Derived from what the read produced, so none of it can drift from the data behind it. A blocker stops a price being presented as complete; it never stops you looking. These definitions are this build’s own — no RRE document specifies them yet.
| Check | Status | What the check found |
|---|---|---|
| Sheet scale | blocker | Scale is UNSET on 1 of 6 plan sheet(s): E-400. Nothing on them has been measured, so there is no raceway and no branch wire — together the largest block of material on a job of this kind. Set the scale from each title block on the Drawings screen. |
| Sheets read for scope | warning | 43 sheet(s) were indexed but not read for scope: A-004, A-008, 000-Copy-of-2498-A-set-2025-0530-Revision-1-p9, 000-Copy-of-2498-A-set-2025-0530-Revision-1-p10, 000-Copy-of-2498-A-set-2025-0530-Revision-1-p11, 000-Copy-of-2498-A-set-2025-0530-Revision-1-p12, 000-Copy-of-2498-A-set-2025-0530-Revision-1-p13, 000-Copy-of-2498-A-set-2025-0530-Revision-1-p14, A-091, A-140, A-420, A-460, A-501, M-100, M-101, M-102, M-200, M-300, M-400, M-500, M-501, M-600, M-601, M-602, P-100, P-101, P-200, P-300, P-301, 004-Copy-of-2498-Revision-1---Notes-_-changes-p1, 004-Copy-of-2498-Revision-1---Notes-_-changes-p3, 004-Copy-of-2498-Revision-1---Notes-_-changes-p4, 004-Copy-of-2498-Revision-1---Notes-_-changes-p5, 004-Copy-of-2498-Revision-1---Notes-_-changes-p6, 004-Copy-of-2498-Revision-1---Notes-_-changes-p7, S-100, S-200, FP-1, 007-rocklinelectric.net-Mail---Fwd_-Mango--...ion---Invitation-to-bid-DUE-05_08_2025-p1, 007-rocklinelectric.net-Mail---Fwd_-Mango--...ion---Invitation-to-bid-DUE-05_08_2025-p2, 007-rocklinelectric.net-Mail---Fwd_-Mango--...ion---Invitation-to-bid-DUE-05_08_2025-p3, E-400, A-425. Looked at by the takeoff and not read: no electrical work on it. Read them, or state the omission on the proposal — the basis of the offer already prints it. |
| Symbol source | pass | A symbol list was found on the drawings: E-200 — SYMBOLS LIST. The project legend is authoritative for this set and outranks everything else — NECA 100-2006 itself allows a drawing to use non-standard symbols provided the legend explains them. NECA 100-2006 stays underneath it for anything the legend leaves silent, and no conventions file exists for the engineering firm. |
| Symbols named | warning | 3 of 894 marks belong to a group nobody has named. An unnamed group buys nothing, so its count cannot reach a price. Name the groups on the Read-drawing screen and point each at a build-up. |
| Every line prices | blocker | 29 line(s) point at no assembly, so nothing prices them: BREAKER - 1-POLE, IN NEW PANEL, BREAKER - NEW CIRCUITS IN EXISTING PANEL MD, BREAKER - NEW CIRCUITS IN EXISTING PANEL A, BREAKER - NEW CIRCUITS IN EXISTING PANEL B, UNISTRUT TRACK-SUSPENSION SUPPORT SYSTEM (P1000 UNISTRUT W/ ELONGATED HOLES, EC FURNISH & INSTALL), LIGHT FIXTURE TYPE MI-1 (schedule MIRROR W/LED)…. They are counted and reported, and they stay outside the total. Attach a build-up from the catalog, or strike the line. |
| Plan and schedule agree | pass | No line has a plan/schedule disagreement. |
| Lines accepted by a person | blocker | Nothing has been accepted. All 122 line(s) are still suggestions, and machine output is a suggestion until a named person accepts it. Accept on the Takeoff screen — 93 line(s) are ready. |
| Engineer conventions known | pass | No engineer-dependent lines. |
| Unsure flags resolved | pass | The model raised no open flags. |
| Cover sheet read | pass | A cover sheet was found and read; its notes parameterise every later pass. |
What the symbol names rest on. The set’s own legend (E-200), which is authoritative for this project.
| Line | Count | Sheet |
|---|---|---|
TRACK LIGHTING RACEWAY/TRACK, LINEAR Track lighting track sections (unistrut-style modular track), current-limited circuits from Panel CL | 227.1 ft | A-130 |
UNISTRUT TRACK-SUSPENSION SUPPORT SYSTEM (P1000 UNISTRUT W/ ELONGATED HOLES, EC FURNISH & INSTALL) Unistrut channel/box that the 2-circuit commercial-grade track system clips into, per Detail 3 'Track Detail: Suspended', sheet A-006. Sheet note states 'UNISTRUT SYSTEM - PROVIDED INSTALLED BY ELECTRICAL CONTRACTOR'. Explicitly excludes the 3/8" threaded hanger rod and the P1001 long-span bracing Unistrut, both of which the same detail marks 'BY GC'. Quantity is a modeled allowance (trapeze_hanger_rule / hanger_hybrid_layer_rule box-point convention), not a plan count -- this detail sheet shows the assembly section only and does not itself carry a track run length or support-point count; the true count/footage lives on the reflected lighting plan (E-300/E-400), which is outside this agent's assigned read set (see job-facts.md and coverage_gaps above). The allowance ties one support point to each track fixture head recorded in job-facts.md's E-800 Table F schedule (P08.1w x95 + P15.1w x115 = 210 heads total, covering BOTH suspended (Detail 3) and surface-mount (Detail 3A) track families combined -- the split between the two mounting types is not shown anywhere in this agent's read set). | 210 ea | A-500 |
EMERGENCY LIGHT/EGRESS DEVICE TAG EM5 Ceiling-mounted emergency/egress device, plan tag 'EM5'; specific device type (concealed emergency light vs. exit-sign variant vs. strobe/horn) not resolved from text alone | 15 ea | A-130 |
EMERGENCY LIGHT/EGRESS DEVICE TAG EM2 Ceiling-mounted emergency/egress device, plan tag 'EM2'; specific device type (concealed emergency light vs. exit-sign variant vs. strobe/horn) not resolved from text alone | 14 ea | A-130 |
Edition: 2022 California Electrical Code, because in force for permits from 2023-01-01, as of the bid date 2025-05-08. City and county amendments are the AHJ’s: check them on any job inside a city that amends the code. “To check” means the code requires it and the drawings do not show it: send an RFI, or make the call. Nothing here is added to the bid on its own.
