Derived from what the read produced, so none of it can drift from the data behind it. A blocker stops a price being presented as complete; it never stops you looking. These definitions are this build’s own — no RRE document specifies them yet.
| Check | Status | What the check found |
|---|---|---|
| Sheet scale | pass | All 5 plan sheet(s) carry a scale, so measurement is available. The other 15 read sheet(s) are specifications, schedules and details — nothing is measured on them, so a scale on one is not needed and a scale missing from one is not a gap. |
| Sheets read for scope | warning | 115 sheet(s) were indexed but not read for scope: 000-Copy-of-CM-Corp---Exhibit-A---Subcontract-Agreement_pdf-p1, 001-Copy-of-CM-Corp---Master-Agreement-MSA-Exhibit-C_pdf-p1, 001-Copy-of-CM-Corp---Master-Agreement-MSA-Exhibit-C_pdf-p2, 001-Copy-of-CM-Corp---Master-Agreement-MSA-Exhibit-C_pdf-p3, 001-Copy-of-CM-Corp---Master-Agreement-MSA-Exhibit-C_pdf-p4, 001-Copy-of-CM-Corp---Master-Agreement-MSA-Exhibit-C_pdf-p5, 001-Copy-of-CM-Corp---Master-Agreement-MSA-Exhibit-C_pdf-p6, 001-Copy-of-CM-Corp---Master-Agreement-MSA-Exhibit-C_pdf-p7, 001-Copy-of-CM-Corp---Master-Agreement-MSA-Exhibit-C_pdf-p8, 002-Copy-of-CM-Corp---Subcontractor-Insurance-Requirements_Updated-9_22_2023_pdf-p1, T1.0, G0.4, G0.5, G0.6, G0.7, A1.1, A6.0, A8.0, M2.0, M4.0, M4.1, M5.4, P1.0, P2.0, P3.0, P4.0, P4.1, P5.0, P6.0, P7.0, 004-Copy-of-S_CaptvieAire-208V_pdf-p8, 004-Copy-of-S_CaptvieAire-208V_pdf-p14, 004-Copy-of-S_CaptvieAire-208V_pdf-p15, 004-Copy-of-S_CaptvieAire-208V_pdf-p16, 004-Copy-of-S_CaptvieAire-208V_pdf-p17, 004-Copy-of-S_CaptvieAire-208V_pdf-p18, 005-Copy-of-S_Daikin-RTU-1_pdf-p1, 005-Copy-of-S_Daikin-RTU-1_pdf-p2, 005-Copy-of-S_Daikin-RTU-1_pdf-p6, 005-Copy-of-S_Daikin-RTU-1_pdf-p7, 005-Copy-of-S_Daikin-RTU-1_pdf-p10, 005-Copy-of-S_Daikin-RTU-1_pdf-p11, 006-Copy-of-S_Daikin-RTU-2_pdf-p1, 006-Copy-of-S_Daikin-RTU-2_pdf-p2, 006-Copy-of-S_Daikin-RTU-2_pdf-p3, 006-Copy-of-S_Daikin-RTU-2_pdf-p5, 006-Copy-of-S_Daikin-RTU-2_pdf-p7, 006-Copy-of-S_Daikin-RTU-2_pdf-p8, 006-Copy-of-S_Daikin-RTU-2_pdf-p10, 006-Copy-of-S_Daikin-RTU-2_pdf-p11, 006-Copy-of-S_Daikin-RTU-2_pdf-p12, 006-Copy-of-S_Daikin-RTU-2_pdf-p13, 006-Copy-of-S_Daikin-RTU-2_pdf-p14, DHH036, 006-Copy-of-S_Daikin-RTU-2_pdf-p16, 006-Copy-of-S_Daikin-RTU-2_pdf-p17, 006-Copy-of-S_Daikin-RTU-2_pdf-p18, DHH048, 006-Copy-of-S_Daikin-RTU-2_pdf-p20, 006-Copy-of-S_Daikin-RTU-2_pdf-p21, 006-Copy-of-S_Daikin-RTU-2_pdf-p22, DHH060, 006-Copy-of-S_Daikin-RTU-2_pdf-p24, 006-Copy-of-S_Daikin-RTU-2_pdf-p25, 006-Copy-of-S_Daikin-RTU-2_pdf-p26, DHH072, 006-Copy-of-S_Daikin-RTU-2_pdf-p28, 006-Copy-of-S_Daikin-RTU-2_pdf-p29, 006-Copy-of-S_Daikin-RTU-2_pdf-p30, 006-Copy-of-S_Daikin-RTU-2_pdf-p31, 006-Copy-of-S_Daikin-RTU-2_pdf-p32, 006-Copy-of-S_Daikin-RTU-2_pdf-p33, 006-Copy-of-S_Daikin-RTU-2_pdf-p34, 006-Copy-of-S_Daikin-RTU-2_pdf-p35, 006-Copy-of-S_Daikin-RTU-2_pdf-p36, 006-Copy-of-S_Daikin-RTU-2_pdf-p37, 006-Copy-of-S_Daikin-RTU-2_pdf-p38, 006-Copy-of-S_Daikin-RTU-2_pdf-p39, 006-Copy-of-S_Daikin-RTU-2_pdf-p40, 006-Copy-of-S_Daikin-RTU-2_pdf-p41, 006-Copy-of-S_Daikin-RTU-2_pdf-p42, 006-Copy-of-S_Daikin-RTU-2_pdf-p43, 006-Copy-of-S_Daikin-RTU-2_pdf-p44, 006-Copy-of-S_Daikin-RTU-2_pdf-p45, 006-Copy-of-S_Daikin-RTU-2_pdf-p46, 006-Copy-of-S_Daikin-RTU-2_pdf-p47, 006-Copy-of-S_Daikin-RTU-2_pdf-p48, 006-Copy-of-S_Daikin-RTU-2_pdf-p49, 006-Copy-of-S_Daikin-RTU-2_pdf-p50, 006-Copy-of-S_Daikin-RTU-2_pdf-p51, 006-Copy-of-S_Daikin-RTU-2_pdf-p52, 006-Copy-of-S_Daikin-RTU-2_pdf-p53, 006-Copy-of-S_Daikin-RTU-2_pdf-p55, 006-Copy-of-S_Daikin-RTU-2_pdf-p56, 006-Copy-of-S_Daikin-RTU-2_pdf-p57, 006-Copy-of-S_Daikin-RTU-2_pdf-p58, 006-Copy-of-S_Daikin-RTU-2_pdf-p59, 006-Copy-of-S_Daikin-RTU-2_pdf-p60, 006-Copy-of-S_Daikin-RTU-2_pdf-p61, 006-Copy-of-S_Daikin-RTU-2_pdf-p62, 006-Copy-of-S_Daikin-RTU-2_pdf-p65, 006-Copy-of-S_Daikin-RTU-2_pdf-p67, 006-Copy-of-S_Daikin-RTU-2_pdf-p68, 006-Copy-of-S_Daikin-RTU-2_pdf-p69, 006-Copy-of-S_Daikin-RTU-2_pdf-p70, 006-Copy-of-S_Daikin-RTU-2_pdf-p71, 006-Copy-of-S_Daikin-RTU-2_pdf-p72, 006-Copy-of-S_Daikin-RTU-2_pdf-p73, 006-Copy-of-S_Daikin-RTU-2_pdf-p74, 006-Copy-of-S_Daikin-RTU-2_pdf-p75, 006-Copy-of-S_Daikin-RTU-2_pdf-p77, 006-Copy-of-S_Daikin-RTU-2_pdf-p78, 006-Copy-of-S_Daikin-RTU-2_pdf-p79, 006-Copy-of-S_Daikin-RTU-2_pdf-p80, 007-rocklinelectric.net-Mail---CM-CORP_-The-Melt--Stanford-CA--Answered-RFI_s-p1. Looked at by the takeoff and not read: no electrical work on it. Read them, or state the omission on the proposal — the basis of the offer already prints it. |
