Model line id L-0113.) The model also raised 'no_priced_assembly', 'quantity_depends_on_POS_count_see_A-120_A-140', 'verify_against_millwork_shop_drawings', which the contract has no flag for; recorded here rather than dropped.
Detail 3 shows the leader-called-out tag '27-21.4' immediately above and sharing the callout cluster with '26-12.22', both pointing into the cash-wrap cabinet/counter zone - i.e. the data drop and the power drop are provisioned at the same location. A-400 itself carries no descriptive text for 27-21.4 (its notes column only spells out 05-25, 06-30.25, 26-12.22, and 26-12.23); the note's content was cross-referenced from A-002 General Notes, read by another sheet-agent this run, which assigns EC the conduit pull and home run with a 6 ft tail, and the owner's vendor the termination. Carried here at 1 representative unit for the same reason as L-0001 - true count depends on POS positions per A-120/A-140. (Model line id L-0115.) The model also raised 'no_priced_assembly', 'quantity_depends_on_POS_count_see_A-120_A-140', 'note_text_cross_referenced_from_A-002_not_on_this_sheet', 'termination_by_owners_vendor_not_EC', which the contract has no flag for; recorded here rather than dropped.
Read note 26-50.21 'Continuous led per schedule' in the Division 26-50 Interior Lighting notes block, cross-referenced to the leader callout '26-50.21' on detail item 5 'Detail @ M-2A Millwork', pointing at the cabinet's vertical corner. The sheet gives no dimensioned run length (no measurement is derivable), so this line is recorded as 1 location rather than a footage; the project's whole-building LED-strip totals (LAL/LAF families) are already carried in the E-800 fixture schedule per job-facts.md and are not re-added here. (Model line id L-0117.) The model also raised 'footage_not_measurable_this_sheet', 'cross_reference_E-300_E-400_for_actual_run_length', 'possible_overlap_with_E-800_fixture_schedule_totals', which the contract has no flag for; recorded here rather than dropped.
Read the 'NOTE: SIGNAGE INSIDE TENANT SPACE' leader with callout '26-50.21' on 'Elevation @ M-2B Millwork' (item 2), pointing to the recessed 'MANGO' logo lettering at the top of the millwork wall. No fixture tag, wattage, or count is given here; counted as 1 signage element. (Model line id L-0118.) The model also raised 'needs_catalog_entry', 'confirm_furnish_by_sign_vendor_vs_EC_see_coverage_gaps', 'confirm_committed_roundel_unlit', which the contract has no flag for; recorded here rather than dropped.
Door schedule row #05 (Retail to Storage, type B, single, notes 1,2,7A,10,12) carries keyed note 7A: 'Door from Retail to Back of House. GC to coordinate with tenant alarm company and to provide the necessary wiring and power. Provide Key pad connected to local alarm on sales side.' Read from the door-schedule table and notes block, rendered at 400-500dpi (the table is not present in the page's extracted text layer -- see sheet.note). Per house default #3/#4 (job-facts.md), the keypad hardware is vendor-furnished/coordinated with the tenant's alarm company; EC scope is the power circuit, box and low-voltage pull to it. Striking this line drops the sales-side keypad connection at this one door. (Model line id L-0119.) The model also raised 'no_priced_assembly', 'needs_assembly_mapping', 'possible_duplicate_of_A-090_A-150_device', which the contract has no flag for; recorded here rather than dropped.
Same keyed note 7A as L-0001 continues: 'Provide push alarm release on employee side.' This is a second, distinct device from the sales-side keypad, on the Back-of-House face of the same door #05 opening. GC/EC scope is wiring and power per note 7A; the alarm-release hardware itself is tenant-alarm-company coordinated. Striking this line drops the employee-side push-alarm-release wiring at this door. (Model line id L-0120.) The model also raised 'no_priced_assembly', 'needs_assembly_mapping', 'possible_duplicate_of_A-090_A-150_device', which the contract has no flag for; recorded here rather than dropped.
Door schedule row #06 (BOH Hallway to Storage, type A, single, notes 2,7C,12; hardware 'ALLEGION CO 100 Satin Chrome(626) LAT lever on Corridor side, Panic bar on Storage side', keylock from Hall side) carries keyed note 7C: 'Door from Service to Back of House. GC to coordinate with tenant alarm company and to provide the necessary wiring and power. Provide Allegion CO 100 or similar. Key pad from exterior for control access.' EC scope per house default is the power circuit, box and low-voltage pull to the keypad; Allegion hardware is vendor-furnished. Striking this line drops door #06's exterior keypad connection. (Model line id L-0121.) The model also raised 'no_priced_assembly', 'needs_assembly_mapping', 'possible_duplicate_of_A-090_A-150_device', which the contract has no flag for; recorded here rather than dropped.
Door schedule row #07 (BOH Hallway to Office, type A, single, notes 2,7B,12; hardware 'ALLEGION CO 100 Satin Chrome(626) LAT lever, Keypad on storage side', keylock from Storage side) carries keyed note 7B: 'Door to Office. Provide Allegion CO 100 or similar. Key Pad exterior / latch, keyless release on interior.' EC scope per house default is power/box/LV pull to the keypad; hardware is vendor-furnished. Striking this line drops door #07's exterior keypad connection. (Model line id L-0122.) The model also raised 'no_priced_assembly', 'needs_assembly_mapping', 'possible_duplicate_of_A-090_A-150_device', which the contract has no flag for; recorded here rather than dropped.