| Section | Status | What the code requires | What the takeoff shows | RRE’s practice |
|---|---|---|---|---|
NEC 2020 210.8(B)(2) GFCI on commercial kitchen receptacles | to check | GFCI protection for every receptacle in a commercial kitchen: single-phase up to 50 A and three-phase up to 100 A, 150 V to ground or less. | A kitchen job (DEDICATED POWER CIRCUIT - REFRIGERATOR (KITCHENETTE); DEDICATED POWER CIRCUIT - MICROWAVE (KITCHENETTE); POWER CONNECTION - CHARGING STATION), and no receptacle line says it is in the kitchen: confirm the kitchen receptacles are GFCI. | RRE carries a GFCI receptacle at the device where the set calls for GFCI, and adds none on code alone (Mango: no GFCI bid; The Melt: 25 where the set said so). |
NEC 2020 210.8(B)(1) GFCI on bathroom receptacles | to check | GFCI protection for every receptacle in a bathroom: single-phase up to 50 A and three-phase up to 100 A, 150 V to ground or less. | In play for RECEPTACLE - DUPLEX, WALL-MOUNTED (RESTROOM LAVATORY COUNTER). Nothing on the takeoff shows it. | RRE carries GFCI at the device where the set calls for it. |
NEC 2020 210.8(B) GFCI near sinks, in locker rooms, wet and damp locations | to check | GFCI protection for receptacles within 6 ft of a sink, in locker rooms with showers, in indoor wet or damp locations, and in garages, service bays and similar areas. | In play for RECEPTACLE - DUPLEX, WALL-MOUNTED (RESTROOM LAVATORY COUNTER). Nothing on the takeoff shows it. |
The RRE item carries no price for the part named, so the estimate has the install labor and rough-in only, and the vendor or sub prices the rest. Send the lighting and gear lists from Material list & vendor quotes.
| Line | Needs a price for | Count | Sheet |
|---|---|---|---|
TRACK FIXTURE TYPE P15.1w (schedule Track) Track head, modular/track fixture (Tracks 2/4/6) | LED TRACK SPOT FIXTURE | 115 ea | E-300 |
TRACK FIXTURE TYPE P08.1w (schedule Track) Track head, modular/track fixture, current-limited (fed via Panel CL, Tracks 1/3/5/7) | LED TRACK SPOT FIXTURE | 95 ea | E-300 |
EMERGENCY LIGHT TAG EM5 (remote head or battery-pack option, unresolved) Standalone 'EM5' red text tag at a fixture/device position with no fixture-family prefix | LED EMERGENCYLIGHT DUAL | 14 ea | A-092 |
EMERGENCY LIGHT TAG EM2 (remote head or battery-pack option, unresolved) Standalone 'EM2' red text tag at a fixture/device position with no fixture-family prefix | LED EMERGENCYLIGHT DUAL | 11 ea | A-092 |
LIGHT FIXTURE TYPE EX01 (schedule EX01) Exit sign, 120V LED, 90-min battery back-up, unswitched (circuit 41) | LED GRN EXIT FIXTURE | 6 ea | E-300 |
13 lines the reader wrote at zero are not listed: they add nothing to the bid.
Nothing in this tab.