| Symbol source | pass | A symbol list was found on the drawings: 004-Copy-of-S_CaptvieAire-208V_pdf-p4 — CaptiveAire Master Drawing 6912904 sheet 4 - Hood #1 (5430ND-2) fire system: TANK-SP-2 fire cabinet piping plan/elevation, fire cabinet legend, section view with recessed LED hood lights, 2" 120VAC electric gas valve & strainer schedule, CAS installation includes/excludes, E1.0 — ELECTRICAL LEGEND AND DETAILS. The project legend is authoritative for this set and outranks everything else — NECA 100-2006 itself allows a drawing to use non-standard symbols provided the legend explains them. NECA 100-2006 stays underneath it for anything the legend leaves silent, and no conventions file exists for the engineering firm. |
| Symbols named | pass | All 326 marks belong to a named group. |
| Every line prices | blocker | 39 line(s) point at no assembly, so nothing prices them: CIRCUIT BREAKER 15A 2P 208Y/120V BOLT-ON, PANEL A, CIRCUIT BREAKER 20A 1P 208Y/120V BOLT-ON, PANEL A, CIRCUIT BREAKER 20A 2P 208Y/120V BOLT-ON, PANEL A, CIRCUIT BREAKER 35A 2P 208Y/120V BOLT-ON, PANEL A, CIRCUIT BREAKER 20A 1P 208Y/120V BOLT-ON, PANEL B, CIRCUIT BREAKER 30A 3P 208Y/120V BOLT-ON, PANEL B…. They are counted and reported, and they stay outside the total. Attach a build-up from the catalog, or strike the line. |
| Plan and schedule agree | pass | No line has a plan/schedule disagreement. |
| Lines accepted by a person | blocker | Nothing has been accepted. All 171 line(s) are still suggestions, and machine output is a suggestion until a named person accepts it. Accept on the Takeoff screen — 132 line(s) are ready. |
| Engineer conventions known | pass | No engineer-dependent lines. |
| Unsure flags resolved | pass | The model raised no open flags. |
| Cover sheet read | pass | A cover sheet was found and read; its notes parameterise every later pass. |
What the symbol names rest on. The set’s own legend (004-Copy-of-S_CaptvieAire-208V_pdf-p4, E1.0), which is authoritative for this project.
| Line | Count | Sheet |
|---|---|---|
#16 THHN CU WIRE, 0-10V DIMMING PAIR (FULL CIRCUIT) 0-10V dimming pair in the lighting conduit | 1376 ft | E2.0 |
FEEDER (4)500KCMIL CU THHN + (1)#3G IN 3-1/2" EMT Transformer (landlord, 112.5 kVA) to panel L | 65 ft | E4.0 |
THERMOSTAT CONTROL CABLE, 18 AWG 8-CONDUCTOR (18/8) CL2, THERMOSTAT TO ROOFTOP UNIT (RTU-1, RTU-2), IN CONDUIT Thermostat-to-unit control cable; M0.1 GN11 has thermostats 'wired in conduit by electrical contractor'. Cable type assumed (Daikin unit may call for a communicating thermostat cable). | 63 ft | M1.0 |
TRACK - SUSPENDED LINE-VOLTAGE TRACK (CONTECH LT), TYPE TR 3 TR runs tagged 'TR A-31,d 60W', total feet | 33.5 ft | E2.0 |
FEEDER (4)#1/0 CU THHN + (1)#6G IN 2" EMT Panel L to panel A | 10 ft | E4.0 |
FEEDER (4)#1/0 CU THHN + (1)#6G IN 2" EMT Panel L to panel B (through shunt trip device) | 10 ft | E4.0 |
SHUNT TRIP SIGNAL WIRING, HOOD CONTROL PANEL ST/N1 TO SHUNT TRIP BREAKER COIL A1/A2, 120VAC, 2 WIRES Fire-condition shunt trip signal to the shunt trip device ahead of panel B (appliance power). | 1 ea | 004-Copy-of-S_CaptvieAire-208V_pdf-p11 |
Edition: 2025 California Electrical Code, because no job address on file, so California is assumed (RRE bids its California zones only); in force for permits from 2026-01-01, as of the bid date 2026-09-30. City and county amendments are the AHJ’s: check them on any job inside a city that amends the code. “To check” means the code requires it and the drawings do not show it: send an RFI, or make the call. Nothing here is added to the bid on its own.
