Derived from what the read produced, so none of it can drift from the data behind it. A blocker stops a price being presented as complete; it never stops you looking. These definitions are this build’s own — no RRE document specifies them yet.
| Check | Status | What the check found |
|---|---|---|
| Sheet scale | pass | All 5 plan sheet(s) carry a scale, so measurement is available. The other 15 read sheet(s) are specifications, schedules and details — nothing is measured on them, so a scale on one is not needed and a scale missing from one is not a gap. |
| Sheets read for scope | warning | 115 sheet(s) were indexed but not read for scope: 000-Copy-of-CM-Corp---Exhibit-A---Subcontract-Agreement_pdf-p1, 001-Copy-of-CM-Corp---Master-Agreement-MSA-Exhibit-C_pdf-p1, 001-Copy-of-CM-Corp---Master-Agreement-MSA-Exhibit-C_pdf-p2, 001-Copy-of-CM-Corp---Master-Agreement-MSA-Exhibit-C_pdf-p3, 001-Copy-of-CM-Corp---Master-Agreement-MSA-Exhibit-C_pdf-p4, 001-Copy-of-CM-Corp---Master-Agreement-MSA-Exhibit-C_pdf-p5, 001-Copy-of-CM-Corp---Master-Agreement-MSA-Exhibit-C_pdf-p6, 001-Copy-of-CM-Corp---Master-Agreement-MSA-Exhibit-C_pdf-p7, 001-Copy-of-CM-Corp---Master-Agreement-MSA-Exhibit-C_pdf-p8, 002-Copy-of-CM-Corp---Subcontractor-Insurance-Requirements_Updated-9_22_2023_pdf-p1, T1.0, G0.4, G0.5, G0.6, G0.7, A1.1, A6.0, A8.0, M2.0, M4.0, M4.1, M5.4, P1.0, P2.0, P3.0, P4.0, P4.1, P5.0, P6.0, P7.0, 004-Copy-of-S_CaptvieAire-208V_pdf-p8, 004-Copy-of-S_CaptvieAire-208V_pdf-p14, 004-Copy-of-S_CaptvieAire-208V_pdf-p15, 004-Copy-of-S_CaptvieAire-208V_pdf-p16, 004-Copy-of-S_CaptvieAire-208V_pdf-p17, 004-Copy-of-S_CaptvieAire-208V_pdf-p18, 005-Copy-of-S_Daikin-RTU-1_pdf-p1, 005-Copy-of-S_Daikin-RTU-1_pdf-p2, 005-Copy-of-S_Daikin-RTU-1_pdf-p6, 005-Copy-of-S_Daikin-RTU-1_pdf-p7, 005-Copy-of-S_Daikin-RTU-1_pdf-p10, 005-Copy-of-S_Daikin-RTU-1_pdf-p11, 006-Copy-of-S_Daikin-RTU-2_pdf-p1, 006-Copy-of-S_Daikin-RTU-2_pdf-p2, 006-Copy-of-S_Daikin-RTU-2_pdf-p3, 006-Copy-of-S_Daikin-RTU-2_pdf-p5, 006-Copy-of-S_Daikin-RTU-2_pdf-p7, 006-Copy-of-S_Daikin-RTU-2_pdf-p8, 006-Copy-of-S_Daikin-RTU-2_pdf-p10, 006-Copy-of-S_Daikin-RTU-2_pdf-p11, 006-Copy-of-S_Daikin-RTU-2_pdf-p12, 006-Copy-of-S_Daikin-RTU-2_pdf-p13, 006-Copy-of-S_Daikin-RTU-2_pdf-p14, DHH036, 006-Copy-of-S_Daikin-RTU-2_pdf-p16, 006-Copy-of-S_Daikin-RTU-2_pdf-p17, 006-Copy-of-S_Daikin-RTU-2_pdf-p18, DHH048, 006-Copy-of-S_Daikin-RTU-2_pdf-p20, 006-Copy-of-S_Daikin-RTU-2_pdf-p21, 006-Copy-of-S_Daikin-RTU-2_pdf-p22, DHH060, 006-Copy-of-S_Daikin-RTU-2_pdf-p24, 006-Copy-of-S_Daikin-RTU-2_pdf-p25, 006-Copy-of-S_Daikin-RTU-2_pdf-p26, DHH072, 006-Copy-of-S_Daikin-RTU-2_pdf-p28, 006-Copy-of-S_Daikin-RTU-2_pdf-p29, 006-Copy-of-S_Daikin-RTU-2_pdf-p30, 006-Copy-of-S_Daikin-RTU-2_pdf-p31, 006-Copy-of-S_Daikin-RTU-2_pdf-p32, 006-Copy-of-S_Daikin-RTU-2_pdf-p33, 006-Copy-of-S_Daikin-RTU-2_pdf-p34, 006-Copy-of-S_Daikin-RTU-2_pdf-p35, 006-Copy-of-S_Daikin-RTU-2_pdf-p36, 006-Copy-of-S_Daikin-RTU-2_pdf-p37, 006-Copy-of-S_Daikin-RTU-2_pdf-p38, 006-Copy-of-S_Daikin-RTU-2_pdf-p39, 006-Copy-of-S_Daikin-RTU-2_pdf-p40, 006-Copy-of-S_Daikin-RTU-2_pdf-p41, 006-Copy-of-S_Daikin-RTU-2_pdf-p42, 006-Copy-of-S_Daikin-RTU-2_pdf-p43, 006-Copy-of-S_Daikin-RTU-2_pdf-p44, 006-Copy-of-S_Daikin-RTU-2_pdf-p45, 006-Copy-of-S_Daikin-RTU-2_pdf-p46, 006-Copy-of-S_Daikin-RTU-2_pdf-p47, 006-Copy-of-S_Daikin-RTU-2_pdf-p48, 006-Copy-of-S_Daikin-RTU-2_pdf-p49, 006-Copy-of-S_Daikin-RTU-2_pdf-p50, 006-Copy-of-S_Daikin-RTU-2_pdf-p51, 006-Copy-of-S_Daikin-RTU-2_pdf-p52, 006-Copy-of-S_Daikin-RTU-2_pdf-p53, 006-Copy-of-S_Daikin-RTU-2_pdf-p55, 006-Copy-of-S_Daikin-RTU-2_pdf-p56, 006-Copy-of-S_Daikin-RTU-2_pdf-p57, 006-Copy-of-S_Daikin-RTU-2_pdf-p58, 006-Copy-of-S_Daikin-RTU-2_pdf-p59, 006-Copy-of-S_Daikin-RTU-2_pdf-p60, 006-Copy-of-S_Daikin-RTU-2_pdf-p61, 006-Copy-of-S_Daikin-RTU-2_pdf-p62, 006-Copy-of-S_Daikin-RTU-2_pdf-p65, 006-Copy-of-S_Daikin-RTU-2_pdf-p67, 006-Copy-of-S_Daikin-RTU-2_pdf-p68, 006-Copy-of-S_Daikin-RTU-2_pdf-p69, 006-Copy-of-S_Daikin-RTU-2_pdf-p70, 006-Copy-of-S_Daikin-RTU-2_pdf-p71, 006-Copy-of-S_Daikin-RTU-2_pdf-p72, 006-Copy-of-S_Daikin-RTU-2_pdf-p73, 006-Copy-of-S_Daikin-RTU-2_pdf-p74, 006-Copy-of-S_Daikin-RTU-2_pdf-p75, 006-Copy-of-S_Daikin-RTU-2_pdf-p77, 006-Copy-of-S_Daikin-RTU-2_pdf-p78, 006-Copy-of-S_Daikin-RTU-2_pdf-p79, 006-Copy-of-S_Daikin-RTU-2_pdf-p80, 007-rocklinelectric.net-Mail---CM-CORP_-The-Melt--Stanford-CA--Answered-RFI_s-p1. Looked at by the takeoff and not read: no electrical work on it. Read them, or state the omission on the proposal — the basis of the offer already prints it. |
| Symbol source | pass | A symbol list was found on the drawings: 004-Copy-of-S_CaptvieAire-208V_pdf-p4 — CaptiveAire Master Drawing 6912904 sheet 4 - Hood #1 (5430ND-2) fire system: TANK-SP-2 fire cabinet piping plan/elevation, fire cabinet legend, section view with recessed LED hood lights, 2" 120VAC electric gas valve & strainer schedule, CAS installation includes/excludes, E1.0 — ELECTRICAL LEGEND AND DETAILS. The project legend is authoritative for this set and outranks everything else — NECA 100-2006 itself allows a drawing to use non-standard symbols provided the legend explains them. NECA 100-2006 stays underneath it for anything the legend leaves silent, and no conventions file exists for the engineering firm. |
| Symbols named | pass | All 326 marks belong to a named group. |