LOW VOLTAGE CABLING - ENTRY SECURITY/EAS SYSTEM Cat 6A cable drops, 4' length, entry EAS system: power pack, security antennas, RFID (2), siren, reserve | 6 ea | A-500 |
EMERGENCY LIGHT/EGRESS DEVICE TAG EM3 Ceiling-mounted emergency/egress device, plan tag 'EM3'; specific device type (concealed emergency light vs. exit-sign variant vs. strobe/horn) not resolved from text alone | 6 ea | A-130 |
EXISTING ELECTRICAL PANEL FIELD-VERIFICATION / CERTIFIED REPORT EC to field-verify condition/code-compliance of existing electrical panel(s) and provide a certified report of existing electrical panel(s) and services, per keyed note 02-26.40.a/.b ('Existing electrical panel(s) to remain if code compliant. GC to confirm that the existing panel complies with current building code and that it can be re-used.' / 'GC to provide a certified report of existing electrical panel and services.') | 4 ea | A-110 |
LOW VOLTAGE CABLING - BURGLAR ALARM (6/18AWG) 6/18AWG cable, GC provide and install all wiring, Invonics burglar alarm devices (access keypad, alarm keypad, control panel) | 3 ea | A-500 |
LIGHT FIXTURE TYPE 26-50.21 LED STRIP (base run, Oak Wall Panel/Repisa) Owner-furnished continuous LED strip light and LED driver, EC/GC-installed in aluminum channel with diffuser at 'TOP OF MILLWORK' (8'-2" AFF) on the Oak Wall Panel/Repisa millwork assembly, per keyed note 26-50.21 ('Continuous led per schedule... to be installed with aluminum channel and diffuser... At cabinets led strip to be fully recessed') and the furnish/install split at notes 06-30.30/06-30.31 (owner furnishes shelf, T-bracket, Z-bracket, LED and LED drivers; GC/EC installs the LED, conceals fasteners, provides glue/biscuits at joints). Documented once per panel type on this sheet: elevation 2B (M12 type A & M7 Wall Panel and Repisa) and elevation 3B (M12 type B & M7 Wall Panel and Repisa) each show one 'LED LIGHT' callout at top of millwork. | 2 ea | 000-Copy-of-2498-A-set-2025-0530-Revision-1-p38 |
POWER RECEPTACLE - IT RACK (BACK OF HOUSE) Quad receptacle, IT rack, back of house (Owner-provide rack, GC install, min 2 quads) | 2 ea | A-500 |
POWER & DATA CONNECTION - POS STATION AT CASH COUNTER Quad receptacle (white, general), quad receptacle (red, dedicated breaker), duplex receptacle (white) at cash counter, plus (6) Cat 6A data drops with metal junction box, per cash counter | 1 ea | A-500 |
POWER & LOW VOLTAGE - BURGLAR ALARM SOUNDER/VIDEO RECORDER Duplex receptacle 110V plus (1) Cat 6A drop, Invonics sounder/alarm - video recorder, GC provide and install | 1 ea | A-500 |
EXISTING OUTLET/SWITCH DEVICE REMOVAL OR REPLACEMENT Where an outlet/switch/device is not required, remove completely and patch surface; where an outlet/switch/device is to remain, replace the device for new finishes with a screwless-type cover plate, per keyed note 02-26.41.a/.b | 1 ls | A-110 |
EXISTING LIGHT FIXTURE RELAMP / REWIRE ALLOWANCE Existing light fixtures to be re-used: replace damaged fixtures, relamp all fixtures with 3500K lamps to ensure light color consistency, rewire/recircuit as necessary, per keyed note 02-26.45.a-d | 1 ls | A-110 |
EMERGENCY LIGHT/EGRESS DEVICE TAG EM1 Ceiling-mounted emergency/egress device, plan tag 'EM1'; specific device type (concealed emergency light vs. exit-sign variant vs. strobe/horn) not resolved from text alone | 1 ea | A-130 |
SIGNAGE POWER CONNECTION - INTERIOR ILLUMINATED SIGN EQ-38b EC power connection (J-box + whip + local disconnect per house standard) to interior backlit 'MANGO' ceiling-display sign box, tagged EQ-38b, mounted over the hallway/entry opening at Ext. Ceiling Display height 11'-0" AFF | 1 ea | A-300 |
LED REMOTE TRANSFORMER (millwork cabinet, back-of-cash-counter, note 26-50.23) LED remote transformer/driver installed concealed inside the back-cash-counter millwork cabinet per keyed note 26-50.23: accessible and well vented; if installed in an adjacent wall/column enclosure or ceiling, a taped-in access panel is required. Detail item 5 ('Detail @ M-2A Millwork', 3"=1'-0") shows one transformer symbol near the top of the cabinet interior alongside a 'Provide 2" Diameter Opening' callout in the millwork top, read as the cable pass-through for the driver's low-voltage output leg. | 1 ea | A-410 |
PLYWOOD BACKBOARD 4'x4' - LOW VOLTAGE/DATA BACKBOARD 4'x4' fire-rated plywood backboard for LV/data termination point, wall mounted | 1 ea | E-601 |
| — |
NEC 2020 210.62 Receptacles in show windows | to check | At least one 125-volt receptacle within 18 in. of the top of a show window for each 12 linear ft of show window. | In play for LED DRIVER/TRANSFORMER POWER CONNECTION & ACCESS COORDINATION; SIGNAGE POWER PASS-THRU KIT - EQ-30b (Storefront Window Display Section, view 1). Nothing on the takeoff shows it. | — |
NEC 2020 250.30 Grounding a transformer (separately derived system) | to check | A transformer secondary is grounded as a separately derived system: a system bonding jumper, a grounding electrode conductor to an electrode, and the supply-side bonding jumper sized from 250.102. | In play for LED DRIVER/TRANSFORMER POWER CONNECTION & ACCESS COORDINATION; TRANSFORMER, CONCEALED IN ACCESS PANEL (DIV 26 KEYED NOTE 26-50.23); LED DRIVER / REMOTE TRANSFORMER FOR LIGHT FIXTURE TYPE MI-1; and 1 more. Nothing on the takeoff shows it. | — |