| Section | Status | What the code requires | What the takeoff shows | RRE’s practice |
|---|---|---|---|---|
NEC 2023 110.16 Arc-flash warning label on gear | to check | Switchboards, switchgear, panelboards, meter socket enclosures and motor control centers likely to be worked on energized carry a field- or factory-applied arc-flash hazard warning. | In play for PANELBOARD 400A MCB 208Y/120V 3PH 4W 42-CKT NEMA 1 SURFACE, 10kAIC; PANELBOARD 225A MLO 208Y/120V 3PH 4W 60-CKT NEMA 1 SURFACE, 10kAIC; PANELBOARD 225A MLO 208Y/120V 3PH 4W 30-CKT NEMA 1 SURFACE, 10kAIC. Nothing on the takeoff shows it. | RRE carries phenolic nameplates and labels as their own item where the set calls for them. |
NEC 2023 210.8(B), 406.9(B) GFCI, weather-resistant, in-use cover outdoors and on the roof | to check | Rooftop and outdoor receptacles GFCI protected, weather-resistant type, with an extra-duty in-use cover in wet locations. | 2 of 3 in play are not shown with it: #10 THHN CU; 3/4" EMT CONDUIT (ROOF EQUIPMENT HOMERUNS). | RRE carries roof and patio receptacles as WR GFCI with an in-use cover where they are drawn (The Melt: 3). |
NEC 2023 408.4(A) Circuit directory at every panel | to check | Every circuit and circuit modification legibly identified as to its clear, evident and specific purpose on a circuit directory at the panel. |
The RRE item carries no price for the part named, so the estimate has the install labor and rough-in only, and the vendor or sub prices the rest. Send the lighting and gear lists from Material list & vendor quotes.
| Line | Needs a price for | Count | Sheet |
|---|---|---|---|
LIGHT FIXTURE TYPE P1 - SUSPENDED CYLINDER LED DOWNLIGHT (ALPHABET BETA-3R) P1 pendant cylinders, dining room and corridor, circuit A-1,a | LED PENDANT MOUNTED LA | 33 ea | E2.0 |
LIGHT FIXTURE TYPE P1E - SUSPENDED CYLINDER LED DOWNLIGHT W/ REMOTE EMERGENCY BATTERY (ALPHABET BETA-3R) P1E hatched symbols, dining/corridor, A-1,a | LED EMERGENCYLIGHT DUAL | 22 ea | E2.0 |
LIGHT FIXTURE TYPE YP1 - DECORATIVE RLM PENDANT W/ GUARD (BARN LIGHT) YP1 pendants, A-33,b | LED PENDANT MOUNTED LA | 8 ea | E2.0 |
LIGHT FIXTURE TYPE X - LED EXIT SIGN W/ BATTERY (LITHONIA LHQM) Exit signs tagged X A-3 | LED GRN EXIT FIXTURE | 7 ea | E2.0 |
TRACK HEAD TYPE T3 - TRACK ACCENT (LUMENTURE T65) T3 heads on the two short TR runs | LED TRACK SPOT FIXTURE | 6 ea | E2.0 |
LIGHT FIXTURE TYPE YP2 - 66" I-BEAM LINEAR PENDANT (BASILE STUDIO) |
23 lines the reader wrote at zero are not listed: they add nothing to the bid.
Nothing in this tab.