| Every line prices | blocker | 39 line(s) point at no assembly, so nothing prices them: CIRCUIT BREAKER 15A 2P 208Y/120V BOLT-ON, PANEL A, CIRCUIT BREAKER 20A 1P 208Y/120V BOLT-ON, PANEL A, CIRCUIT BREAKER 20A 2P 208Y/120V BOLT-ON, PANEL A, CIRCUIT BREAKER 35A 2P 208Y/120V BOLT-ON, PANEL A, CIRCUIT BREAKER 20A 1P 208Y/120V BOLT-ON, PANEL B, CIRCUIT BREAKER 30A 3P 208Y/120V BOLT-ON, PANEL B…. They are counted and reported, and they stay outside the total. Attach a build-up from the catalog, or strike the line. |
| Plan and schedule agree | pass | No line has a plan/schedule disagreement. |
| Lines accepted by a person | blocker | Nothing has been accepted. All 171 line(s) are still suggestions, and machine output is a suggestion until a named person accepts it. Accept on the Takeoff screen — 132 line(s) are ready. |
| Engineer conventions known | pass | No engineer-dependent lines. |
| Unsure flags resolved | pass | The model raised no open flags. |
| Cover sheet read | pass | A cover sheet was found and read; its notes parameterise every later pass. |
What the symbol names rest on. The set’s own legend (004-Copy-of-S_CaptvieAire-208V_pdf-p4, E1.0), which is authoritative for this project.
| Line | Count | Sheet |
|---|---|---|
#16 THHN CU WIRE, 0-10V DIMMING PAIR (FULL CIRCUIT) 0-10V dimming pair in the lighting conduit | 1376 ft | E2.0 |
FEEDER (4)500KCMIL CU THHN + (1)#3G IN 3-1/2" EMT Transformer (landlord, 112.5 kVA) to panel L | 65 ft | E4.0 |
THERMOSTAT CONTROL CABLE, 18 AWG 8-CONDUCTOR (18/8) CL2, THERMOSTAT TO ROOFTOP UNIT (RTU-1, RTU-2), IN CONDUIT Thermostat-to-unit control cable; M0.1 GN11 has thermostats 'wired in conduit by electrical contractor'. Cable type assumed (Daikin unit may call for a communicating thermostat cable). | 63 ft | M1.0 |
TRACK - SUSPENDED LINE-VOLTAGE TRACK (CONTECH LT), TYPE TR 3 TR runs tagged 'TR A-31,d 60W', total feet | 33.5 ft | E2.0 |
FEEDER (4)#1/0 CU THHN + (1)#6G IN 2" EMT Panel L to panel A | 10 ft | E4.0 |
FEEDER (4)#1/0 CU THHN + (1)#6G IN 2" EMT Panel L to panel B (through shunt trip device) | 10 ft | E4.0 |
SHUNT TRIP SIGNAL WIRING, HOOD CONTROL PANEL ST/N1 TO SHUNT TRIP BREAKER COIL A1/A2, 120VAC, 2 WIRES Fire-condition shunt trip signal to the shunt trip device ahead of panel B (appliance power). | 1 ea | 004-Copy-of-S_CaptvieAire-208V_pdf-p11 |
Edition: 2025 California Electrical Code, because no job address on file, so California is assumed (RRE bids its California zones only); in force for permits from 2026-01-01, as of the bid date 2026-09-30. City and county amendments are the AHJ’s: check them on any job inside a city that amends the code. “To check” means the code requires it and the drawings do not show it: send an RFI, or make the call. Nothing here is added to the bid on its own.
| Section | Status | What the code requires | What the takeoff shows | RRE’s practice |
|---|---|---|---|---|
NEC 2023 110.16 Arc-flash warning label on gear | to check | Switchboards, switchgear, panelboards, meter socket enclosures and motor control centers likely to be worked on energized carry a field- or factory-applied arc-flash hazard warning. | In play for PANELBOARD 400A MCB 208Y/120V 3PH 4W 42-CKT NEMA 1 SURFACE, 10kAIC; PANELBOARD 225A MLO 208Y/120V 3PH 4W 60-CKT NEMA 1 SURFACE, 10kAIC; PANELBOARD 225A MLO 208Y/120V 3PH 4W 30-CKT NEMA 1 SURFACE, 10kAIC. Nothing on the takeoff shows it. | RRE carries phenolic nameplates and labels as their own item where the set calls for them. |
NEC 2023 210.8(B), 406.9(B) GFCI, weather-resistant, in-use cover outdoors and on the roof | to check | Rooftop and outdoor receptacles GFCI protected, weather-resistant type, with an extra-duty in-use cover in wet locations. | 2 of 3 in play are not shown with it: #10 THHN CU; 3/4" EMT CONDUIT (ROOF EQUIPMENT HOMERUNS). | RRE carries roof and patio receptacles as WR GFCI with an in-use cover where they are drawn (The Melt: 3). |
NEC 2023 408.4(A) Circuit directory at every panel | to check | Every circuit and circuit modification legibly identified as to its clear, evident and specific purpose on a circuit directory at the panel. |
The RRE item carries no price for the part named, so the estimate has the install labor and rough-in only, and the vendor or sub prices the rest. Send the lighting and gear lists from Material list & vendor quotes.
| Line | Needs a price for | Count | Sheet |
|---|---|---|---|
LIGHT FIXTURE TYPE P1 - SUSPENDED CYLINDER LED DOWNLIGHT (ALPHABET BETA-3R) P1 pendant cylinders, dining room and corridor, circuit A-1,a | LED PENDANT MOUNTED LA | 33 ea | E2.0 |
LIGHT FIXTURE TYPE P1E - SUSPENDED CYLINDER LED DOWNLIGHT W/ REMOTE EMERGENCY BATTERY (ALPHABET BETA-3R) P1E hatched symbols, dining/corridor, A-1,a | LED EMERGENCYLIGHT DUAL | 22 ea | E2.0 |
LIGHT FIXTURE TYPE YP1 - DECORATIVE RLM PENDANT W/ GUARD (BARN LIGHT) YP1 pendants, A-33,b | LED PENDANT MOUNTED LA | 8 ea | E2.0 |
LIGHT FIXTURE TYPE X - LED EXIT SIGN W/ BATTERY (LITHONIA LHQM) Exit signs tagged X A-3 | LED GRN EXIT FIXTURE | 7 ea | E2.0 |
TRACK HEAD TYPE T3 - TRACK ACCENT (LUMENTURE T65) T3 heads on the two short TR runs | LED TRACK SPOT FIXTURE | 6 ea | E2.0 |
LIGHT FIXTURE TYPE YP2 - 66" I-BEAM LINEAR PENDANT (BASILE STUDIO) |
23 lines the reader wrote at zero are not listed: they add nothing to the bid.