NEC 2020 406.12 Tamper-resistant receptacles | to check | Tamper-resistant 15- and 20-ampere, 125- and 250-volt receptacles in dwellings, guest rooms and dormitories, child care, preschools and schools, business offices, corridors, waiting rooms, clinics, medical and dental offices, outpatient facilities, assembly occupancies and the other areas the section lists. | In play for POWER RECEPTACLE - CAMERA MONITOR (OFFICE). Nothing on the takeoff shows it. | — |
NEC 2020 625.40, 625.54 EV charging: individual circuit and GFCI | to check | Each outlet for EV charging on an individual branch circuit, receptacles for EV charging GFCI protected, and EVSE over 60 A or 150 V to ground with a lockable disconnect. | In play for RECEPTACLE - QUAD, MILLWORK-MOUNTED (M-14 CHARGING STATION); POWER CONNECTION - CHARGING STATION. Nothing on the takeoff shows it. | — |
NEC 2020 422.31, 424.19, 430.102 Disconnect for water heaters, heaters, fans and motor loads | shown | A disconnect within sight of the appliance, heater or motor, or a branch-circuit breaker that can be locked in the open position. | In play for EXHAUST FAN / BATHROOM LIGHT SWITCH INTERLOCK WIRING; GEAR - EWH DISCONNECT. Shown: GEAR - EWH DISCONNECT. | A lockable breaker answers it as well as a switch: check the panel schedule before adding a disconnect. |
NEC 2020 450.3(B) Transformer overcurrent protection | shown | Primary (and where used, secondary) overcurrent protection for each transformer within the percentages of Table 450.3(B), and the secondary conductors protected per 240.21(C). | In play for LED DRIVER/TRANSFORMER POWER CONNECTION & ACCESS COORDINATION; TRANSFORMER, CONCEALED IN ACCESS PANEL (DIV 26 KEYED NOTE 26-50.23); LED DRIVER / REMOTE TRANSFORMER FOR LIGHT FIXTURE TYPE MI-1; and 1 more. Shown: BREAKER - NEW CIRCUITS IN EXISTING PANEL MD; LIGHT FIXTURE TYPE MI-1 (schedule MIRROR W/LED). | — |
NEC 2020 600.5(A) Sign outlet at each tenant entrance | shown | At least one outlet at each entrance to each tenant space accessible to pedestrians, for a sign, on a 20-ampere branch circuit that supplies no other load. | Shown: EMERGENCY LIGHT/EGRESS DEVICE TAG EM5; EMERGENCY LIGHT/EGRESS DEVICE TAG EM2; EMERGENCY LIGHT/EGRESS DEVICE TAG EM3; and 16 more. | RRE prices "power to building signage" where the set shows it; the matrix row is left blank where it does not. |
NEC 2020 600.6 Disconnect within sight of a sign | shown | Each sign or outline lighting system, or its feeder, has an externally operable disconnect within sight of the sign, or one capable of being locked in the open position. | In play for EMERGENCY LIGHT/EGRESS DEVICE TAG EM5; EMERGENCY LIGHT/EGRESS DEVICE TAG EM2; EMERGENCY LIGHT/EGRESS DEVICE TAG EM3; and 14 more. Shown: SIGNAGE POWER CONNECTION - ILLUMINATED SIGN BOX EQ-30b; GEAR - EWH DISCONNECT; RECEPTACLE CLOCK OUTLET; and 4 more. | RRE prices a WP switch at signage as a fused disconnect assembly (firm practice wp_switch_mapping). |
NEC 2020 Chapter 9 Table 1, 358.22 Conduit fill | shown | Over two conductors, a raceway is filled to no more than 40 % of its internal area (Chapter 9 Tables 1, 4 and 5; THHN conductors, EMT). | All 1 callout naming conductors and conduit is within it. | — |
A takeoff cannot settle every article: load calculations and coordination are the engineer of record’s, and workmanship is the inspector’s. Each is listed so nothing is silently skipped. “Waiting on a code read” means the article is in play and this job’s drawing read has not been checked against the code yet: re-run the read, or check it on the drawings.
| 90 | Introduction | general | Scope and definitions: nothing to check on a job. |
| 100 | Definitions | general | Scope and definitions: nothing to check on a job. |
| 110 | Requirements for Electrical Installations | checked | In play; none of its checked sections applies to these lines. |
| 200 | Use and Identification of Grounded Conductors | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 210 | Branch Circuits | to check | 4 sections checked against the takeoff, 4 to check: 210.8(B)(2), 210.8(B)(1), 210.8(B), 210.62. |
| 215 | Feeders | checked | In play; none of its checked sections applies to these lines. |
| 220 | Branch-Circuit, Feeder, and Service Load Calculations | design | The engineer of record’s: sizing, calculation or coordination, not checked against a takeoff. |
| 225 | Outside Branch Circuits and Feeders | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 230 | Services | checked | In play; none of its checked sections applies to these lines. |
| 240 | Overcurrent Protection | checked | In play; none of its checked sections applies to these lines. |
| 242 | Overvoltage Protection | not in play | Nothing on this takeoff puts it in play. |
| 250 | Grounding and Bonding | to check | 1 section checked against the takeoff, 1 to check: 250.30. |
| 300 | General Requirements for Wiring Methods and Materials | checked | In play; none of its checked sections applies to these lines. |
| 310 | Conductors for General Wiring | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 311 | Medium Voltage Conductors and Cable | not in play | Nothing on this takeoff puts it in play. |
| 312 | Cabinets, Cutout Boxes, and Meter Socket Enclosures | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 314 | Outlet, Device, Pull, and Junction Boxes; Conduit Bodies; Fittings; and Handhole Enclosures | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 320 | Armored Cable: Type AC | not in play | Nothing on this takeoff puts it in play. |