PLYWOOD BACKBOARD 4' x 8' x 3/4" FIRE-RATED, PAINTED, AT TELECOM / LV LOCATION Backboard for the low-voltage rough-in (data, camera, speaker, WAP backboxes) | 1 ea | E3.2 |
EQUIPMENT CONNECTION, ROOF UNIT (disconnect to unit, 3/4" liquidtight flex whip) Final connection disconnect-to-unit at RTU-1, RTU-2, SF-1, EF-1, EF-2 | 0 ea | E3.1 |
DUCT SMOKE DETECTOR, DUCT-MOUNTED W/ SAMPLING TUBE AND HOUSING (EC FURNISH & WIRE, MC INSTALL IN DUCT) Duct smoke detector for RTU-1 supply/return, furnished and wired by EC, installed by mechanical contractor, per M0.2 Smoke Detector section. | 0 ea | 004-Copy-of-S_CaptvieAire-208V_pdf-p3 |
DUCT SMOKE DETECTOR REMOTE ALARM INDICATOR / KEY TEST STATION, 1-GANG, W/ 4" SQ BOX + 3/4" EMT STUB 12 FT Remote alarm indicator for the duct smoke detector, EC-furnished and wired per M0.2. | 0 ea | 004-Copy-of-S_CaptvieAire-208V_pdf-p3 |
| In play for PANELBOARD 400A MCB 208Y/120V 3PH 4W 42-CKT NEMA 1 SURFACE, 10kAIC; PANELBOARD 225A MLO 208Y/120V 3PH 4W 60-CKT NEMA 1 SURFACE, 10kAIC; PANELBOARD 225A MLO 208Y/120V 3PH 4W 30-CKT NEMA 1 SURFACE, 10kAIC. Nothing on the takeoff shows it. |
| RRE carries a panel directory update where circuits land in an existing panel. |
NEC 2023 210.8(B)(2) GFCI on commercial kitchen receptacles | shown | GFCI protection for every receptacle in a commercial kitchen: single-phase up to 50 A and three-phase up to 100 A, 150 V to ground or less. | In play for GFCI DUPLEX RECEPTACLE 20A 125V (kitchen equipment, GN24); SPECIAL PURPOSE RECEPTACLE 208V (kitchen equipment, NEMA per equipment, GFCI per GN24); DOUBLE DUPLEX GFCI RECEPTACLE 20A 125V NEMA 5-20R (2 GFCI DUPLEX, 2-GANG) STAINLESS PLATE. Shown: GFCI DUPLEX RECEPTACLE 20A 125V (kitchen equipment, GN24); SPECIAL PURPOSE RECEPTACLE 208V (kitchen equipment, NEMA per equipment, GFCI per GN24); DOUBLE DUPLEX GFCI RECEPTACLE 20A 125V NEMA 5-20R (2 GFCI DUPLEX, 2-GANG) STAINLESS PLATE. | RRE carries a GFCI receptacle at the device where the set calls for GFCI, and adds none on code alone (Mango: no GFCI bid; The Melt: 25 where the set said so). |
NEC 2023 210.8(B)(1) GFCI on bathroom receptacles | shown | GFCI protection for every receptacle in a bathroom: single-phase up to 50 A and three-phase up to 100 A, 150 V to ground or less. | In play for GFCI DUPLEX RECEPTACLE 20A 125V +42" (restrooms, 'GFI'). Shown: GFCI DUPLEX RECEPTACLE 20A 125V +42" (restrooms, 'GFI'). | RRE carries GFCI at the device where the set calls for it. |
NEC 2023 210.63(A) Service receptacle at HVAC equipment | shown | A 125-volt, 15- or 20-ampere receptacle on the same level and within 25 ft of heating, air-conditioning and refrigeration equipment, not on the load side of the equipment disconnect. | In play for 3/4" EMT CONDUIT (ROOF EQUIPMENT HOMERUNS); #10 THHN CU; #1/0 THHN CU; and 16 more. Shown: #10 THHN CU; 3/4" EMT CONDUIT (ROOF EQUIPMENT HOMERUNS); GFCI DUPLEX RECEPTACLE 20A 125V (kitchen equipment, GN24); and 2 more. | RRE carries the roof receptacle where the set draws one (reading check 11). |
NEC 2023 300.11, 410.36(B) Support in suspended ceilings | shown | Raceways, cables and boxes above a suspended ceiling are supported independently of the ceiling grid, or by identified support wires; lay-in luminaires are fastened to the grid framing. | In play for LAY-IN LIGHT FIXTURE SUPPORT WIRE, 12 GA GALVANIZED, TAUT HANGER AT EACH FIXTURE CORNER TO STRUCTURE ABOVE (2X4 TROFFER R3/R3EM); LAY-IN LIGHT FIXTURE SLACK SAFETY WIRE, 12 GA GALVANIZED, DIAGONALLY OPPOSITE CORNERS TO STRUCTURE ABOVE (2X4 TROFFER R3/R3EM); LIGHT FIXTURE TYPE R3 - 2X4 RECESSED LED TROFFER (LITHONIA STAKP); and 2 more. Shown: LAY-IN LIGHT FIXTURE SUPPORT WIRE, 12 GA GALVANIZED, TAUT HANGER AT EACH FIXTURE CORNER TO STRUCTURE ABOVE (2X4 TROFFER R3/R3EM); LAY-IN LIGHT FIXTURE SLACK SAFETY WIRE, 12 GA GALVANIZED, DIAGONALLY OPPOSITE CORNERS TO STRUCTURE ABOVE (2X4 TROFFER R3/R3EM). | RRE carries the fixture support wire as its own item where the ceiling is a grid. |
NEC 2023 440.14 Disconnect within sight of HVAC equipment | shown | A disconnecting means within sight from, and readily accessible from, air-conditioning and refrigerating equipment. It may be on or in the unit. | In play for 3/4" EMT CONDUIT (ROOF EQUIPMENT HOMERUNS); #10 THHN CU; #1/0 THHN CU; and 16 more. Shown: 1-1/2" EMT CONDUIT (RTU-1 FEEDER 3#1/0 + #6G); VFD MOTOR LOAD CIRCUIT, HOOD CONTROL PANEL TO FAN DISCONNECT, 3 CONDUCTORS + GROUND 208V 3PH, DEDICATED CONDUIT EACH (EXH-1/EF-1, SUP-3/SF-1); DISCONNECT SWITCH 200A 3P 240V FUSED, 150A FUSES, NEMA 3R, HEAVY DUTY (RTU-1); and 4 more. | RRE priced this on 5 of 5 past jobs (100%). RRE carries a disconnect at every unit with a disconnect symbol or note, sized from its circuit. |
NEC 2023 422.31, 424.19, 430.102 Disconnect for water heaters, heaters, fans and motor loads | shown | A disconnect within sight of the appliance, heater or motor, or a branch-circuit breaker that can be locked in the open position. | In play for #10 THHN CU; 3/4" EMT CONDUIT (ROOF EQUIPMENT HOMERUNS); MOTOR RATED SWITCH ($M) (restroom exhaust fans EF-3/EF-4, A-44); and 10 more. Shown: VFD MOTOR LOAD CIRCUIT, HOOD CONTROL PANEL TO FAN DISCONNECT, 3 CONDUCTORS + GROUND 208V 3PH, DEDICATED CONDUIT EACH (EXH-1/EF-1, SUP-3/SF-1); DISCONNECT SWITCH 30A 3P 240V FUSED, 15A FUSES, NEMA 3R, HEAVY DUTY (EF-1 (CaptiveAire EXH-1)); DISCONNECT SWITCH 30A 3P 240V FUSED, 15A FUSES, NEMA 3R, HEAVY DUTY (SF-1 (CaptiveAire SUP-3 / MUA fan 3)); and 1 more. | A lockable breaker answers it as well as a switch: check the panel schedule before adding a disconnect. |