Raceway model on E3.0, 3 conductors per circuit x run; modelled from untagged devices from panel A. Type changed from '#12 THHN CU WIRE (power branch, modelled)' to #10 by the house rule (house.json house_rules_2026_09_29.branch_conductor: #10 THHN for all general branch); quantity unchanged. (Model line id L-0106.)
From the same modelled run: 2325 ft #12 THHN (3 wires per circuit, dedicated neutral per GN23/E6.0). GN6 upsizes to #10 beyond 100 ft - no circuit on the modelled routes was checked against that; confirm with real tags. Type changed from '#12 THHN CU WIRE (LIGHTING BRANCH)' to #10 by the house rule (house.json house_rules_2026_09_29.branch_conductor: #10 THHN for all general branch); quantity unchanged. (Model line id L-0090.) The model also raised 'modelled from untagged fixtures', which the contract has no flag for; recorded here rather than dropped.
Wire from the same raceway model run: 3 conductors per circuit (hot, dedicated neutral, ground) along each circuit's path, 1288.3 ft #12. All runs < 100 ft so GN6 keeps #12. Modelled from untagged receptacles. Striking removes the IT receptacle branch wire. Type changed from '#12 THHN CU WIRE (branch, IT receptacle circuits)' to #10 by the house rule (house.json house_rules_2026_09_29.branch_conductor: #10 THHN for all general branch); quantity unchanged. (Model line id L-0124.) The model also raised 'modelled from untagged receptacles', which the contract has no flag for; recorded here rather than dropped.
Modelled from untagged fixtures/devices: 0 homerun tags read on E3.0 (text is outlined); 40 circuits from panel A (placed at PANELBOARD A, PDF 935,1000) through the 41 receptacle symbols, 14 shared homeruns, 3 circuits to a pipe. Device drops in EMT (MC drops barred by E6.0). Modelled, not measured. (Model line id L-0105.)
raceway_model.py read 0 circuit tags from E2.0 (lettering drawn as outlines), so the fixtures (scanner groups 14,21,28,42,69) were fed as modelled from untagged fixtures: panel A placed at the time switch/contactor wall (PDF 1248,1075; E3.0 puts panels at the kitchen/dining wall - confirm), 5 lighting circuits (A-1, A-3, A-31, A-33, A-44 from the panel schedule), 2 shared homerun pipes. Job-facts 'MC fixture chain: barred' (E6.0 allows MC only as J-box-to-fixture whips), so the chain stays in EMT: 687.8 ft 3/4" EMT. Polyline is indicative of the modelled route. (Model line id L-0089.) The model also raised 'modelled from untagged fixtures', which the contract has no flag for; recorded here rather than dropped.
Homeruns are not drawn on E3.1 and the callouts are outline lettering (0 tags read by raceway_model; it placed nothing). Modelled by hand: each unit is fed from panel L (BOH, E3.0) up to an assumed roof penetration at SF-1 / hood area (970,700 pt), then orthogonally across the roof to the unit at 1/4"=1'-0" (18 pt/ft), plus a 25 ft allowance per homerun for panel L to the roof deck. EMT + THHN (MC barred, E6.0). 4x25.4 + 4x35.7 + 3x33.8 + 3x80.0 ft; all under 100 ft (GN6). Type changed from '#12 THHN CU' to #10 by the house rule (house.json house_rules_2026_09_29.branch_conductor: #10 THHN for all general branch); quantity unchanged. (Model line id L-0119.)
E1.0 GN10 "ALL EMPTY CONDUIT SHALL HAVE A PULL WIRE"; KN3 data conduit "with pull string". Length = LV stub footage + one 1" KN3 data run. Striking removes the pull string. (Model line id L-0127.)
E1.0 LV legend: every LV device is rough-in only, J-box + 3/4" conduit stubbed to accessible ceiling; KN5 conduits + J-boxes for camera/speaker wiring (wiring by others). Per box = ceiling height (job-facts A7.0) minus box height: dining/corridor open ceiling has no height -> 12 ft each (kiosk 2, POS 2, OSB 1, WAP IT-115 1, cameras IT-113A/B/C/D/E/H 6, speakers IT-114A-G 7 incl. patio IT-114G) = 228 ft; kitchen KDS 6 x (9.5-5.5 at 66" AFF) = 24 ft; BOH IT-121/105/111 3 x (9.0-1.5) = 22.5 ft; kitchen/BOH ceiling cameras IT-113F/G/I box at ceiling = 0 ft. Total 274.5 ft. Striking removes the LV stubs. (Model line id L-0126.)
Homeruns are not drawn on E3.1 and the callouts are outline lettering (0 tags read by raceway_model; it placed nothing). Modelled by hand: each unit is fed from panel L (BOH, E3.0) up to an assumed roof penetration at SF-1 / hood area (970,700 pt), then orthogonally across the roof to the unit at 1/4"=1'-0" (18 pt/ft), plus a 25 ft allowance per homerun for panel L to the roof deck. EMT + THHN (MC barred, E6.0). Runs: RTU-2 58.1, SF-1 25.4, EF-1 35.7, EF-2 33.8, L-6 homerun+roof chain 80.0 ft. (Model line id L-0114.)
raceway_model.py on page 40 with the 11 receptacle positions as stops, panel A located at its E3.0 position (BOH wall grid 6-7/G, mapped onto E3.2 at PDF pt 1006,962) and --untagged-panel A --untagged-circuits 11 (the A-xx tags are drawn as outlines; 0 read from the text layer). Modelled from untagged fixtures/receptacles: 11 runs, 4 shared homerun pipes, house method (Manhattan, no waste, 10 ft device drop). Conduit 233.0 ft 3/4" EMT (E6.0: metallic raceway; MC device drops barred). Scale 1/4"=1'-0" from the view title (18 pt/ft). Striking removes the IT receptacle branch pipe. (Model line id L-0123.) The model also raised 'modelled from untagged receptacles', which the contract has no flag for; recorded here rather than dropped.
Homeruns are not drawn on E3.1 and the callouts are outline lettering (0 tags read by raceway_model; it placed nothing). Modelled by hand: each unit is fed from panel L (BOH, E3.0) up to an assumed roof penetration at SF-1 / hood area (970,700 pt), then orthogonally across the roof to the unit at 1/4"=1'-0" (18 pt/ft), plus a 25 ft allowance per homerun for panel L to the roof deck. EMT + THHN (MC barred, E6.0). 4 x 58.1 ft (schedule #10). (Model line id L-0118.)