Door schedule row EX-01 (Hall to Exterior, existing 90-min rated door, VIF, Replace/Sec, notes 7C,9,10,12) hardware column reads: 'ALLEGION CO 100 Satin Chrome(626) LAT lever, (KeyPad) on Mall Corridor side, Panic bar on Corridor side, Keypad on Mall Corridor side: CO-100-993R-70-KP-LAT'; Latch = Panic; Lock = 'Electron ic locks with Keypad / Panic locks'. Note 7C (referenced) assigns GC coordination with the tenant alarm company plus wiring and power. Read from the door-schedule table render; EC scope is power/box/LV pull, hardware vendor-furnished per house default. Striking this line drops EX-01's exterior keypad/electric-panic-lock power and low-voltage connection. (Model line id L-0123.) The model also raised 'no_priced_assembly', 'needs_assembly_mapping', 'possible_duplicate_of_A-090_A-150_device', which the contract has no flag for; recorded here rather than dropped.
Door schedule row EX-01's Stop column reads 'Electromagnetic Holder' (against 'Existing' closer, notes 7C,9,10,12 - '90 min rated existing door'). General keyed note 2 on this sheet states: 'All electromagnetic door hold openers to be coordinated with fire alarm system for compliance.' EX-01 is the only door on this schedule whose Stop hardware is an electromagnetic holder (all others use Norton/LCN mechanical closers or none) - this is the device the sorter flagged for this sheet. EC scope per house default is the power circuit and the interconnect wiring to the fire-alarm system that releases the holder on alarm; the holder unit itself and its FA-side programming are vendor/fire-alarm-contractor scope. No fire-alarm riser was in this agent's read set to confirm which trade pulls the interconnect leg - see coverage_gaps. (Model line id L-0124.) The model also raised 'no_priced_assembly', 'needs_assembly_mapping', 'possible_duplicate_of_A-090_A-150_device', 'fa_interconnect_scope_unconfirmed', which the contract has no flag for; recorded here rather than dropped.
Added by house rule: RRE priced this on 4 of 4 past jobs (100%). RRE’s last retail job carried 8 hours of panel safe-off; RRE practice is about 1 hour per panel touched, 8 hours on BYLT and Varley too. Recommended: RRE Components 31784, 8HRS PANELS SAFE OFF, once.
Read keyed note 02-26.40.c: 'Contractor shall remove all existing electrical power and data to main panel complete with all related conduits, wire, junction box and/or fittings, typ.' No plan symbols or quantities of the removed devices/runs are shown on A-110 -- carried as a whole-space demolition lump sum. Read as EC scope (the physical removal of electrical/data raceway and wire) even though the note uses the bare word 'Contractor' rather than 'EC' -- see coverage_gaps for the responsibility-wording flag. (Model line id L-0061.) The model also raised 'lump_sum_no_plan_quantity', 'cross_discipline_wording_GC_vs_EC', 'no_assembly_match', which the contract has no flag for; recorded here rather than dropped.
Read keyed note 02-26.40.d: 'All lighting to be removed complete with any fittings and blocking. Branch wiring to be removed back to its source.' Note 02-26.40.e ('Branch wiring may be used if it meets current codes and standards') is a reuse-allowance qualifier, not an additional removal quantity, so it is not billed as its own line -- flagged in the narrative for the estimator's branch-wire takeoff on the E-series sheets. No fixture count is shown on A-110 itself; the existing fixture count/type lives on the lighting/RCP plans read elsewhere this run. (Model line id L-0062.) The model also raised 'lump_sum_no_plan_quantity', 'no_assembly_match', which the contract has no flag for; recorded here rather than dropped.
Read keyed note 02-42.12 ('Existing non-load bearing partition to be removed'), item b: 'Remove any existing electrical outlets and conduits within wall.' A-110's plan view does not tag which specific partitions on this floor are the ones being removed (that detail lives on the architectural demolition floor plan's wall-removal hatch, not decoded/measured this pass) -- carried as a lump sum. (Model line id L-0065.) The model also raised 'lump_sum_no_plan_quantity', 'no_assembly_match', which the contract has no flag for; recorded here rather than dropped.
A-111 (Demolition Reflected Ceiling Plan, page 19) is an architectural demo RCP with a general note 'All pipes, ducts, conduits, finishes, equipment, etc., not being reused, must be removed. Do no abandon in place' plus the specific callout 'EXISTING LIGHTS TO BE REMOVED' over the sales-floor ceiling, and a legend distinguishing 'existing conditions to be removed' (red hatch, applies to most of the plan area) from 'existing to remain' (gray hatch, applied only to the two labeled HVAC units) and 'not in scope'. Manual zoom of the vector plan confirms recurring small recessed-can/spot fixture icons throughout the red-hatched area, consistent with the note. No fixture tags or a lighting schedule appear on this sheet, so this is carried as a lump-sum demo/disconnect scope item rather than a per-fixture count; striking this line would drop the EC's demo/disconnect scope for existing lighting entirely. A symbol-vector scan was attempted and is not usable here (see coverage_gaps) -- the geometry is dominated by ceiling-grid hatch fragments, not isolable fixture icons. (Model line id L-0069.) The model also raised 'no_plan_count', 'no_fixture_schedule_on_sheet', 'quantity_is_allowance_not_a_count', 'confirm_via_field_verification_or_existing_lighting_plan', which the contract has no flag for; recorded here rather than dropped.