NEC 2023 600.5(A) Sign outlet at each tenant entrance | shown | At least one outlet at each entrance to each tenant space accessible to pedestrians, for a sign, on a 20-ampere branch circuit that supplies no other load. | Shown: JUNCTION BOX 4" SQ WITH CONNECTION (hard-wired equipment / signage / hood); DISCONNECT SWITCH 30A 1P NON-FUSED, NEMA 1, SIGN (INTERIOR) WITH J-BOX; DISCONNECT SWITCH 30A 1P NON-FUSED, NEMA 1, SIGN (EXTERIOR SIGN, INSIDE FACE OF WALL) WITH J-BOX. | RRE prices "power to building signage" where the set shows it; the matrix row is left blank where it does not. |
NEC 2023 600.6 Disconnect within sight of a sign | shown | Each sign or outline lighting system, or its feeder, has an externally operable disconnect within sight of the sign, or one capable of being locked in the open position. | In play for JUNCTION BOX 4" SQ WITH CONNECTION (hard-wired equipment / signage / hood); DISCONNECT SWITCH 30A 1P NON-FUSED, NEMA 1, SIGN (INTERIOR) WITH J-BOX; DISCONNECT SWITCH 30A 1P NON-FUSED, NEMA 1, SIGN (EXTERIOR SIGN, INSIDE FACE OF WALL) WITH J-BOX. Shown: 1-1/2" EMT CONDUIT (RTU-1 FEEDER 3#1/0 + #6G); PANEL SAFE-OFF; DISCONNECT SWITCH 30A 1P NON-FUSED, NEMA 1, SIGN (INTERIOR) WITH J-BOX; and 8 more. | RRE prices a WP switch at signage as a fused disconnect assembly (firm practice wp_switch_mapping). |
NEC 2023 Chapter 9 Table 1, 358.22 Conduit fill | shown | Over two conductors, a raceway is filled to no more than 40 % of its internal area (Chapter 9 Tables 1, 4 and 5; THHN conductors, EMT). | All 3 callouts naming conductors and conduit are within it. | — |
A takeoff cannot settle every article: load calculations and coordination are the engineer of record’s, and workmanship is the inspector’s. Each is listed so nothing is silently skipped. “Waiting on a code read” means the article is in play and this job’s drawing read has not been checked against the code yet: re-run the read, or check it on the drawings.
| 90 | Introduction | general | Scope and definitions: nothing to check on a job. |
| 100 | Definitions | general | Scope and definitions: nothing to check on a job. |
| 110 | Requirements for Electrical Installations | to check | 1 section checked against the takeoff, 1 to check: 110.16. |
| 200 | Use and Identification of Grounded Conductors | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 210 | Branch Circuits | to check | 4 sections checked against the takeoff, 1 to check: 210.8(B), 406.9(B). |
| 215 | Feeders | checked | In play; none of its checked sections applies to these lines. |
| 220 | Branch-Circuit, Feeder, and Service Load Calculations | design | The engineer of record’s: sizing, calculation or coordination, not checked against a takeoff. |
| 225 | Outside Branch Circuits and Feeders | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 230 | Services | checked | In play; none of its checked sections applies to these lines. |
| 235 | Branch Circuits, Feeders, and Services Over 1000 Volts ac, 1500 Volts dc | not in play | Nothing on this takeoff puts it in play. |
| 240 | Overcurrent Protection | checked | In play; none of its checked sections applies to these lines. |
| 242 | Overvoltage Protection | not in play | Nothing on this takeoff puts it in play. |
| 245 | Overcurrent Protection for Systems Rated Over 1000 Volts ac, 1500 Volts dc | not in play | Nothing on this takeoff puts it in play. |
| 250 | Grounding and Bonding | checked | In play; none of its checked sections applies to these lines. |
| 300 | General Requirements for Wiring Methods and Materials | checked | 1 section checked against the takeoff, all shown. |
| 305 | General Requirements for Wiring Methods and Materials for Systems Rated Over 1000 Volts ac, 1500 Volts dc | not in play | Nothing on this takeoff puts it in play. |
| 310 | Conductors for General Wiring | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 312 | Cabinets, Cutout Boxes, and Meter Socket Enclosures | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 314 | Outlet, Device, Pull, and Junction Boxes; Conduit Bodies; Fittings; and Handhole Enclosures | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 315 | Medium Voltage Conductors, Cable, Cable Joints, and Cable Terminations | not in play | Nothing on this takeoff puts it in play. |
| 320 | Armored Cable: Type AC | not in play | Nothing on this takeoff puts it in play. |
| 322 | Flat Cable Assemblies: Type FC | not in play | Nothing on this takeoff puts it in play. |
| 324 | Flat Conductor Cable: Type FCC | not in play |
| 400 | Flexible Cords and Flexible Cables | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 402 | Fixture Wires | not in play | Nothing on this takeoff puts it in play. |
| 404 | Switches | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 406 | Receptacles, Cord Connectors, and Attachment Plugs (Caps) | checked | In play; none of its checked sections applies to these lines. |
| 408 | Switchboards, Switchgear, and Panelboards | to check | 1 section checked against the takeoff, 1 to check: 408.4(A). |