Homeruns are not drawn on E3.1 and the callouts are outline lettering (0 tags read by raceway_model; it placed nothing). Modelled by hand: each unit is fed from panel L (BOH, E3.0) up to an assumed roof penetration at SF-1 / hood area (970,700 pt), then orthogonally across the roof to the unit at 1/4"=1'-0" (18 pt/ft), plus a 25 ft allowance per homerun for panel L to the roof deck. EMT + THHN (MC barred, E6.0). 3 x 45.9 ft. (Model line id L-0116.)
60 wired 20A/1P circuits across panels L/A/B (spares, spaces, FUTURE EXT LTG excluded). (Model line id L-0029.)
Detail G/A8.1 'SUSPENDED LIGHT FIXTURE' (lay-in fixture in ACT): '12 GA GALVANIZED WIRE AT FOUR CORNERS OF FIXTURE' (also detail E: '12 GA WIRE AT EACH CORNER OF LIGHT FIXTURE AND TWO SLACK WIRES'). 4 wires x 12 lay-in 2x4 troffers counted on E2.0 (R3 6 + R3EM 6, E2.0 L-0006/L-0007) = 48. E1.0 GN9 gives fixture support to the EC ('support suspended fixtures independently at each corner, 12 ga wire'). Kitchen ACT is the only lay-in fixture ceiling on E2.0. (Model line id L-0160.) The model also raised 'ceiling-wire length not measurable: structure height above the 9\'-6" kitchen ceiling not given on A8.1', which the contract has no flag for; recorded here rather than dropped.
E1.0 LV legend: every low-voltage device gets a J-box and 3/4 in conduit stubbed to accessible ceiling. 9 0-10V $D positions on E2.0: 7 in the BOH gang (ceiling 9'-0" C-2 less 48" mount = 5 ft each) and 2 at the kitchen doors (9'-6" less 48" = 5.5 ft each): 35 + 11 = 46 ft (av_stub_rule). (Model line id L-0088.)
Homeruns are not drawn on E3.1 and the callouts are outline lettering (0 tags read by raceway_model; it placed nothing). Modelled by hand: each unit is fed from panel L (BOH, E3.0) up to an assumed roof penetration at SF-1 / hood area (970,700 pt), then orthogonally across the roof to the unit at 1/4"=1'-0" (18 pt/ft), plus a 25 ft allowance per homerun for panel L to the roof deck. EMT + THHN (MC barred, E6.0). RTU-1 150A: 3#1/0 + #6G per schedule wire size -> 1-1/2" EMT. (Model line id L-0115.)
Homeruns are not drawn on E3.1 and the callouts are outline lettering (0 tags read by raceway_model; it placed nothing). Modelled by hand: each unit is fed from panel L (BOH, E3.0) up to an assumed roof penetration at SF-1 / hood area (970,700 pt), then orthogonally across the roof to the unit at 1/4"=1'-0" (18 pt/ft), plus a 25 ft allowance per homerun for panel L to the roof deck. EMT + THHN (MC barred, E6.0). 1 x 45.9 ft. (Model line id L-0117.)
Counted 33 open-circle P1 symbols tagged 'P1 A-1,a' on the E2.0 lighting plan (dining room 120 and corridor), confirmed on 170-dpi crops; scanner group 14 matches the count. E4.0 schedule / T24 (11 P1+P1E) is a compliance count, the plan governs. Striking removes the P1 fixtures. (Model line id L-0063.)
Runs 7.0, 7.0 and 19.5 ft bought in 8' pieces with a 4' piece for the remainder: 1 + 1 + 2 = 4 eight-foot pieces. (Model line id L-0075.)
M1.0 draws the two thermostat positions (T with keynote 1, 'PROVIDE 7-DAY PROGRAMMABLE THERMOSTAT ... INSTALL 48" AFF'): RTU-1's on the dining/corridor wall at grid 7/G, RTU-2's at grid 8/F in the BOH corridor. Measured rectilinear at 1/4"=1'-0" (18 pt/ft) from each T to its unit's supply drop: RTU-1 T (916,944) to RTU-1 drop (836,839) = 80+104 pt = 10.3 ft; RTU-2 T (1159,1049) to RTU-2 drop at the 16x12 main (1306,1091) = 148+43 pt = 10.6 ft. Plus 4 ft each to rise from the stub top to the deck and into the curb (roof deck height not given on M1.0; keynote 12 puts supply duct centerline at 16'-0" AFF). 14.3 + 14.6 = 28.9, carried 29 ft. The 12 ft wall stubs are already on M0.1 and are not included. Responsibility conflict M0.1 GN11 vs M0.2 'Controls, Electric' (see M0.1 gap) applies: strike with M0.1 L-0001 if the mechanical contractor carries controls conduit. (Model line id L-0164.) The model also raised 'est-review', 'responsibility conflict M0.1 GN11 vs M0.2 Controls', 'vertical allowance assumed', which the contract has no flag for; recorded here rather than dropped.
Detail G/A8.1 'SUSPENDED LIGHT FIXTURE' (lay-in fixture in ACT): '12 GA GALVANIZED SLACK WIRES MIN. TWO PER FIXTURE FROM DIAGONALLY OPPOSITE CORNERS TO STRUCTURE ABOVE'. 2 wires x 12 lay-in troffers on E2.0 (R3 6 + R3EM 6) = 24. Carried separately from the 4 corner wires because the detail draws and notes both (detail E repeats 'each corner ... and two slack wires'). (Model line id L-0161.) The model also raised 'estimator decision: detail reads as 4 corner + 2 slack = 6 wires per troffer; if the two slack wires are two of the four corner wires, drop this line', which the contract has no flag for; recorded here rather than dropped.
Counted 22 hatched-circle P1E symbols tagged 'P1E A-1,a' on E2.0; scanner group 21 matches. Striking removes the emergency P1E fixtures. (Model line id L-0064.)
Kitchen equipment duplex receptacles at P-750, R-155 x2, R-156, C-851, P-756, C-700, R-161, C-820, C-910, H-681, C-880, C-875, C-890, R-175 x2, S-950, S-920, S-930, GWH-1 (L-8), GWH-2 (L-10). E1.0 GN24 'all kitchen equipment shall have readily accessible GFCI protection' + schedule note 4: carried GFCI at the device. (Model line id L-0093.)
E3.2 KN3: "PROVIDE (2) 1" CONDUITS FOR POWER AND (1) 1" CONDUIT WITH PULL STRING FOR DATA AT REGISTERS. COORDINATE ROUTING OF TRENCHING IN FIELD... ROUTE TO NEAREST WALL AS SHOWN." Measured the drawn dashed run from the POS counter stubs to the wall stubs at A-23: 5.9 ft at 1/4"=1'-0", x3 conduits = 17.7 ft. Below-slab PVC assumed (E6.0 wants metallic raceways; confirm RMC/PVC-coated if the engineer holds it). Vertical stub-ups not drawn, not added. Striking removes the trench conduits. (Model line id L-0125.) The model also raised 'material_below_slab_confirm', which the contract has no flag for; recorded here rather than dropped.
Counted 14 data outlet positions (open triangles, E1.0 legend "data outlet"; a cluster of triangles at one spot is one box): kiosk x2 (2 jacks each), POS IT-101A (3) and IT-101B (2), OSB at A-35, KDS ice cream/expo/melt finish/grill/prep x2, and IT-121, IT-105, IT-111 at the BOH manager area. LVC provides cable (E1.1); EC box + stub only. Striking removes 14 backboxes. (Model line id L-0128.)