| 322 | Flat Cable Assemblies: Type FC | not in play | Nothing on this takeoff puts it in play. |
| 324 | Flat Conductor Cable: Type FCC | not in play | Nothing on this takeoff puts it in play. |
| 326 | Integrated Gas Spacer Cable: Type IGS | not in play | Nothing on this takeoff puts it in play. |
| 400 | Flexible Cords and Flexible Cables | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 402 | Fixture Wires | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 404 | Switches | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 406 | Receptacles, Cord Connectors, and Attachment Plugs (Caps) | to check | 1 section checked against the takeoff, 1 to check: 406.12. |
| 408 | Switchboards, Switchgear, and Panelboards | checked | In play; none of its checked sections applies to these lines. |
| 409 | Industrial Control Panels | not in play | Nothing on this takeoff puts it in play. |
| 410 | Luminaires, Lampholders, and Lamps | checked | In play; none of its checked sections applies to these lines. |
| 411 | Low-Voltage Lighting | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 422 | Appliances | checked | 1 section checked against the takeoff, all shown. |
| 500 | Hazardous (Classified) Locations, Classes I, II, and III, Divisions 1 and 2 | not in play | Nothing on this takeoff puts it in play. |
| 501 | Class I Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 502 | Class II Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 503 | Class III Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 504 | Intrinsically Safe Systems | not in play | Nothing on this takeoff puts it in play. |
| 505 | Zone 0, 1, and 2 Locations | not in play | Nothing on this takeoff puts it in play. |
| 506 | Zone 20, 21, and 22 Locations for Combustible Dusts or Ignitible Fibers/Flyings | not in play | Nothing on this takeoff puts it in play. |
| 510 | Hazardous (Classified) Locations — Specific | not in play | Nothing on this takeoff puts it in play. |
| 511 | Commercial Garages, Repair and Storage | not in play | Nothing on this takeoff puts it in play. |
| 513 | Aircraft Hangars | not in play |
| 600 | Electric Signs and Outline Lighting | checked | 2 sections checked against the takeoff, all shown. |
| 604 | Manufactured Wiring Systems | not in play | Nothing on this takeoff puts it in play. |
| 605 | Office Furnishings | not in play | Nothing on this takeoff puts it in play. |
| 610 | Cranes and Hoists | not in play | Nothing on this takeoff puts it in play. |
| 620 | Elevators, Dumbwaiters, Escalators, Moving Walks, Platform Lifts, and Stairway Chairlifts | not in play | Nothing on this takeoff puts it in play. |
| 625 | Electric Vehicle Power Transfer System | to check | 1 section checked against the takeoff, 1 to check: 625.40, 625.54. |
| 626 | Electrified Truck Parking Spaces | not in play | Nothing on this takeoff puts it in play. |
| 630 | Electric Welders | not in play | Nothing on this takeoff puts it in play. |
| 640 | Audio Signal Processing, Amplification, and Reproduction Equipment | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 645 | Information Technology Equipment |
| 700 | Emergency Systems | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 701 | Legally Required Standby Systems | not in play | Nothing on this takeoff puts it in play. |
| 702 | Optional Standby Systems | not in play | Nothing on this takeoff puts it in play. |
| 705 | Interconnected Electric Power Production Sources | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 706 | Energy Storage Systems | not in play | Nothing on this takeoff puts it in play. |
| 708 | Critical Operations Power Systems (COPS) | not in play | Nothing on this takeoff puts it in play. |
| 710 | Stand-Alone Systems | not in play | Nothing on this takeoff puts it in play. |
| 712 | Direct Current Microgrids | not in play | Nothing on this takeoff puts it in play. |
| 720 | Circuits and Equipment Operating at Less Than 50 Volts | not in play | Nothing on this takeoff puts it in play. |
| 725 | Class 1, Class 2, and Class 3 Remote-Control, Signaling, and Power-Limited Circuits |
| 800 | General Requirements for Communications Systems | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 805 | Communications Circuits | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 810 | Radio and Television Antenna Equipment | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 820 | Community Antenna Television and Radio Distribution Systems | not in play | Nothing on this takeoff puts it in play. |
| 830 | Network-Powered Broadband Communications Systems | not in play | Nothing on this takeoff puts it in play. |
| 840 | Premises-Powered Broadband Communications Systems | not in play | Nothing on this takeoff puts it in play. |
| Ch. 9 | Tables: conduit fill, conductor properties, power-limited sources | checked | 1 section checked against the takeoff, all shown. |
EMERGENCY LIGHT TAG EM3 (remote head or battery-pack option, unresolved) Standalone 'EM3' red text tag at a fixture/device position with no fixture-family prefix | LED EMERGENCYLIGHT DUAL | 5 ea | A-092 |
LIGHT FIXTURE TYPE BA (schedule BA) -- EM emergency battery-pack option Suspended 4' light fixture (Table F 'BA') shown on the photometric plan with an 'EM' battery-pack designator per Lighting Note 6 -- EC wiring/connection of the integral battery pack, not a separate fixture body | LED EMERGENCYLIGHT DUAL | 3 ea | A-092 |