LOW VOLTAGE CABLING - ENTRY SECURITY/EAS SYSTEM Cat 6A cable drops, 4' length, entry EAS system: power pack, security antennas, RFID (2), siren, reserve | 6 ea | A-500 |
EMERGENCY LIGHT/EGRESS DEVICE TAG EM3 Ceiling-mounted emergency/egress device, plan tag 'EM3'; specific device type (concealed emergency light vs. exit-sign variant vs. strobe/horn) not resolved from text alone | 6 ea | A-130 |
EXISTING ELECTRICAL PANEL FIELD-VERIFICATION / CERTIFIED REPORT EC to field-verify condition/code-compliance of existing electrical panel(s) and provide a certified report of existing electrical panel(s) and services, per keyed note 02-26.40.a/.b ('Existing electrical panel(s) to remain if code compliant. GC to confirm that the existing panel complies with current building code and that it can be re-used.' / 'GC to provide a certified report of existing electrical panel and services.') | 4 ea | A-110 |
LOW VOLTAGE CABLING - BURGLAR ALARM (6/18AWG) 6/18AWG cable, GC provide and install all wiring, Invonics burglar alarm devices (access keypad, alarm keypad, control panel) | 3 ea | A-500 |
LIGHT FIXTURE TYPE 26-50.21 LED STRIP (base run, Oak Wall Panel/Repisa) Owner-furnished continuous LED strip light and LED driver, EC/GC-installed in aluminum channel with diffuser at 'TOP OF MILLWORK' (8'-2" AFF) on the Oak Wall Panel/Repisa millwork assembly, per keyed note 26-50.21 ('Continuous led per schedule... to be installed with aluminum channel and diffuser... At cabinets led strip to be fully recessed') and the furnish/install split at notes 06-30.30/06-30.31 (owner furnishes shelf, T-bracket, Z-bracket, LED and LED drivers; GC/EC installs the LED, conceals fasteners, provides glue/biscuits at joints). Documented once per panel type on this sheet: elevation 2B (M12 type A & M7 Wall Panel and Repisa) and elevation 3B (M12 type B & M7 Wall Panel and Repisa) each show one 'LED LIGHT' callout at top of millwork. | 2 ea | 000-Copy-of-2498-A-set-2025-0530-Revision-1-p38 |
POWER RECEPTACLE - IT RACK (BACK OF HOUSE) Quad receptacle, IT rack, back of house (Owner-provide rack, GC install, min 2 quads) | 2 ea | A-500 |
POWER & DATA CONNECTION - POS STATION AT CASH COUNTER Quad receptacle (white, general), quad receptacle (red, dedicated breaker), duplex receptacle (white) at cash counter, plus (6) Cat 6A data drops with metal junction box, per cash counter | 1 ea | A-500 |
POWER & LOW VOLTAGE - BURGLAR ALARM SOUNDER/VIDEO RECORDER Duplex receptacle 110V plus (1) Cat 6A drop, Invonics sounder/alarm - video recorder, GC provide and install | 1 ea | A-500 |
EXISTING OUTLET/SWITCH DEVICE REMOVAL OR REPLACEMENT Where an outlet/switch/device is not required, remove completely and patch surface; where an outlet/switch/device is to remain, replace the device for new finishes with a screwless-type cover plate, per keyed note 02-26.41.a/.b | 1 ls | A-110 |
EXISTING LIGHT FIXTURE RELAMP / REWIRE ALLOWANCE Existing light fixtures to be re-used: replace damaged fixtures, relamp all fixtures with 3500K lamps to ensure light color consistency, rewire/recircuit as necessary, per keyed note 02-26.45.a-d | 1 ls | A-110 |
EMERGENCY LIGHT/EGRESS DEVICE TAG EM1 Ceiling-mounted emergency/egress device, plan tag 'EM1'; specific device type (concealed emergency light vs. exit-sign variant vs. strobe/horn) not resolved from text alone | 1 ea | A-130 |
SIGNAGE POWER CONNECTION - INTERIOR ILLUMINATED SIGN EQ-38b EC power connection (J-box + whip + local disconnect per house standard) to interior backlit 'MANGO' ceiling-display sign box, tagged EQ-38b, mounted over the hallway/entry opening at Ext. Ceiling Display height 11'-0" AFF | 1 ea | A-300 |
LED REMOTE TRANSFORMER (millwork cabinet, back-of-cash-counter, note 26-50.23) LED remote transformer/driver installed concealed inside the back-cash-counter millwork cabinet per keyed note 26-50.23: accessible and well vented; if installed in an adjacent wall/column enclosure or ceiling, a taped-in access panel is required. Detail item 5 ('Detail @ M-2A Millwork', 3"=1'-0") shows one transformer symbol near the top of the cabinet interior alongside a 'Provide 2" Diameter Opening' callout in the millwork top, read as the cable pass-through for the driver's low-voltage output leg. | 1 ea | A-410 |
PLYWOOD BACKBOARD 4'x4' - LOW VOLTAGE/DATA BACKBOARD 4'x4' fire-rated plywood backboard for LV/data termination point, wall mounted | 1 ea | E-601 |
| — |