Dining room and front-of-house duplex receptacles A-41 (x6, incl. KN1 show-window receptacles), A-55 (x3), A-53 +15" (x3); dining note: all receptacles tamper resistant. (Model line id L-0092.)
Three L2 tags 'L2 A-33,e' ring the millwork enclosure west of grid DB on E2.0; no run length is dimensioned, so the three heavy edges were measured at 18 pt/ft: 2.9 + 5.4 + 2.9 ft = 11.3 ft. Tape location (top/under shelf) not detailed; confirm on the millwork drawings. (Model line id L-0073.)
Counted 11 slashed-circle R1 tags 'R1 A-3,h' in the BOH/prep area east of grid DB on E2.0 (170-dpi crop). T24 lists R1/R1E 17; plan shows 16 (11 R1 + 5 R1E). Scanner group 28 holds both R1 and R1E (17 members). Striking removes R1. (Model line id L-0065.)
J-boxes drawn: A-54, A-56, A-58 interior signage (KN6); L-2, L-4 exterior signage on inside face of wall (KN9); A-43, A-45 hand dryers; H-680, H-682 hood / hood control panel (KN14); walk-in condenser feed A-2,4 (tag 3) and evaporator A-6 (tag 4). (Model line id L-0098.)
Counted a 7-gang row of '$D' dimmer switches labelled a b c d e h z at the time switch location, plus 2 '$D' marked k,3 at the kitchen doors, on E2.0. Detail 2 names them 'remote dimming switches (typ)'. Plate/box ganging: one 7-gang location. (Model line id L-0080.)
Counted 9 camera symbols tagged IT-113A through IT-113I (E1.0 legend "camera"). KN5: EC provides conduits and junction boxes for camera wiring (by others); E1.1 cameras by vendor, LVC cable. Striking removes 9 boxes. (Model line id L-0130.)
One L1 run tagged 'L1 A-33,e' (leader to the millwork line north of the restroom corridor) on E2.0; no dimension on the plan, so the drawn line was measured at 1/4"=1'-0" (18 pt/ft): about 152 pt = 8.5 ft. Confirm against the millwork elevation. (Model line id L-0072.)
House rule: panel safe-off one line, 8 hr per job. Existing landlord 200A disconnect/meter and switchboard MSB6 remain (E4.0 one-line). (Model line id L-0062.)
Counted 8 R2 tags 'R2 A-44', 4 in each unisex restroom, on E2.0; matches the T24 count of 8. (Model line id L-0067.)
Counted 8 YP1 large-circle pendants tagged 'YP1 A-33,b' (3 along the north storefront, 5 along the track by the banquette) on E2.0; matches T24 8. (Model line id L-0070.)
Special-purpose (Y-symbol) receptacles at C-830, C-800, C-900, C-730, C-780 (2), C-720, C-870. No schedule gives NEMA configurations; GFCI protection per GN24 / schedule note 4. (Model line id L-0095.)
Six 'X A-3' tags on E2.0 with 7 exit symbols (the main entry shows a wall exit plus a ceiling exit under one tag). Face/arrow count not settled. (Model line id L-0079.)
Counted 7 speaker symbols (circled "s") tagged IT-114A through IT-114G. KN5: conduits + J-boxes for speaker wiring by EC, wiring by others (PROAVCOMM/MOOD). IT-114G sits outside the storefront at the patio: exterior-rated box, confirm mounting. Striking removes 7 boxes. (Model line id L-0131.)
Counted 6 plain (X-only) 2x4 troffers tagged 'R3 A-3,k' in the kitchen on E2.0. R3+R3EM = 12 matches T24 R3/R3E 12. (Model line id L-0068.)
Counted 6 hatched 2x4 troffers tagged 'R3EM A-3,k' on E2.0 (the T24 form calls them R3E). (Model line id L-0069.)
Counted 6 T3 track heads (3 per run) on the two 7 ft TR runs on E2.0. T24 lists 2 (compliance count); plan governs. (Model line id L-0077.)
No J-box symbol is drawn at them, but job-facts lists inverters #1/#2, the time switch, LC1, LC2 as hard-wired, and KN2 circuits walk-in cooler lights (by walk-in mfr) to A-8: 2 + 1 + 2 + 1 = 6 connections (hardwired_equipment_jbox). (Model line id L-0087.)
Counted 6 quad receptacle symbols at the kitchen KDS positions (A-19 KDS ice cream, A-21 KDS expo, A-23 KDS melt finish, A-25 KDS grill, A-27 and A-29 KDS prep). GFCI at the device per E1.0 GN24 "ALL KITCHEN EQUIPMENT SHALL HAVE READILY ACCESSIBLE GFCI PROTECTION" (kitchen place named in the set) and E3.0 kitchen schedule note 4; E4.0 also flags these GF. E1.1: KDS double gang 4x120V, stainless plate, 66" AFF. Striking removes 6 GFCI double duplex devices. (Model line id L-0122.) The model also raised 'gfci_from_note_GN24_confirm_KDS_is_kitchen_equipment', which the contract has no flag for; recorded here rather than dropped.
One YP2 linear pendant tagged 'YP2 A-33,c' over the communal table on E2.0 (T24 1); the schedule gives it as 66 in = 5.5 ft, which the drawn bar confirms (about 99 pt at 18 pt/ft). One fixture. (Model line id L-0071.)
Counted 5 filled-circle R1E tags 'R1E A-3,h' in BOH on E2.0. Striking removes R1E. (Model line id L-0066.)
Counted 5 T1 heads on the 19.5 ft banquette track on E2.0. T24 lists 1; plan governs. (Model line id L-0078.)
2 feeders x 2 ends (150A/3P breaker in L, MLO lugs in A/B). (Model line id L-0037.)
The 19.5 ft banquette run takes 2 x 8' + 1 x 4'; the 7 ft runs take one 8' each (cut). (Model line id L-0076.)
3 wired 20A/2P circuits across panels L/A/B (spares, spaces, FUTURE EXT LTG excluded). (Model line id L-0030.)
E3.0 KN6 'provide junction box and disconnect for interior signage' at A-54/A-56/A-58 (20A/1P). Size not called out. Step 4.5: the unit this disconnect serves is not in any equipment schedule read (output/work/equipment); line kept as drawn, sizing unverified -- see coverage. (Model line id L-0055.) The model also raised 'size inferred from MOCP', 'unit-not-scheduled', which the contract has no flag for; recorded here rather than dropped.
Front counter cloud (delta 1, KN2): A-39 two quads, A-37 one quad (A-37 is GF on panel A; symbol not marked GFCI -- carried as plain quad). (Model line id L-0096.)
E3.1 roof plan: three duplex receptacle symbols each tagged "L-6 WP/GFCI", at SF-1, RTU-1 and RTU-2. GFCI at the device, weatherproof in-use cover (E1.0 GN20). Panel L-6 = roof receptacles. (Model line id L-0112.)
Counted 3 duplex receptacle symbols (circle with two bars, E1.0 legend "duplex receptacle NEMA 5-20R") on the E3.2 IT power plan: kiosk A-11 and A-13 at the dining-room kiosk wall (KN1) and A-35 for the order status board ("confirm final mounting height and location of power and data for OSB"). Dining-room receptacles tamper resistant (E3.0 note). E4.0 flags A-11/13/35 GF breakers; no GFCI symbol or note names the kiosk/OSB place, so no device GFCI is carried (panel GF breaker per schedule). Striking removes 3 duplex devices. (Model line id L-0120.)