LIGHT FIXTURE TYPE BA/EM (schedule BA) Suspended 4' light fixture, emergency-circuit tagged variant | LED EMERGENCYLIGHT DUAL | 3 ea | A-130 |
LIGHT FIXTURE TYPE QA (schedule: not found) -- EM emergency battery-pack option Fixture family 'QA' with an 'EM' battery-pack designator -- no Table F schedule row exists for 'QA' anywhere in this run's read set | LED EMERGENCYLIGHT DUAL | 1 ea | A-092 |
LIGHT FIXTURE TYPE EXIT SIGN (schedule EX01 or EX02, tag not printed on A-300) Wall-mounted illuminated EXIT sign fixture, shown pictorially above the corridor/back-of-house door head in Interior Section/Elevation 6; EC furnish-connect per house standard off the emergency lighting circuit | LED GRN EXIT FIXTURE | 1 ea | A-300 |
EXIT SIGN FIXTURE - WALL-MOUNT STANDOFF BRACKET SUPPORT Wall-mounted illuminated exit sign fixture shown in interior elevation, mounted high on wall via a two-point standoff bracket/arm (not flush or ceiling-mounted); support hardware for one exit-sign location. Fixture itself is already carried in the E-800 fixture schedule count of 7 (EX01 x6 + EX02 x1) - this line covers the mounting bracket/support only, so it must not be added to the E-800 fixture unit count. | LED GRN EXIT FIXTURE | 1 ea | A-310 |
LIGHT FIXTURE TYPE EXIT (schedule EX01 or EX02) Illuminated wall/ceiling-mounted EXIT sign fixture shown above the corridor door in the Hall Elevation, view 7, sheet A-320. No fixture tag is printed beside the icon on this sheet; job-facts.md's E-800 Title-24 fixture schedule carries two exit-sign types (EX01, 6 units, 28W and EX02, 1 unit, 28W) that this unit is one of. Emergency/unswitched circuiting per job-facts (Panel A ckt41, lock-on breaker) is recorded elsewhere from E-601 by another sheet agent -- this line is the device count only. | LED GRN EXIT FIXTURE | 1 ea | A-320 |
| Line | Needs a price for | Count | Sheet |
|---|---|---|---|
TRANSFORMER, CONCEALED IN ACCESS PANEL (DIV 26 KEYED NOTE 26-50.23) Signage/lighting step-down transformer, concealed behind a taped-in ceiling/wall access panel, at each of the two storefront window section details (existing bay and display-platform bay) | the gear itself (no RRE item picked yet) | 2 ea | A-210 |
LED DRIVER / REMOTE TRANSFORMER FOR LIGHT FIXTURE TYPE MI-1 Remote LED transformer serving the mirror LED strip (L-0002), installed concealed in an accessible cabinet or closet per spec 26-50.22; a cavity for the transformer is shown behind/below the mirror at the fitting-room table detail with a leader labeled 'LINE OF CAVITY FOR TRANSFORMER' and 'TO LED TRANSFORMER'. Note requires the transformer be accessible and well-vented, with a taped-in access panel if built into an adjacent wall/column/ceiling enclosure. | the gear itself (no RRE item picked yet) | 1 ea | A-500 |
LED REMOTE TRANSFORMER (millwork cabinet, back-of-cash-counter, note 26-50.23) LED remote transformer/driver installed concealed inside the back-cash-counter millwork cabinet per keyed note 26-50.23: accessible and well vented; if installed in an adjacent wall/column enclosure or ceiling, a taped-in access panel is required. Detail item 5 ('Detail @ M-2A Millwork', 3"=1'-0") shows one transformer symbol near the top of the cabinet interior alongside a 'Provide 2" Diameter Opening' callout in the millwork top, read as the cable pass-through for the driver's low-voltage output leg. | the gear itself (no RRE item picked yet) | 1 ea | A-410 |
Read off the schedules and notes. RRE buys none of the material named here. Check each against the responsibility matrix on the proposal: these are what it should say is by others.
| Line | Furnished by | Installed by | RRE’s part | Sheet |
|---|---|---|---|---|
CONDUIT TO CASH-COUNTER RECESSED OUTLET The drawings say “by others”. | Others | Others | Not RRE’s: furnished and installed by others | A-400 |
LIGHT FIXTURE TYPE 26-50.21 LED STRIP (base run, Oak Wall Panel/Repisa) The drawings say “owner-furnished”. | Owner | not stated | RRE installs / connects only | 000-Copy-of-2498-A-set-2025-0530-Revision-1-p38 |
LIGHT FIXTURE TYPE 26-50.21 LED STRIP (conditional upper run, ceiling >13'-0") The drawings say “owner-furnished”. | Owner | not stated | RRE installs / connects only | 000-Copy-of-2498-A-set-2025-0530-Revision-1-p38 |
LED DRIVER/TRANSFORMER POWER CONNECTION & ACCESS COORDINATION The drawings say “owner-furnished”. | Owner | not stated | RRE installs / connects only | 000-Copy-of-2498-A-set-2025-0530-Revision-1-p38 |
POWER CONNECTION - ILLUMINATED SIGN (ENTRANCE) The drawings say “owner-furnished”. | Owner | not stated | RRE installs / connects only | A-500 |
LUTRON VIVE CENTRAL HUB The drawings say “vendor-supplied”. | Vendor | not stated | RRE installs / connects only | E-300 |
SIGNAGE - ILLUMINATED BLADE SIGN (GC FURNISH & INSTALL) The drawings say “owner-furnished”. | Owner | not stated | RRE installs / connects only | A-500 |
LOW VOLTAGE / LINE VOLTAGE SLAB CORE DRILL COORDINATION The drawings say “by gc”. | GC | not stated | RRE installs / connects only | A-110 |
POWER & LOW VOLTAGE - ACCESS CONTROL KEYPAD (DOOR #05, RETAIL TO STORAGE, SALES SIDE) The drawings say “vendor-furnished”. | Vendor | not stated | RRE installs / connects only | A-500 |
POWER & LOW VOLTAGE - ACCESS CONTROL KEYPAD (DOOR #06, BOH HALLWAY TO STORAGE, EXTERIOR-FACE CONTROL) The drawings say “vendor-furnished”. | Vendor | not stated | RRE installs / connects only | A-500 |