NEC 2020 210.62 Receptacles in show windows | to check | At least one 125-volt receptacle within 18 in. of the top of a show window for each 12 linear ft of show window. | In play for LED DRIVER/TRANSFORMER POWER CONNECTION & ACCESS COORDINATION; SIGNAGE POWER PASS-THRU KIT - EQ-30b (Storefront Window Display Section, view 1). Nothing on the takeoff shows it. | — |
NEC 2020 250.30 Grounding a transformer (separately derived system) | to check | A transformer secondary is grounded as a separately derived system: a system bonding jumper, a grounding electrode conductor to an electrode, and the supply-side bonding jumper sized from 250.102. | In play for LED DRIVER/TRANSFORMER POWER CONNECTION & ACCESS COORDINATION; TRANSFORMER, CONCEALED IN ACCESS PANEL (DIV 26 KEYED NOTE 26-50.23); LED DRIVER / REMOTE TRANSFORMER FOR LIGHT FIXTURE TYPE MI-1; and 1 more. Nothing on the takeoff shows it. | — |
NEC 2020 406.12 Tamper-resistant receptacles | to check | Tamper-resistant 15- and 20-ampere, 125- and 250-volt receptacles in dwellings, guest rooms and dormitories, child care, preschools and schools, business offices, corridors, waiting rooms, clinics, medical and dental offices, outpatient facilities, assembly occupancies and the other areas the section lists. | In play for POWER RECEPTACLE - CAMERA MONITOR (OFFICE). Nothing on the takeoff shows it. | — |
NEC 2020 625.40, 625.54 EV charging: individual circuit and GFCI | to check | Each outlet for EV charging on an individual branch circuit, receptacles for EV charging GFCI protected, and EVSE over 60 A or 150 V to ground with a lockable disconnect. | In play for RECEPTACLE - QUAD, MILLWORK-MOUNTED (M-14 CHARGING STATION); POWER CONNECTION - CHARGING STATION. Nothing on the takeoff shows it. | — |
NEC 2020 422.31, 424.19, 430.102 Disconnect for water heaters, heaters, fans and motor loads | shown | A disconnect within sight of the appliance, heater or motor, or a branch-circuit breaker that can be locked in the open position. | In play for EXHAUST FAN / BATHROOM LIGHT SWITCH INTERLOCK WIRING; GEAR - EWH DISCONNECT. Shown: GEAR - EWH DISCONNECT. | A lockable breaker answers it as well as a switch: check the panel schedule before adding a disconnect. |
NEC 2020 450.3(B) Transformer overcurrent protection | shown | Primary (and where used, secondary) overcurrent protection for each transformer within the percentages of Table 450.3(B), and the secondary conductors protected per 240.21(C). | In play for LED DRIVER/TRANSFORMER POWER CONNECTION & ACCESS COORDINATION; TRANSFORMER, CONCEALED IN ACCESS PANEL (DIV 26 KEYED NOTE 26-50.23); LED DRIVER / REMOTE TRANSFORMER FOR LIGHT FIXTURE TYPE MI-1; and 1 more. Shown: BREAKER - NEW CIRCUITS IN EXISTING PANEL MD; LIGHT FIXTURE TYPE MI-1 (schedule MIRROR W/LED). | — |
NEC 2020 600.5(A) Sign outlet at each tenant entrance | shown | At least one outlet at each entrance to each tenant space accessible to pedestrians, for a sign, on a 20-ampere branch circuit that supplies no other load. | Shown: EMERGENCY LIGHT/EGRESS DEVICE TAG EM5; EMERGENCY LIGHT/EGRESS DEVICE TAG EM2; EMERGENCY LIGHT/EGRESS DEVICE TAG EM3; and 16 more. | RRE prices "power to building signage" where the set shows it; the matrix row is left blank where it does not. |
NEC 2020 600.6 Disconnect within sight of a sign | shown | Each sign or outline lighting system, or its feeder, has an externally operable disconnect within sight of the sign, or one capable of being locked in the open position. | In play for EMERGENCY LIGHT/EGRESS DEVICE TAG EM5; EMERGENCY LIGHT/EGRESS DEVICE TAG EM2; EMERGENCY LIGHT/EGRESS DEVICE TAG EM3; and 14 more. Shown: SIGNAGE POWER CONNECTION - ILLUMINATED SIGN BOX EQ-30b; GEAR - EWH DISCONNECT; RECEPTACLE CLOCK OUTLET; and 4 more. | RRE prices a WP switch at signage as a fused disconnect assembly (firm practice wp_switch_mapping). |
NEC 2020 Chapter 9 Table 1, 358.22 Conduit fill | shown | Over two conductors, a raceway is filled to no more than 40 % of its internal area (Chapter 9 Tables 1, 4 and 5; THHN conductors, EMT). | All 1 callout naming conductors and conduit is within it. | — |
A takeoff cannot settle every article: load calculations and coordination are the engineer of record’s, and workmanship is the inspector’s. Each is listed so nothing is silently skipped. “Waiting on a code read” means the article is in play and this job’s drawing read has not been checked against the code yet: re-run the read, or check it on the drawings.