2 wired 15A/3P circuits across panels L/A/B (spares, spaces, FUTURE EXT LTG excluded). (Model line id L-0028.)
2 wired 30A/3P circuits across panels L/A/B (spares, spaces, FUTURE EXT LTG excluded). (Model line id L-0033.)
2 wired 50A/3P circuits across panels L/A/B (spares, spaces, FUTURE EXT LTG excluded). (Model line id L-0035.)
(4)500kcmil,(1)#3G from landlord 112.5 kVA transformer to L: 2 ends. (Model line id L-0038.) The model also raised 'confirm EC terminates at landlord transformer', which the contract has no flag for; recorded here rather than dropped.
E3.0 KN9 'junction box and disconnect on inside face of wall for exterior signage; within sight of sign' at L-2 and L-4. Step 4.5: the unit this disconnect serves is not in any equipment schedule read (output/work/equipment); line kept as drawn, sizing unverified -- see coverage. (Model line id L-0056.) The model also raised 'size inferred from MOCP', 'unit-not-scheduled', which the contract has no flag for; recorded here rather than dropped.
E2.0 KN3; INVERTER #1 and #2 shown in restrooms. (Model line id L-0061.)
Two 'OS' sensors, one per unisex restroom, on E2.0; E3.0 KN5 interlocks the restroom exhaust fan to them. (Model line id L-0081.)
Restrooms 123/124: A-47 +42" GFI, one each. (Model line id L-0094.)
Restrooms: $M at EF-3 and EF-4, A-44; KN5 interlock with restroom occupancy sensor. (Model line id L-0102.)
EF-3, EF-4 ceiling exhaust fans (hard-wired, job-facts). (Model line id L-0103.)
Counted 2 quad receptacle symbols (circle with cross, E1.0 legend "quad receptacle NEMA 5-20R") at the two POS registers, circuits A-15 and A-17 (E1.1 matrix P-3/P-4: double gang 4x120V under each POS). Front counter, dining side: tamper resistant. Not GFCI: symbol and tag carry no GF and no note names the POS place (E4.0 GF breaker only). Striking removes 2 double duplex devices. (Model line id L-0121.)
M0.1 Mechanical General Note 11 (outlined text, read from a 200-dpi render) reads: 'Thermostats and humidistats shall be located and set by mechanical contractor and wired in conduit by electrical contractor ... mounting heights shall be 48" AFF to meet ADA requirements.' This sheet does not locate thermostats; the count of 2 assumes one thermostat per rooftop unit (RTU-1 and RTU-2 per job facts) and no humidistats. Each position is carried as a box with a 12 ft 3/4" EMT stub per the house rule for low-voltage backboxes. Striking this line removes the EC thermostat rough-in (e.g. if the M0.2 controls section governs and the mechanical contractor provides the conduit). (Model line id L-0168.) The model also raised 'assumed count', 'responsibility conflict M0.1 GN11 vs M0.2 Controls', 'est-review', which the contract has no flag for; recorded here rather than dropped.
Panelboard L schedule: 400A bus, 400A MCB, surface, NEMA 1, 42 circuits. (Model line id L-0001.)
Panelboard A schedule: 225A bus MLO, surface, circuits 1-60. (Model line id L-0002.)
Panelboard B schedule: 225A bus MLO, surface, circuits 1-30. (Model line id L-0003.)
One-line: 'PROVIDE SHUNT TRIP DEVICE AHEAD OF PANEL'; panel B note 'shunt trip device to shut down entire panel'. (Model line id L-0004.) The model also raised 'device form not specified', which the contract has no flag for; recorded here rather than dropped.
1 wired 15A/2P circuits across panels L/A/B (spares, spaces, FUTURE EXT LTG excluded). (Model line id L-0027.)
1 wired 25A/3P circuits across panels L/A/B (spares, spaces, FUTURE EXT LTG excluded). (Model line id L-0031.)
1 wired 30A/2P circuits across panels L/A/B (spares, spaces, FUTURE EXT LTG excluded). (Model line id L-0032.)
1 wired 35A/2P circuits across panels L/A/B (spares, spaces, FUTURE EXT LTG excluded). (Model line id L-0034.)
1 wired 150A/3P circuits across panels L/A/B (spares, spaces, FUTURE EXT LTG excluded). (Model line id L-0036.)
E3.1 callout '200/3/150 NEMA 3R' = 200A switch, 3P, 150A fuse (E1.0 legend 60/3/40 convention). Step 4.5 sized from the unit: RTU-1 schedule (M3.0 / Daikin p3) 208V 3PH MOCP 150A -> next standard switch at or above the MOCP is 200A; outdoors on the roof so NEMA 3R; E3.1 draws this disconnect fused, so fuses at the MOCP (150A). (Model line id L-0042.)
Rooftop unit RTU-1 (roof): flex whip from NEMA 3R disconnect to unit. (Model line id L-0043.)
E3.1 callout '30/3/25 NEMA 3R' (rev 1 cloud). Step 4.5 sized from the unit: RTU-2 schedule (M3.0 (rev 1)) 208V 3PH MOCP 25A -> next standard switch at or above the MOCP is 30A; outdoors on the roof so NEMA 3R; E3.1 draws this disconnect fused, so fuses at the MOCP (25A). Daikin submittal p54 prints MOP 35A (MCA 31.1) for the DHH0363D row -- that would make it a 60A switch with 35A fuses; the M3.0 rev-1 schedule (MOCP 25) governs here, flagged. (Model line id L-0044.) The model also raised 'schedule-submittal-conflict', which the contract has no flag for; recorded here rather than dropped.
Rooftop unit RTU-2 (roof): flex whip from NEMA 3R disconnect to unit. (Model line id L-0045.)
E3.1 callout '30/3/15 NEMA 3R'. Step 4.5 sized from the unit: EF-1 (CaptiveAire EXH-1) schedule (J10 / M5.2 / CaptiveAire p11) 208V 3PH MOCP 15A -> next standard switch at or above the MOCP is 30A; outdoors on the roof so NEMA 3R; E3.1 draws this disconnect fused, so fuses at the MOCP (15A). (Model line id L-0046.)
Rooftop unit SF-1 supply fan (roof): flex whip from NEMA 3R disconnect to unit. (Model line id L-0047.)
E3.1 callout '30/3/15 NEMA 3R'. Step 4.5 sized from the unit: SF-1 (CaptiveAire SUP-3 / MUA fan 3) schedule (J10 / M3.0 / CaptiveAire p11) 208V 3PH MOCP 15A -> next standard switch at or above the MOCP is 30A; outdoors on the roof so NEMA 3R; E3.1 draws this disconnect fused, so fuses at the MOCP (15A). (Model line id L-0048.)
Rooftop unit EF-1 exhaust fan (roof): flex whip from NEMA 3R disconnect to unit. (Model line id L-0049.)
E3.1 'L-25 NEMA 3R' with $M motor-rated switch symbol; 20A/1P circuit. Step 4.5: EF-2 (CaptiveAire EXH-2) 115V 1PH, MCA 11.2A, MOP 20A (J10/M5.2); the 20A 1P motor-rated switch in a NEMA 3R enclosure covers the 20A MOCP. (Model line id L-0050.)
Rooftop unit EF-2 exhaust fan (roof): flex whip from NEMA 3R disconnect to unit. (Model line id L-0051.)