| 409 | Industrial Control Panels | not in play | Nothing on this takeoff puts it in play. |
| 410 | Luminaires, Lampholders, and Lamps | checked | In play; none of its checked sections applies to these lines. |
| 411 | Low-Voltage Lighting | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 422 | Appliances | checked | 1 section checked against the takeoff, all shown. |
| 424 | Fixed Electric Space-Heating Equipment |
| 500 | Hazardous (Classified) Locations, Classes I, II, and III, Divisions 1 and 2 | not in play | Nothing on this takeoff puts it in play. |
| 501 | Class I Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 502 | Class II Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 503 | Class III Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 504 | Intrinsically Safe Systems | not in play | Nothing on this takeoff puts it in play. |
| 505 | Zone 0, 1, and 2 Locations | not in play | Nothing on this takeoff puts it in play. |
| 506 | Zone 20, 21, and 22 Locations for Combustible Dusts or Ignitible Fibers/Flyings | not in play | Nothing on this takeoff puts it in play. |
| 510 | Hazardous (Classified) Locations — Specific | not in play | Nothing on this takeoff puts it in play. |
| 511 | Commercial Garages, Repair and Storage | not in play | Nothing on this takeoff puts it in play. |
| 513 | Aircraft Hangars | not in play |
| 600 | Electric Signs and Outline Lighting | checked | 2 sections checked against the takeoff, all shown. |
| 604 | Manufactured Wiring Systems | not in play | Nothing on this takeoff puts it in play. |
| 605 | Office Furnishings | not in play | Nothing on this takeoff puts it in play. |
| 610 | Cranes and Hoists | not in play | Nothing on this takeoff puts it in play. |
| 620 | Elevators, Dumbwaiters, Escalators, Moving Walks, Platform Lifts, and Stairway Chairlifts | not in play | Nothing on this takeoff puts it in play. |
| 625 | Electric Vehicle Power Transfer System | not in play | Nothing on this takeoff puts it in play. |
| 626 | Electrified Truck Parking Spaces | not in play | Nothing on this takeoff puts it in play. |
| 630 | Electric Welders | not in play | Nothing on this takeoff puts it in play. |
| 640 | Audio Signal Processing, Amplification, and Reproduction Equipment | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 645 | Information Technology Equipment |
| 700 | Emergency Systems | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 701 | Legally Required Standby Systems | not in play | Nothing on this takeoff puts it in play. |
| 702 | Optional Standby Systems | not in play | Nothing on this takeoff puts it in play. |
| 705 | Interconnected Electric Power Production Sources | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 706 | Energy Storage Systems | not in play | Nothing on this takeoff puts it in play. |
| 708 | Critical Operations Power Systems (COPS) | not in play | Nothing on this takeoff puts it in play. |
| 710 | Stand-Alone Systems | not in play | Nothing on this takeoff puts it in play. |
| 712 | Direct Current Microgrids | not in play | Nothing on this takeoff puts it in play. |
| 722 | Cables for Power-Limited Circuits and Fault-Managed Power Circuits | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 724 | Class 1 Power-Limited Circuits and Class 1 Power-Limited Remote-Control and Signaling Circuits |
| 800 | General Requirements for Communications Systems | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 805 | Communications Circuits | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 810 | Radio and Television Antenna Equipment | not in play | Nothing on this takeoff puts it in play. |
| 820 | Community Antenna Television and Radio Distribution Systems | not in play | Nothing on this takeoff puts it in play. |
| 830 | Network-Powered Broadband Communications Systems | not in play | Nothing on this takeoff puts it in play. |
| 840 | Premises-Powered Broadband Communications Systems | not in play | Nothing on this takeoff puts it in play. |
| Ch. 9 | Tables: conduit fill, conductor properties, power-limited sources | checked | 1 section checked against the takeoff, all shown. |
| LED PENDANT MOUNTED LA |
| 5.5 ft |
| E2.0 |
LIGHT FIXTURE TYPE R1E - 6" ROUND RECESSED LED DOWNLIGHT W/ REMOTE EMERGENCY BATTERY (ALPHABET NBU4) R1E, BOH, A-3,h | LED EMERGENCYLIGHT DUAL | 5 ea | E2.0 |
TRACK HEAD TYPE T1 - TRACK WALL WASH (LUMENTURE TWW160) T1 heads on banquette TR run | LED TRACK SPOT FIXTURE | 5 ea | E2.0 |
EMERGENCY LIGHTING INVERTER BODINE ELI-S-20, 20VA 120V, 90-MIN NICD, CEILING MOUNT Inverter #1 and #2 (restrooms) | LED EMERGENCYLIGHT DUAL | 2 ea | E2.0 |
| Line | Needs a price for | Count | Sheet |
|---|---|---|---|
PANELBOARD 400A MCB 208Y/120V 3PH 4W 42-CKT NEMA 1 SURFACE, 10kAIC Panel L (new), BOH | 400/42 120/208V PNL 3PH | 1 ea | E4.0 |
PANELBOARD 225A MLO 208Y/120V 3PH 4W 60-CKT NEMA 1 SURFACE, 10kAIC Panel A (new), BOH | 225/36 120/208V PNL 3PH | 1 ea | E4.0 |
PANELBOARD 225A MLO 208Y/120V 3PH 4W 30-CKT NEMA 1 SURFACE, 10kAIC Panel B (new), BOH | 225/36 120/208V PNL 3PH | 1 ea | E4.0 |
Read off the schedules and notes. RRE buys none of the material named here. Check each against the responsibility matrix on the proposal: these are what it should say is by others.