| 90 | Introduction | general | Scope and definitions: nothing to check on a job. |
| 100 | Definitions | general | Scope and definitions: nothing to check on a job. |
| 110 | Requirements for Electrical Installations | checked | In play; none of its checked sections applies to these lines. |
| 200 | Use and Identification of Grounded Conductors | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 210 | Branch Circuits | to check | 4 sections checked against the takeoff, 4 to check: 210.8(B)(2), 210.8(B)(1), 210.8(B), 210.62. |
| 215 | Feeders | checked | In play; none of its checked sections applies to these lines. |
| 220 | Branch-Circuit, Feeder, and Service Load Calculations | design | The engineer of record’s: sizing, calculation or coordination, not checked against a takeoff. |
| 225 | Outside Branch Circuits and Feeders | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 230 | Services | checked | In play; none of its checked sections applies to these lines. |
| 240 | Overcurrent Protection | checked | In play; none of its checked sections applies to these lines. |
| 242 | Overvoltage Protection | not in play | Nothing on this takeoff puts it in play. |
| 250 | Grounding and Bonding | to check | 1 section checked against the takeoff, 1 to check: 250.30. |
| 300 | General Requirements for Wiring Methods and Materials | checked | In play; none of its checked sections applies to these lines. |
| 310 | Conductors for General Wiring | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 311 | Medium Voltage Conductors and Cable | not in play | Nothing on this takeoff puts it in play. |
| 312 | Cabinets, Cutout Boxes, and Meter Socket Enclosures | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 314 | Outlet, Device, Pull, and Junction Boxes; Conduit Bodies; Fittings; and Handhole Enclosures | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 320 | Armored Cable: Type AC | not in play | Nothing on this takeoff puts it in play. |
| 322 | Flat Cable Assemblies: Type FC | not in play | Nothing on this takeoff puts it in play. |
| 324 | Flat Conductor Cable: Type FCC | not in play | Nothing on this takeoff puts it in play. |
| 326 | Integrated Gas Spacer Cable: Type IGS | not in play | Nothing on this takeoff puts it in play. |
| 400 | Flexible Cords and Flexible Cables | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 402 | Fixture Wires | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 404 | Switches | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 406 | Receptacles, Cord Connectors, and Attachment Plugs (Caps) | to check | 1 section checked against the takeoff, 1 to check: 406.12. |
| 408 | Switchboards, Switchgear, and Panelboards | checked | In play; none of its checked sections applies to these lines. |
| 409 | Industrial Control Panels | not in play | Nothing on this takeoff puts it in play. |
| 410 | Luminaires, Lampholders, and Lamps | checked | In play; none of its checked sections applies to these lines. |
| 411 | Low-Voltage Lighting | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 422 | Appliances | checked | 1 section checked against the takeoff, all shown. |
| 500 | Hazardous (Classified) Locations, Classes I, II, and III, Divisions 1 and 2 | not in play | Nothing on this takeoff puts it in play. |
| 501 | Class I Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 502 | Class II Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 503 | Class III Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 504 | Intrinsically Safe Systems | not in play | Nothing on this takeoff puts it in play. |
| 505 | Zone 0, 1, and 2 Locations | not in play | Nothing on this takeoff puts it in play. |
| 506 | Zone 20, 21, and 22 Locations for Combustible Dusts or Ignitible Fibers/Flyings | not in play | Nothing on this takeoff puts it in play. |
| 510 | Hazardous (Classified) Locations — Specific | not in play | Nothing on this takeoff puts it in play. |
| 511 | Commercial Garages, Repair and Storage | not in play | Nothing on this takeoff puts it in play. |
| 513 | Aircraft Hangars | not in play |
| 600 | Electric Signs and Outline Lighting | checked | 2 sections checked against the takeoff, all shown. |
| 604 | Manufactured Wiring Systems | not in play | Nothing on this takeoff puts it in play. |
| 605 | Office Furnishings | not in play | Nothing on this takeoff puts it in play. |
| 610 | Cranes and Hoists | not in play | Nothing on this takeoff puts it in play. |
| 620 | Elevators, Dumbwaiters, Escalators, Moving Walks, Platform Lifts, and Stairway Chairlifts | not in play | Nothing on this takeoff puts it in play. |
| 625 | Electric Vehicle Power Transfer System | to check | 1 section checked against the takeoff, 1 to check: 625.40, 625.54. |
| 626 | Electrified Truck Parking Spaces | not in play | Nothing on this takeoff puts it in play. |
| 630 | Electric Welders | not in play | Nothing on this takeoff puts it in play. |
| 640 | Audio Signal Processing, Amplification, and Reproduction Equipment | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 645 | Information Technology Equipment |
| 700 | Emergency Systems | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 701 | Legally Required Standby Systems | not in play | Nothing on this takeoff puts it in play. |
| 702 | Optional Standby Systems | not in play | Nothing on this takeoff puts it in play. |
| 705 | Interconnected Electric Power Production Sources | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 706 | Energy Storage Systems | not in play | Nothing on this takeoff puts it in play. |
| 708 | Critical Operations Power Systems (COPS) | not in play | Nothing on this takeoff puts it in play. |
| 710 | Stand-Alone Systems | not in play | Nothing on this takeoff puts it in play. |
| 712 | Direct Current Microgrids | not in play | Nothing on this takeoff puts it in play. |