E3.0 KN3 'walk-in cooler condenser (on roof). Provide NEMA 3R disconnect switch per manufacturer's requirements'. No size callout; sized from the unit's 15A/2P breaker (smallest 2P switch 30A). Unit not drawn on E3.1. Step 4.5: the unit this disconnect serves is not in any equipment schedule read (output/work/equipment); line kept as drawn, sizing unverified -- see coverage. (Model line id L-0052.) The model also raised 'size inferred from MOCP', 'unit location not on roof plan', 'unit-not-scheduled', which the contract has no flag for; recorded here rather than dropped.
Rooftop condenser: flex whip from NEMA 3R disconnect. (Model line id L-0053.)
E3.0 KN4 'provide disconnect switch per manufacturer's requirements'. No size; derived from 20A/1P circuit. Step 4.5: the unit this disconnect serves is not in any equipment schedule read (output/work/equipment); line kept as drawn, sizing unverified -- see coverage. (Model line id L-0054.) The model also raised 'size inferred from MOCP', 'unit-not-scheduled', which the contract has no flag for; recorded here rather than dropped.
E2.0 detail 2: LC1 controls A-1, A-33, A-31, A-3, A-56, A-58, A-54, A-41 (+ EM legs); note 4 Square D 8903 'pole quantity as indicated'. Pole count read ~12-13. Pole count: the duplicate reader (struck L-0083) read 13 poles drawn and assumed 16 for spares; this line keeps 12 -- flagged, see coverage. (Model line id L-0057.) The model also raised 'confirm pole count', 'pole-count-unsure', which the contract has no flag for; recorded here rather than dropped.
E2.0 detail 2: LC2 with L-2, L-4 and 2 spare poles. (Model line id L-0058.)
E2.0 note 3. (Model line id L-0059.)
E2.0 detail 2 'provide 2-hour timed override switch'. (Model line id L-0060.)
Front counter: A-51 duplex beside the quads. (Model line id L-0097.)
RP on L-12 at GWH-1/GWH-2 (hard-wired, job-facts). (Model line id L-0104.)
KN4 "PROVIDE WIRELESS ACCESS POINTS. COORDINATE LOCATIONS AND QUANTITY WITH OWNER AND IT VENDOR." One WAP drawn (IT-115, triangle, keynote 4) in the dining room. Striking removes 1 box. (Model line id L-0129.)
Fire System Parts List, fire system 1 (TANK FS 4.0/4.0, fire cabinet left, hood 1): 'A0034332 JUNCTION BOX FOR MANUAL PULL STATION. 1.5" DEEP BACK BOX, RED COLOR' qty 1 by factory, and 'A0034331 24VDC SINGLE ACTION MANUAL ACTUATION DEVICE (PUSH/PULL STATION) WITH PROTECTIVE COVER, ONE (1) NORMALLY OPEN CONTACT' qty 1 by factory; the Typical Ansul R-102 layout draws 1 REMOTE MANUAL PULL STATION. The box and device are CaptiveAire-furnished; the sheet does not say who mounts the box or runs the raceway. Carried as EC box mounting + conduit stub on the house LV backbox rule; strike if the fire-suppression distributor does its own rough-in. (Model line id L-0144.) The model also raised 'est-review', 'responsibility assumed', which the contract has no flag for; recorded here rather than dropped.
Gas Valve(s) table, fire system 1: TYPE 'SC ELECTRICAL', SIZE 2.000, SUPPLIED BY 'CAPTIVEAIRE SYSTEMS' - 1 valve. An electric (solenoid) gas valve needs a field-wired connection to the hood fan and light control panel (drawn on the Typical Ansul R-102 layout; power to the panel is E3.0 KN14). Valve location and conduit route are not on this sheet, so only the connection is counted; the raceway run is a coverage gap. (Model line id L-0145.) The model also raised 'est-review', which the contract has no flag for; recorded here rather than dropped.
CaptiveAire electrical package job 6912904 (DCV-2111, ECP #1-1..#1-4), p11. ECP #1-1 'CONTROL PANEL TO FANS - Responsibility: Electrician': 'SHIELDED TWISTED PAIR PWM SPEED SIGNAL CONTROL PANEL TO ECM OUTDOOR RATED' to EXH-2 ECM-01 (RED+/BLACK-). One run counted. (Model line id L-0147.) The model also raised 'route-length-not-on-sheet', which the contract has no flag for; recorded here rather than dropped.
CaptiveAire electrical package job 6912904 (DCV-2111, ECP #1-1..#1-4), p11. ECP #1-2 'CONTROL PANEL TO ACCESSORY ITEMS - Responsibility: Electrician': 'CONTROL PANEL TO HOOD LIGHTS 1400 W MAX WIRE TO J-BOX ON TOP OF HOOD' B1 black / W1 white / GND green, HOOD LIGHTS 1. Package table: Hood #1, 1 light switch. One connection counted. (Model line id L-0148.)
CaptiveAire electrical package job 6912904 (DCV-2111, ECP #1-1..#1-4), p11. ECP #1-2 'CONTROL PANEL TO GAS VALVE' (120V ONLY, or 24V DC ONLY) and ECP #1-3 'ELECTRICIAN: ... 5. WIRE GAS VALVE'; EC requirement table row GAS VALVE <1.0 A. One valve drawn. (Model line id L-0149.)
CaptiveAire electrical package job 6912904 (DCV-2111, ECP #1-1..#1-4), p11. ECP #1-2 'CONTROL PANEL TO ROOM TEMP SENSOR - WIRE TO CONTROL BOARD. INSTALL SENSOR IN ROOM AWAY FROM HEAT SOURCES. DO NOT INSTALL SENSOR ON THE CEILING GRID', under 'Responsibility: Electrician'; description: 'Room temperature sensor shipped loose for field installation.' Duct sensors T2/T3 are factory wired (not taken). 1 counted. (Model line id L-0151.)
CaptiveAire electrical package job 6912904 (DCV-2111, ECP #1-1..#1-4), p11. ECP #1-2 'CONTROL PANEL TO WORLD WIDE WEB - CAT-5 ETHERNET CONNECTION ... WIRE DIRECTLY TO COMMUNICATION ROUTER', under 'CONTROL PANEL TO ACCESSORY ITEMS - Responsibility: Electrician'. 1 counted. Conflicts with E1.1 (LVC provides cable) -- see coverage gap. (Model line id L-0152.) The model also raised 'lv-cable-party-conflict', which the contract has no flag for; recorded here rather than dropped.
CaptiveAire electrical package job 6912904 (DCV-2111, ECP #1-1..#1-4), p11. ECP #1-1 'SUP-3 MAKE UP AIR ... FAN START SIGNAL TO MUA BOARD *WIRE TO UNIT INTERLOCK' 24VAC SFO1/SFC1; damper interlock 'NOT REQUIRED FOR ALL UNITS. SEE MAKE-UP AIR SCHEMATIC.' 1 counted. (Model line id L-0153.)
CaptiveAire ECP #1-8 (Core Fire Protection) component list: 'PN: PS-01 Station STI-SS2431 Remote Puill/Push FOR SHIPMENT' wired into the J10 manual actuation loop (MAD-01, 'Multiple manual actuation possible'); one station listed for Fire System #1 (FS-1 MASTER). Counted 1 backbox + stub; LV loop wire (Belden 6320UL) is not measurable on this schematic. (Model line id L-0154.)