POWER & LOW VOLTAGE - ACCESS CONTROL KEYPAD (DOOR #07, BOH HALLWAY TO OFFICE, EXTERIOR-FACE CONTROL, KEYLESS RELEASE INTERIOR) The drawings say “vendor-furnished”. | Vendor | not stated | RRE installs / connects only | A-500 |
POWER & LOW VOLTAGE - ELECTRIC PANIC HARDWARE WITH KEYPAD (DOOR EX-01, MALL CORRIDOR EGRESS DOOR) The drawings say “vendor-furnished”. | Vendor | not stated | RRE installs / connects only | A-500 |
DEMOLITION OF EXISTING ELECTRICAL POWER & DATA TO MAIN PANEL Struck by Firm policy: RRE does not bid demolition: Demolition by others: RRE does not bid demolition. | — | not stated | Struck: not in this bid | A-110 |
DEMOLITION OF EXISTING LIGHTING & BRANCH WIRING Struck by Firm policy: RRE does not bid demolition: Demolition by others: RRE does not bid demolition. | — | not stated | Struck: not in this bid | A-110 |
REMOVAL OF ELECTRICAL OUTLETS/CONDUIT IN DEMOLISHED PARTITION Struck by Firm policy: RRE does not bid demolition: Demolition by others: RRE does not bid demolition. | — | not stated | Struck: not in this bid | A-110 |
DEMO - EXISTING CEILING LIGHT FIXTURES (REMOVE, TYPE UNSPECIFIED) Struck by Firm policy: RRE does not bid demolition: Demolition by others: RRE does not bid demolition. | — | not stated | Struck: not in this bid | A-111 |
| 330 | Metal-Clad Cable: Type MC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 332 | Mineral-Insulated, Metal-Sheathed Cable: Type MI | not in play | Nothing on this takeoff puts it in play. |
| 334 | Nonmetallic-Sheathed Cable: Types NM and NMC | not in play | Nothing on this takeoff puts it in play. |
| 336 | Power and Control Tray Cable: Type TC | not in play | Nothing on this takeoff puts it in play. |
| 337 | Type P Cable | not in play | Nothing on this takeoff puts it in play. |
| 338 | Service-Entrance Cable: Types SE and USE | not in play | Nothing on this takeoff puts it in play. |
| 340 | Underground Feeder and Branch-Circuit Cable: Type UF | not in play | Nothing on this takeoff puts it in play. |
| 342 | Intermediate Metal Conduit: Type IMC | not in play | Nothing on this takeoff puts it in play. |
| 344 | Rigid Metal Conduit: Type RMC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 348 | Flexible Metal Conduit: Type FMC | not in play | Nothing on this takeoff puts it in play. |
| 350 | Liquidtight Flexible Metal Conduit: Type LFMC | not in play | Nothing on this takeoff puts it in play. |
| 352 | Rigid Polyvinyl Chloride Conduit: Type PVC | not in play | Nothing on this takeoff puts it in play. |
| 353 | High Density Polyethylene Conduit: Type HDPE Conduit | not in play | Nothing on this takeoff puts it in play. |
| 354 | Nonmetallic Underground Conduit with Conductors: Type NUCC | not in play | Nothing on this takeoff puts it in play. |
| 355 | Reinforced Thermosetting Resin Conduit: Type RTRC | not in play | Nothing on this takeoff puts it in play. |
| 356 | Liquidtight Flexible Nonmetallic Conduit: Type LFNC | not in play | Nothing on this takeoff puts it in play. |
| 358 | Electrical Metallic Tubing: Type EMT | checked | In play; none of its checked sections applies to these lines. |
| 360 | Flexible Metallic Tubing: Type FMT | not in play | Nothing on this takeoff puts it in play. |
| 362 | Electrical Nonmetallic Tubing: Type ENT | not in play | Nothing on this takeoff puts it in play. |
| 366 | Auxiliary Gutters | not in play | Nothing on this takeoff puts it in play. |
| 368 | Busways | not in play | Nothing on this takeoff puts it in play. |
| 369 | Insulated Bus Pipe (IBP)/Tubular Covered Conductors (TCC) Systems | not in play | Nothing on this takeoff puts it in play. |
| 370 | Cablebus | not in play | Nothing on this takeoff puts it in play. |
| 371 | Flexible Bus Systems | not in play | Nothing on this takeoff puts it in play. |
| 372 | Cellular Concrete Floor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 374 | Cellular Metal Floor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 376 | Metal Wireways | not in play | Nothing on this takeoff puts it in play. |
| 378 | Nonmetallic Wireways | not in play | Nothing on this takeoff puts it in play. |
| 380 | Multioutlet Assembly | not in play | Nothing on this takeoff puts it in play. |
| 382 | Nonmetallic Extensions | not in play | Nothing on this takeoff puts it in play. |
| 384 | Strut-Type Channel Raceway | not in play | Nothing on this takeoff puts it in play. |
| 386 | Surface Metal Raceways | not in play | Nothing on this takeoff puts it in play. |
| 388 | Surface Nonmetallic Raceways | not in play | Nothing on this takeoff puts it in play. |
| 390 | Underfloor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 392 | Cable Trays | not in play | Nothing on this takeoff puts it in play. |
| 393 | Low-Voltage Suspended Ceiling Power Distribution Systems | not in play | Nothing on this takeoff puts it in play. |
| 394 | Concealed Knob-and-Tube Wiring | not in play | Nothing on this takeoff puts it in play. |
| 396 | Messenger-Supported Wiring | not in play | Nothing on this takeoff puts it in play. |
| 398 | Open Wiring on Insulators | not in play | Nothing on this takeoff puts it in play. |
| 399 | Outdoor, Overhead Conductors over 1000 Volts | not in play | Nothing on this takeoff puts it in play. |
| 424 |
| Fixed Electric Space-Heating Equipment |
| not in play |
| Nothing on this takeoff puts it in play. |