| 720 | Circuits and Equipment Operating at Less Than 50 Volts | not in play | Nothing on this takeoff puts it in play. |
| 725 | Class 1, Class 2, and Class 3 Remote-Control, Signaling, and Power-Limited Circuits |
| 800 | General Requirements for Communications Systems | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 805 | Communications Circuits | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 810 | Radio and Television Antenna Equipment | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 820 | Community Antenna Television and Radio Distribution Systems | not in play | Nothing on this takeoff puts it in play. |
| 830 | Network-Powered Broadband Communications Systems | not in play | Nothing on this takeoff puts it in play. |
| 840 | Premises-Powered Broadband Communications Systems | not in play | Nothing on this takeoff puts it in play. |
| Ch. 9 | Tables: conduit fill, conductor properties, power-limited sources | checked | 1 section checked against the takeoff, all shown. |
EMERGENCY LIGHT TAG EM3 (remote head or battery-pack option, unresolved) Standalone 'EM3' red text tag at a fixture/device position with no fixture-family prefix | LED EMERGENCYLIGHT DUAL | 5 ea | A-092 |
LIGHT FIXTURE TYPE BA (schedule BA) -- EM emergency battery-pack option Suspended 4' light fixture (Table F 'BA') shown on the photometric plan with an 'EM' battery-pack designator per Lighting Note 6 -- EC wiring/connection of the integral battery pack, not a separate fixture body | LED EMERGENCYLIGHT DUAL | 3 ea | A-092 |
LIGHT FIXTURE TYPE BA/EM (schedule BA) Suspended 4' light fixture, emergency-circuit tagged variant | LED EMERGENCYLIGHT DUAL | 3 ea | A-130 |
LIGHT FIXTURE TYPE QA (schedule: not found) -- EM emergency battery-pack option Fixture family 'QA' with an 'EM' battery-pack designator -- no Table F schedule row exists for 'QA' anywhere in this run's read set | LED EMERGENCYLIGHT DUAL | 1 ea | A-092 |
LIGHT FIXTURE TYPE EXIT SIGN (schedule EX01 or EX02, tag not printed on A-300) Wall-mounted illuminated EXIT sign fixture, shown pictorially above the corridor/back-of-house door head in Interior Section/Elevation 6; EC furnish-connect per house standard off the emergency lighting circuit | LED GRN EXIT FIXTURE | 1 ea | A-300 |
EXIT SIGN FIXTURE - WALL-MOUNT STANDOFF BRACKET SUPPORT Wall-mounted illuminated exit sign fixture shown in interior elevation, mounted high on wall via a two-point standoff bracket/arm (not flush or ceiling-mounted); support hardware for one exit-sign location. Fixture itself is already carried in the E-800 fixture schedule count of 7 (EX01 x6 + EX02 x1) - this line covers the mounting bracket/support only, so it must not be added to the E-800 fixture unit count. | LED GRN EXIT FIXTURE | 1 ea | A-310 |
LIGHT FIXTURE TYPE EXIT (schedule EX01 or EX02) Illuminated wall/ceiling-mounted EXIT sign fixture shown above the corridor door in the Hall Elevation, view 7, sheet A-320. No fixture tag is printed beside the icon on this sheet; job-facts.md's E-800 Title-24 fixture schedule carries two exit-sign types (EX01, 6 units, 28W and EX02, 1 unit, 28W) that this unit is one of. Emergency/unswitched circuiting per job-facts (Panel A ckt41, lock-on breaker) is recorded elsewhere from E-601 by another sheet agent -- this line is the device count only. | LED GRN EXIT FIXTURE | 1 ea | A-320 |
| Line | Needs a price for | Count | Sheet |
|---|---|---|---|
TRANSFORMER, CONCEALED IN ACCESS PANEL (DIV 26 KEYED NOTE 26-50.23) Signage/lighting step-down transformer, concealed behind a taped-in ceiling/wall access panel, at each of the two storefront window section details (existing bay and display-platform bay) | the gear itself (no RRE item picked yet) | 2 ea | A-210 |
LED DRIVER / REMOTE TRANSFORMER FOR LIGHT FIXTURE TYPE MI-1 Remote LED transformer serving the mirror LED strip (L-0002), installed concealed in an accessible cabinet or closet per spec 26-50.22; a cavity for the transformer is shown behind/below the mirror at the fitting-room table detail with a leader labeled 'LINE OF CAVITY FOR TRANSFORMER' and 'TO LED TRANSFORMER'. Note requires the transformer be accessible and well-vented, with a taped-in access panel if built into an adjacent wall/column/ceiling enclosure. | the gear itself (no RRE item picked yet) | 1 ea | A-500 |
LED REMOTE TRANSFORMER (millwork cabinet, back-of-cash-counter, note 26-50.23) LED remote transformer/driver installed concealed inside the back-cash-counter millwork cabinet per keyed note 26-50.23: accessible and well vented; if installed in an adjacent wall/column enclosure or ceiling, a taped-in access panel is required. Detail item 5 ('Detail @ M-2A Millwork', 3"=1'-0") shows one transformer symbol near the top of the cabinet interior alongside a 'Provide 2" Diameter Opening' callout in the millwork top, read as the cable pass-through for the driver's low-voltage output leg. | the gear itself (no RRE item picked yet) | 1 ea | A-410 |
Read off the schedules and notes. RRE buys none of the material named here. Check each against the responsibility matrix on the proposal: these are what it should say is by others.
| Line | Furnished by | Installed by | RRE’s part | Sheet |
|---|---|---|---|---|
CONDUIT TO CASH-COUNTER RECESSED OUTLET The drawings say “by others”. | Others | Others | Not RRE’s: furnished and installed by others | A-400 |
LIGHT FIXTURE TYPE 26-50.21 LED STRIP (base run, Oak Wall Panel/Repisa) The drawings say “owner-furnished”. | Owner | not stated | RRE installs / connects only | 000-Copy-of-2498-A-set-2025-0530-Revision-1-p38 |
LIGHT FIXTURE TYPE 26-50.21 LED STRIP (conditional upper run, ceiling >13'-0") The drawings say “owner-furnished”. | Owner | not stated | RRE installs / connects only | 000-Copy-of-2498-A-set-2025-0530-Revision-1-p38 |
LED DRIVER/TRANSFORMER POWER CONNECTION & ACCESS COORDINATION The drawings say “owner-furnished”. | Owner | not stated | RRE installs / connects only | 000-Copy-of-2498-A-set-2025-0530-Revision-1-p38 |