| Line | Furnished by | Installed by | RRE’s part | Sheet |
|---|---|---|---|---|
3/4" EMT CONDUIT STUB TO ACCESSIBLE CEILING (low-voltage rough-in, empty w/ pull string) RRE carries the line; the read says “wiring by others”. | Others | not stated | RRE carries it; a part is by others | E3.2 |
CAMERA BACKBOX 4" SQ (rough-in only, camera + cable by others) The drawings say “by others”. | Others | Others | Not RRE’s: furnished and installed by others | E3.2 |
SPEAKER BACKBOX 4" SQ (rough-in only, speaker + cable by others) The drawings say “by others”. | Others | Others | Not RRE’s: furnished and installed by others | E3.2 |
ELECTRIC GAS SHUTOFF VALVE 2" (CAPTIVEAIRE 'SC ELECTRICAL', FURNISHED BY CAPTIVEAIRE, SET BY PLUMBER) - EC 120V CONNECTION + FLEX WHIP FROM HOOD CONTROL PANEL The drawings say “furnished by captiveaire”. | CAPTIVEAIRE | not stated | RRE installs / connects only | 004-Copy-of-S_CaptvieAire-208V_pdf-p3 |
FEEDER TERMINATION 400A 3PH 4W, (4)500 KCMIL + #3G The drawings say “landlord-furnished”. | Landlord | not stated | RRE installs / connects only | E4.0 |
| Nothing on this takeoff puts it in play. |
| 326 | Integrated Gas Spacer Cable: Type IGS | not in play | Nothing on this takeoff puts it in play. |
| 330 | Metal-Clad Cable: Type MC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 332 | Mineral-Insulated, Metal-Sheathed Cable: Type MI | not in play | Nothing on this takeoff puts it in play. |
| 334 | Nonmetallic-Sheathed Cable: Types NM and NMC | not in play | Nothing on this takeoff puts it in play. |
| 335 | Instrumentation Tray Cable: Type ITC | not in play | Nothing on this takeoff puts it in play. |
| 336 | Power and Control Tray Cable: Type TC | not in play | Nothing on this takeoff puts it in play. |
| 337 | Type P Cable | not in play | Nothing on this takeoff puts it in play. |
| 338 | Service-Entrance Cable: Types SE and USE | not in play | Nothing on this takeoff puts it in play. |
| 340 | Underground Feeder and Branch-Circuit Cable: Type UF | not in play | Nothing on this takeoff puts it in play. |
| 342 | Intermediate Metal Conduit: Type IMC | not in play | Nothing on this takeoff puts it in play. |
| 344 | Rigid Metal Conduit: Type RMC | not in play | Nothing on this takeoff puts it in play. |
| 348 | Flexible Metal Conduit: Type FMC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 350 | Liquidtight Flexible Metal Conduit: Type LFMC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 352 | Rigid Polyvinyl Chloride Conduit: Type PVC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 353 | High Density Polyethylene Conduit: Type HDPE Conduit | not in play | Nothing on this takeoff puts it in play. |
| 354 | Nonmetallic Underground Conduit with Conductors: Type NUCC | not in play | Nothing on this takeoff puts it in play. |
| 355 | Reinforced Thermosetting Resin Conduit: Type RTRC | not in play | Nothing on this takeoff puts it in play. |
| 356 | Liquidtight Flexible Nonmetallic Conduit: Type LFNC | not in play | Nothing on this takeoff puts it in play. |
| 358 | Electrical Metallic Tubing: Type EMT | checked | In play; none of its checked sections applies to these lines. |
| 360 | Flexible Metallic Tubing: Type FMT | not in play | Nothing on this takeoff puts it in play. |
| 362 | Electrical Nonmetallic Tubing: Type ENT | not in play | Nothing on this takeoff puts it in play. |
| 366 | Auxiliary Gutters | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 368 | Busways | not in play | Nothing on this takeoff puts it in play. |
| 369 | Insulated Bus Pipe (IBP)/Tubular Covered Conductors (TCC) Systems | not in play | Nothing on this takeoff puts it in play. |
| 370 | Cablebus | not in play | Nothing on this takeoff puts it in play. |
| 371 | Flexible Bus Systems | not in play | Nothing on this takeoff puts it in play. |
| 372 | Cellular Concrete Floor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 374 | Cellular Metal Floor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 376 | Metal Wireways | not in play | Nothing on this takeoff puts it in play. |
| 378 | Nonmetallic Wireways | not in play | Nothing on this takeoff puts it in play. |
| 380 | Multioutlet Assembly | not in play | Nothing on this takeoff puts it in play. |
| 382 | Nonmetallic Extensions | not in play | Nothing on this takeoff puts it in play. |
| 384 | Strut-Type Channel Raceway | not in play | Nothing on this takeoff puts it in play. |
| 386 | Surface Metal Raceways | not in play | Nothing on this takeoff puts it in play. |
| 388 | Surface Nonmetallic Raceways | not in play | Nothing on this takeoff puts it in play. |
| 390 | Underfloor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 392 | Cable Trays | not in play | Nothing on this takeoff puts it in play. |
| 393 | Low-Voltage Suspended Ceiling Power Distribution Systems | not in play | Nothing on this takeoff puts it in play. |
| 394 | Concealed Knob-and-Tube Wiring | not in play | Nothing on this takeoff puts it in play. |
| 395 | Outdoor Overhead Conductors over 1000 Volts | not in play | Nothing on this takeoff puts it in play. |
| 396 | Messenger-Supported Wiring | not in play | Nothing on this takeoff puts it in play. |
| 398 | Open Wiring on Insulators | not in play | Nothing on this takeoff puts it in play. |
| not in play |
| Nothing on this takeoff puts it in play. |
| 425 | Fixed Resistance and Electrode Industrial Process Heating Equipment | not in play | Nothing on this takeoff puts it in play. |