| 425 | Fixed Resistance and Electrode Industrial Process Heating Equipment | not in play | Nothing on this takeoff puts it in play. |
| 426 | Fixed Outdoor Electric Deicing and Snow-Melting Equipment | not in play | Nothing on this takeoff puts it in play. |
| 427 | Fixed Electric Heating Equipment for Pipelines and Vessels | not in play | Nothing on this takeoff puts it in play. |
| 430 | Motors, Motor Circuits, and Controllers | checked | In play; none of its checked sections applies to these lines. |
| 440 | Air-Conditioning and Refrigerating Equipment | checked | In play; none of its checked sections applies to these lines. |
| 445 | Generators | not in play | Nothing on this takeoff puts it in play. |
| 450 | Transformers and Transformer Vaults (Including Secondary Ties) | checked | 1 section checked against the takeoff, all shown. |
| 455 | Phase Converters | not in play | Nothing on this takeoff puts it in play. |
| 460 | Capacitors | not in play | Nothing on this takeoff puts it in play. |
| 470 | Resistors and Reactors | not in play | Nothing on this takeoff puts it in play. |
| 480 | Stationary Standby Batteries | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 490 | Equipment Over 1000 Volts, Nominal | not in play | Nothing on this takeoff puts it in play. |
| Nothing on this takeoff puts it in play. |
| 514 | Motor Fuel Dispensing Facilities | not in play | Nothing on this takeoff puts it in play. |
| 515 | Bulk Storage Plants | not in play | Nothing on this takeoff puts it in play. |
| 516 | Spray Application, Dipping, Coating, and Printing Processes | not in play | Nothing on this takeoff puts it in play. |
| 517 | Health Care Facilities | not in play | Nothing on this takeoff puts it in play. |
| 518 | Assembly Occupancies | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 520 | Theaters, Audience Areas of Motion Picture and Television Studios, Performance Areas, and Similar Locations | not in play | Nothing on this takeoff puts it in play. |
| 522 | Control Systems for Permanent Amusement Attractions | not in play | Nothing on this takeoff puts it in play. |
| 525 | Carnivals, Circuses, Fairs, and Similar Events | not in play | Nothing on this takeoff puts it in play. |
| 530 | Motion Picture and Television Studios and Similar Locations | not in play | Nothing on this takeoff puts it in play. |
| 540 | Motion Picture Projection Rooms | not in play | Nothing on this takeoff puts it in play. |
| 545 | Manufactured Buildings and Relocatable Structures | not in play | Nothing on this takeoff puts it in play. |
| 547 | Agricultural Buildings | not in play | Nothing on this takeoff puts it in play. |
| 550 | Mobile Homes, Manufactured Homes, and Mobile Home Parks | not in play | Nothing on this takeoff puts it in play. |
| 551 | Recreational Vehicles and Recreational Vehicle Parks | not in play | Nothing on this takeoff puts it in play. |
| 552 | Park Trailers | not in play | Nothing on this takeoff puts it in play. |
| 555 | Marinas, Boatyards, Floating Buildings, and Commercial and Noncommercial Docking Facilities | not in play | Nothing on this takeoff puts it in play. |
| 590 | Temporary Installations | not in play | Nothing on this takeoff puts it in play. |
| Nothing on this takeoff puts it in play. |
| 646 | Modular Data Centers | not in play | Nothing on this takeoff puts it in play. |
| 647 | Sensitive Electronic Equipment | not in play | Nothing on this takeoff puts it in play. |
| 650 | Pipe Organs | not in play | Nothing on this takeoff puts it in play. |
| 660 | X-Ray Equipment | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 665 | Induction and Dielectric Heating Equipment | not in play | Nothing on this takeoff puts it in play. |
| 668 | Electrolytic Cells | not in play | Nothing on this takeoff puts it in play. |
| 669 | Electroplating | not in play | Nothing on this takeoff puts it in play. |
| 670 | Industrial Machinery | not in play | Nothing on this takeoff puts it in play. |
| 675 | Electrically Driven or Controlled Irrigation Machines | not in play | Nothing on this takeoff puts it in play. |
| 680 | Swimming Pools, Fountains, and Similar Installations | not in play | Nothing on this takeoff puts it in play. |
| 682 | Natural and Artificially Made Bodies of Water | not in play | Nothing on this takeoff puts it in play. |
| 685 | Integrated Electrical Systems | not in play | Nothing on this takeoff puts it in play. |
| 690 | Solar Photovoltaic (PV) Systems | not in play | Nothing on this takeoff puts it in play. |
| 691 | Large-Scale Photovoltaic (PV) Electric Supply Stations | not in play | Nothing on this takeoff puts it in play. |
| 692 | Fuel Cell Systems | not in play | Nothing on this takeoff puts it in play. |
| 694 | Wind Electric Systems | not in play | Nothing on this takeoff puts it in play. |
| 695 | Fire Pumps | not in play | Nothing on this takeoff puts it in play. |
| not read yet |
| In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 727 | Instrumentation Tray Cable: Type ITC | not in play | Nothing on this takeoff puts it in play. |
| 728 | Fire-Resistive Cable Systems | not in play | Nothing on this takeoff puts it in play. |
| 750 | Energy Management Systems | not in play | Nothing on this takeoff puts it in play. |
| 760 | Fire Alarm Systems | checked | In play; none of its checked sections applies to these lines. |
| 770 | Optical Fiber Cables | not in play | Nothing on this takeoff puts it in play. |