POWER CONNECTION - ILLUMINATED SIGN (ENTRANCE) The drawings say “owner-furnished”. | Owner | not stated | RRE installs / connects only | A-500 |
LUTRON VIVE CENTRAL HUB The drawings say “vendor-supplied”. | Vendor | not stated | RRE installs / connects only | E-300 |
SIGNAGE - ILLUMINATED BLADE SIGN (GC FURNISH & INSTALL) The drawings say “owner-furnished”. | Owner | not stated | RRE installs / connects only | A-500 |
LOW VOLTAGE / LINE VOLTAGE SLAB CORE DRILL COORDINATION The drawings say “by gc”. | GC | not stated | RRE installs / connects only | A-110 |
POWER & LOW VOLTAGE - ACCESS CONTROL KEYPAD (DOOR #05, RETAIL TO STORAGE, SALES SIDE) The drawings say “vendor-furnished”. | Vendor | not stated | RRE installs / connects only | A-500 |
POWER & LOW VOLTAGE - ACCESS CONTROL KEYPAD (DOOR #06, BOH HALLWAY TO STORAGE, EXTERIOR-FACE CONTROL) The drawings say “vendor-furnished”. | Vendor | not stated | RRE installs / connects only | A-500 |
POWER & LOW VOLTAGE - ACCESS CONTROL KEYPAD (DOOR #07, BOH HALLWAY TO OFFICE, EXTERIOR-FACE CONTROL, KEYLESS RELEASE INTERIOR) The drawings say “vendor-furnished”. | Vendor | not stated | RRE installs / connects only | A-500 |
POWER & LOW VOLTAGE - ELECTRIC PANIC HARDWARE WITH KEYPAD (DOOR EX-01, MALL CORRIDOR EGRESS DOOR) The drawings say “vendor-furnished”. | Vendor | not stated | RRE installs / connects only | A-500 |
DEMOLITION OF EXISTING ELECTRICAL POWER & DATA TO MAIN PANEL Struck by Firm policy: RRE does not bid demolition: Demolition by others: RRE does not bid demolition. | — | not stated | Struck: not in this bid | A-110 |
DEMOLITION OF EXISTING LIGHTING & BRANCH WIRING Struck by Firm policy: RRE does not bid demolition: Demolition by others: RRE does not bid demolition. | — | not stated | Struck: not in this bid | A-110 |
REMOVAL OF ELECTRICAL OUTLETS/CONDUIT IN DEMOLISHED PARTITION Struck by Firm policy: RRE does not bid demolition: Demolition by others: RRE does not bid demolition. | — | not stated | Struck: not in this bid | A-110 |
DEMO - EXISTING CEILING LIGHT FIXTURES (REMOVE, TYPE UNSPECIFIED) Struck by Firm policy: RRE does not bid demolition: Demolition by others: RRE does not bid demolition. | — | not stated | Struck: not in this bid | A-111 |
| 330 | Metal-Clad Cable: Type MC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 332 | Mineral-Insulated, Metal-Sheathed Cable: Type MI | not in play | Nothing on this takeoff puts it in play. |
| 334 | Nonmetallic-Sheathed Cable: Types NM and NMC | not in play | Nothing on this takeoff puts it in play. |
| 336 | Power and Control Tray Cable: Type TC | not in play | Nothing on this takeoff puts it in play. |
| 337 | Type P Cable | not in play | Nothing on this takeoff puts it in play. |
| 338 | Service-Entrance Cable: Types SE and USE | not in play | Nothing on this takeoff puts it in play. |
| 340 | Underground Feeder and Branch-Circuit Cable: Type UF | not in play | Nothing on this takeoff puts it in play. |
| 342 | Intermediate Metal Conduit: Type IMC | not in play | Nothing on this takeoff puts it in play. |
| 344 | Rigid Metal Conduit: Type RMC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 348 | Flexible Metal Conduit: Type FMC | not in play | Nothing on this takeoff puts it in play. |
| 350 | Liquidtight Flexible Metal Conduit: Type LFMC | not in play | Nothing on this takeoff puts it in play. |
| 352 | Rigid Polyvinyl Chloride Conduit: Type PVC | not in play | Nothing on this takeoff puts it in play. |
| 353 | High Density Polyethylene Conduit: Type HDPE Conduit | not in play | Nothing on this takeoff puts it in play. |
| 354 | Nonmetallic Underground Conduit with Conductors: Type NUCC | not in play | Nothing on this takeoff puts it in play. |
| 355 | Reinforced Thermosetting Resin Conduit: Type RTRC | not in play | Nothing on this takeoff puts it in play. |
| 356 | Liquidtight Flexible Nonmetallic Conduit: Type LFNC | not in play | Nothing on this takeoff puts it in play. |
| 358 | Electrical Metallic Tubing: Type EMT | checked | In play; none of its checked sections applies to these lines. |
| 360 | Flexible Metallic Tubing: Type FMT | not in play | Nothing on this takeoff puts it in play. |
| 362 | Electrical Nonmetallic Tubing: Type ENT | not in play | Nothing on this takeoff puts it in play. |
| 366 | Auxiliary Gutters | not in play | Nothing on this takeoff puts it in play. |
| 368 | Busways | not in play | Nothing on this takeoff puts it in play. |
| 369 | Insulated Bus Pipe (IBP)/Tubular Covered Conductors (TCC) Systems | not in play | Nothing on this takeoff puts it in play. |
| 370 | Cablebus | not in play | Nothing on this takeoff puts it in play. |
| 371 | Flexible Bus Systems | not in play | Nothing on this takeoff puts it in play. |
| 372 | Cellular Concrete Floor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 374 | Cellular Metal Floor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 376 | Metal Wireways | not in play | Nothing on this takeoff puts it in play. |
| 378 | Nonmetallic Wireways | not in play | Nothing on this takeoff puts it in play. |
| 380 | Multioutlet Assembly | not in play | Nothing on this takeoff puts it in play. |
| 382 | Nonmetallic Extensions | not in play | Nothing on this takeoff puts it in play. |
| 384 | Strut-Type Channel Raceway | not in play | Nothing on this takeoff puts it in play. |
| 386 | Surface Metal Raceways | not in play | Nothing on this takeoff puts it in play. |
| 388 | Surface Nonmetallic Raceways | not in play | Nothing on this takeoff puts it in play. |
| 390 | Underfloor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 392 | Cable Trays | not in play | Nothing on this takeoff puts it in play. |
| 393 | Low-Voltage Suspended Ceiling Power Distribution Systems | not in play | Nothing on this takeoff puts it in play. |
| 394 | Concealed Knob-and-Tube Wiring | not in play | Nothing on this takeoff puts it in play. |