| 426 | Fixed Outdoor Electric Deicing and Snow-Melting Equipment | not in play | Nothing on this takeoff puts it in play. |
| 427 | Fixed Electric Heating Equipment for Pipelines and Vessels | not in play | Nothing on this takeoff puts it in play. |
| 430 | Motors, Motor Circuits, and Controllers | checked | In play; none of its checked sections applies to these lines. |
| 440 | Air-Conditioning and Refrigerating Equipment | checked | 1 section checked against the takeoff, all shown. |
| 445 | Generators | not in play | Nothing on this takeoff puts it in play. |
| 450 | Transformers and Transformer Vaults (Including Secondary Ties) | checked | In play; none of its checked sections applies to these lines. |
| 455 | Phase Converters | not in play | Nothing on this takeoff puts it in play. |
| 460 | Capacitors | not in play | Nothing on this takeoff puts it in play. |
| 470 | Resistors and Reactors | not in play | Nothing on this takeoff puts it in play. |
| 480 | Stationary Standby Batteries | not in play | Nothing on this takeoff puts it in play. |
| 490 | Equipment Over 1000 Volts, Nominal | not in play | Nothing on this takeoff puts it in play. |
| Nothing on this takeoff puts it in play. |
| 514 | Motor Fuel Dispensing Facilities | not in play | Nothing on this takeoff puts it in play. |
| 515 | Bulk Storage Plants | not in play | Nothing on this takeoff puts it in play. |
| 516 | Spray Application, Dipping, Coating, and Printing Processes | not in play | Nothing on this takeoff puts it in play. |
| 517 | Health Care Facilities | not in play | Nothing on this takeoff puts it in play. |
| 518 | Assembly Occupancies | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 520 | Theaters, Audience Areas of Motion Picture and Television Studios, Performance Areas, and Similar Locations | not in play | Nothing on this takeoff puts it in play. |
| 522 | Control Systems for Permanent Amusement Attractions | not in play | Nothing on this takeoff puts it in play. |
| 525 | Carnivals, Circuses, Fairs, and Similar Events | not in play | Nothing on this takeoff puts it in play. |
| 530 | Motion Picture and Television Studios and Similar Locations | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 540 | Motion Picture Projection Rooms | not in play | Nothing on this takeoff puts it in play. |
| 545 | Manufactured Buildings and Relocatable Structures | not in play | Nothing on this takeoff puts it in play. |
| 547 | Agricultural Buildings | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 550 | Mobile Homes, Manufactured Homes, and Mobile Home Parks | not in play | Nothing on this takeoff puts it in play. |
| 551 | Recreational Vehicles and Recreational Vehicle Parks | not in play | Nothing on this takeoff puts it in play. |
| 552 | Park Trailers | not in play | Nothing on this takeoff puts it in play. |
| 555 | Marinas, Boatyards, Floating Buildings, and Commercial and Noncommercial Docking Facilities | not in play | Nothing on this takeoff puts it in play. |
| 590 | Temporary Installations | not in play | Nothing on this takeoff puts it in play. |
| Nothing on this takeoff puts it in play. |
| 646 | Modular Data Centers | not in play | Nothing on this takeoff puts it in play. |
| 647 | Sensitive Electronic Equipment | not in play | Nothing on this takeoff puts it in play. |
| 650 | Pipe Organs | not in play | Nothing on this takeoff puts it in play. |
| 660 | X-Ray Equipment | not in play | Nothing on this takeoff puts it in play. |
| 665 | Induction and Dielectric Heating Equipment | not in play | Nothing on this takeoff puts it in play. |
| 668 | Electrolytic Cells | not in play | Nothing on this takeoff puts it in play. |
| 669 | Electroplating | not in play | Nothing on this takeoff puts it in play. |
| 670 | Industrial Machinery | not in play | Nothing on this takeoff puts it in play. |
| 675 | Electrically Driven or Controlled Irrigation Machines | not in play | Nothing on this takeoff puts it in play. |
| 680 | Swimming Pools, Fountains, and Similar Installations | not in play | Nothing on this takeoff puts it in play. |
| 682 | Natural and Artificially Made Bodies of Water | not in play | Nothing on this takeoff puts it in play. |
| 685 | Integrated Electrical Systems | not in play | Nothing on this takeoff puts it in play. |
| 690 | Solar Photovoltaic (PV) Systems | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 691 | Large-Scale Photovoltaic (PV) Electric Supply Stations | not in play | Nothing on this takeoff puts it in play. |
| 692 | Fuel Cell Systems | not in play | Nothing on this takeoff puts it in play. |
| 694 | Wind Electric Systems | not in play | Nothing on this takeoff puts it in play. |
| 695 | Fire Pumps | not in play | Nothing on this takeoff puts it in play. |
| not in play |
| Nothing on this takeoff puts it in play. |
| 725 | Class 1, Class 2, and Class 3 Remote-Control, Signaling, and Power-Limited Circuits | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 726 | Class 4 (CL4) Fault-Managed Power Systems | not in play | Nothing on this takeoff puts it in play. |
| 728 | Fire-Resistive Cable Systems | not in play | Nothing on this takeoff puts it in play. |
| 750 | Energy Management Systems | not in play | Nothing on this takeoff puts it in play. |
| 760 | Fire Alarm Systems | checked | In play; none of its checked sections applies to these lines. |
| 770 | Optical Fiber Cables | not in play | Nothing on this takeoff puts it in play. |