| 396 | Messenger-Supported Wiring | not in play | Nothing on this takeoff puts it in play. |
| 398 | Open Wiring on Insulators | not in play | Nothing on this takeoff puts it in play. |
| 399 | Outdoor, Overhead Conductors over 1000 Volts | not in play | Nothing on this takeoff puts it in play. |
| 424 |
| Fixed Electric Space-Heating Equipment |
| not in play |
| Nothing on this takeoff puts it in play. |
| 425 | Fixed Resistance and Electrode Industrial Process Heating Equipment | not in play | Nothing on this takeoff puts it in play. |
| 426 | Fixed Outdoor Electric Deicing and Snow-Melting Equipment | not in play | Nothing on this takeoff puts it in play. |
| 427 | Fixed Electric Heating Equipment for Pipelines and Vessels | not in play | Nothing on this takeoff puts it in play. |
| 430 | Motors, Motor Circuits, and Controllers | checked | In play; none of its checked sections applies to these lines. |
| 440 | Air-Conditioning and Refrigerating Equipment | checked | In play; none of its checked sections applies to these lines. |
| 445 | Generators | not in play | Nothing on this takeoff puts it in play. |
| 450 | Transformers and Transformer Vaults (Including Secondary Ties) | checked | 1 section checked against the takeoff, all shown. |
| 455 | Phase Converters | not in play | Nothing on this takeoff puts it in play. |
| 460 | Capacitors | not in play | Nothing on this takeoff puts it in play. |
| 470 | Resistors and Reactors | not in play | Nothing on this takeoff puts it in play. |
| 480 | Stationary Standby Batteries | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 490 | Equipment Over 1000 Volts, Nominal | not in play | Nothing on this takeoff puts it in play. |
| Nothing on this takeoff puts it in play. |
| 514 | Motor Fuel Dispensing Facilities | not in play | Nothing on this takeoff puts it in play. |
| 515 | Bulk Storage Plants | not in play | Nothing on this takeoff puts it in play. |
| 516 | Spray Application, Dipping, Coating, and Printing Processes | not in play | Nothing on this takeoff puts it in play. |
| 517 | Health Care Facilities | not in play | Nothing on this takeoff puts it in play. |
| 518 | Assembly Occupancies | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 520 | Theaters, Audience Areas of Motion Picture and Television Studios, Performance Areas, and Similar Locations | not in play | Nothing on this takeoff puts it in play. |
| 522 | Control Systems for Permanent Amusement Attractions | not in play | Nothing on this takeoff puts it in play. |
| 525 | Carnivals, Circuses, Fairs, and Similar Events | not in play | Nothing on this takeoff puts it in play. |
| 530 | Motion Picture and Television Studios and Similar Locations | not in play | Nothing on this takeoff puts it in play. |
| 540 | Motion Picture Projection Rooms | not in play | Nothing on this takeoff puts it in play. |
| 545 | Manufactured Buildings and Relocatable Structures | not in play | Nothing on this takeoff puts it in play. |
| 547 | Agricultural Buildings | not in play | Nothing on this takeoff puts it in play. |
| 550 | Mobile Homes, Manufactured Homes, and Mobile Home Parks | not in play | Nothing on this takeoff puts it in play. |
| 551 | Recreational Vehicles and Recreational Vehicle Parks | not in play | Nothing on this takeoff puts it in play. |
| 552 | Park Trailers | not in play | Nothing on this takeoff puts it in play. |
| 555 | Marinas, Boatyards, Floating Buildings, and Commercial and Noncommercial Docking Facilities | not in play | Nothing on this takeoff puts it in play. |
| 590 | Temporary Installations | not in play | Nothing on this takeoff puts it in play. |
| Nothing on this takeoff puts it in play. |
| 646 | Modular Data Centers | not in play | Nothing on this takeoff puts it in play. |
| 647 | Sensitive Electronic Equipment | not in play | Nothing on this takeoff puts it in play. |
| 650 | Pipe Organs | not in play | Nothing on this takeoff puts it in play. |
| 660 | X-Ray Equipment | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 665 | Induction and Dielectric Heating Equipment | not in play | Nothing on this takeoff puts it in play. |
| 668 | Electrolytic Cells | not in play | Nothing on this takeoff puts it in play. |
| 669 | Electroplating | not in play | Nothing on this takeoff puts it in play. |
| 670 | Industrial Machinery | not in play | Nothing on this takeoff puts it in play. |
| 675 | Electrically Driven or Controlled Irrigation Machines | not in play | Nothing on this takeoff puts it in play. |
| 680 | Swimming Pools, Fountains, and Similar Installations | not in play | Nothing on this takeoff puts it in play. |
| 682 | Natural and Artificially Made Bodies of Water | not in play | Nothing on this takeoff puts it in play. |
| 685 | Integrated Electrical Systems | not in play | Nothing on this takeoff puts it in play. |
| 690 | Solar Photovoltaic (PV) Systems | not in play | Nothing on this takeoff puts it in play. |
| 691 | Large-Scale Photovoltaic (PV) Electric Supply Stations | not in play | Nothing on this takeoff puts it in play. |
| 692 | Fuel Cell Systems | not in play | Nothing on this takeoff puts it in play. |
| 694 | Wind Electric Systems | not in play | Nothing on this takeoff puts it in play. |
| 695 | Fire Pumps | not in play | Nothing on this takeoff puts it in play. |
| not read yet |
| In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 727 | Instrumentation Tray Cable: Type ITC | not in play | Nothing on this takeoff puts it in play. |
| 728 | Fire-Resistive Cable Systems | not in play | Nothing on this takeoff puts it in play. |
| 750 | Energy Management Systems | not in play | Nothing on this takeoff puts it in play. |
| 760 | Fire Alarm Systems | checked | In play; none of its checked sections applies to these lines. |
| 770 | Optical Fiber Cables | not in play | Nothing on this takeoff puts it in play. |