CaptiveAire ECP #1-6 / #1-7 description of operation: 'Demand Control Ventilation ... Fans modulate based on duct temperature ... Room temperature sensor shipped loose for field installation.' Counted 1 sensor position (one DCV system, job 6912904). Location not on this sheet; E sheets show no sensor box. (Model line id L-0155.)
Sheet 13 HMI detail: 'MOUNTS IN STANDARD DOUBLE GANG JUNCTION BOX', 'CAT-5 CONNECTION ON REVERSE. CONNECTED TO HOOD CONTROL PANEL.' and 'NOTE: MOUNT HMI TO STANDARD DOUBLE GANG WALL JBOX'; the Typical Hood Control Panel Installation draws one LCD INTERFACE per control panel, and E3.0 KN14 shows one hood control panel. The HMI device is CaptiveAire-furnished; the sheet does not name who sets the box. Carried as EC box + 3/4" stub (job LV rough-in rule, E1.0 LV legend). Location of the wall box is not on this sheet. (Model line id L-0156.) The model also raised 'est-review', 'responsibility assumed', which the contract has no flag for; recorded here rather than dropped.
Sheet 13 'Room Override Thermostat' detail: 'Provides room override based on temperature differential between the room and duct. Installed by electrician on a wall, 5'-6' off the finished floor, in the space but not directly under the hood or close to an appliance (including the electrical control box)'. The Typical Hood Control Panel Installation draws one ROOM TEMPERATURE SENSOR wired to the control panel. Count 1 (one hood control panel, E3.0 KN14). (Model line id L-0157.) The model also raised 'est-review', which the contract has no flag for; recorded here rather than dropped.
A2.1 EQUIPMENT SCHEDULE row S-925 '500 LB ICE MACHINE', Osion OCM-500, QTY 1: ELEC X, PHASE 1, AMP 4.33, VOLTS 115, WATTS 520W. E3.0 tags no S-925, so the connection is counted here: 1 receptacle, GFCI per E1.0 GN24 ('ALL KITCHEN EQUIPMENT SHALL HAVE READILY ACCESSIBLE GFCI PROTECTION'). Plug type not scheduled; 20A 5-20R assumed. Circuit/home run not taken off (no panel circuit named). (Model line id L-0159.) The model also raised 'location not drawn on E sheets', 'plug type assumed 5-20R', which the contract has no flag for; recorded here rather than dropped.
M5.1 FAN OPTIONS, fan unit 3 (MUA A2-D.500-20D), qty 1: 'SEPARATE 120V WIRING PACKAGE (REQUIRED AND USED ONLY FOR DCV OR PREWIRE WITH VFD) - THREE PHASE ONLY'. The E4.0 panel L schedule gives SF-1 only L-13/15/17 (3-pole); no 120V circuit to the MUA is scheduled. One control circuit counted; length and source circuit to be set by the estimator (roof run from the panel or from the hood control panel). (Model line id L-0166.) The model also raised 'not on E sheets - confirm with CaptiveAire/engineer', 'length not measured', which the contract has no flag for; recorded here rather than dropped.
Hood Information schedule row HOOD NO 2: 5430VHB-ND, 5'-0", LIGHT(S) QTY 2 'RECESSED ROUND', no utility cabinet, no fire system, no switches; row 1 carries 'DCV-2111' and '1 LIGHT / 1 FAN'. Plan View - Hood #2 draws the 2 lights on one strip. Counted 1 hood needing a light connection beyond Hood #1 (sheet 11 line 'HOOD LIGHT CIRCUIT ... TO J-BOX ON TOP OF HOOD', qty 1). Strike if E3.0 already feeds Hood #2 lights by its own J-box. (Model line id L-0167.) The model also raised 'est-review', which the contract has no flag for; recorded here rather than dropped.
PLYWOOD BACKBOARD 4' x 8' x 3/4" FIRE-RATED, PAINTED, AT TELECOM / LV LOCATION Backboard for the low-voltage rough-in (data, camera, speaker, WAP backboxes) | 1 ea | E3.2 |
EQUIPMENT CONNECTION, ROOF UNIT (disconnect to unit, 3/4" liquidtight flex whip) Final connection disconnect-to-unit at RTU-1, RTU-2, SF-1, EF-1, EF-2 | 0 ea | E3.1 |
DUCT SMOKE DETECTOR, DUCT-MOUNTED W/ SAMPLING TUBE AND HOUSING (EC FURNISH & WIRE, MC INSTALL IN DUCT) Duct smoke detector for RTU-1 supply/return, furnished and wired by EC, installed by mechanical contractor, per M0.2 Smoke Detector section. | 0 ea | 004-Copy-of-S_CaptvieAire-208V_pdf-p3 |
DUCT SMOKE DETECTOR REMOTE ALARM INDICATOR / KEY TEST STATION, 1-GANG, W/ 4" SQ BOX + 3/4" EMT STUB 12 FT Remote alarm indicator for the duct smoke detector, EC-furnished and wired per M0.2. | 0 ea | 004-Copy-of-S_CaptvieAire-208V_pdf-p3 |
| In play for PANELBOARD 400A MCB 208Y/120V 3PH 4W 42-CKT NEMA 1 SURFACE, 10kAIC; PANELBOARD 225A MLO 208Y/120V 3PH 4W 60-CKT NEMA 1 SURFACE, 10kAIC; PANELBOARD 225A MLO 208Y/120V 3PH 4W 30-CKT NEMA 1 SURFACE, 10kAIC. Nothing on the takeoff shows it. |
| RRE carries a panel directory update where circuits land in an existing panel. |
NEC 2023 210.8(B)(2) GFCI on commercial kitchen receptacles | shown | GFCI protection for every receptacle in a commercial kitchen: single-phase up to 50 A and three-phase up to 100 A, 150 V to ground or less. | In play for GFCI DUPLEX RECEPTACLE 20A 125V (kitchen equipment, GN24); SPECIAL PURPOSE RECEPTACLE 208V (kitchen equipment, NEMA per equipment, GFCI per GN24); DOUBLE DUPLEX GFCI RECEPTACLE 20A 125V NEMA 5-20R (2 GFCI DUPLEX, 2-GANG) STAINLESS PLATE. Shown: GFCI DUPLEX RECEPTACLE 20A 125V (kitchen equipment, GN24); SPECIAL PURPOSE RECEPTACLE 208V (kitchen equipment, NEMA per equipment, GFCI per GN24); DOUBLE DUPLEX GFCI RECEPTACLE 20A 125V NEMA 5-20R (2 GFCI DUPLEX, 2-GANG) STAINLESS PLATE. | RRE carries a GFCI receptacle at the device where the set calls for GFCI, and adds none on code alone (Mango: no GFCI bid; The Melt: 25 where the set said so). |
NEC 2023 210.8(B)(1) GFCI on bathroom receptacles | shown | GFCI protection for every receptacle in a bathroom: single-phase up to 50 A and three-phase up to 100 A, 150 V to ground or less. | In play for GFCI DUPLEX RECEPTACLE 20A 125V +42" (restrooms, 'GFI'). Shown: GFCI DUPLEX RECEPTACLE 20A 125V +42" (restrooms, 'GFI'). | RRE carries GFCI at the device where the set calls for it. |
NEC 2023 210.63(A) Service receptacle at HVAC equipment | shown | A 125-volt, 15- or 20-ampere receptacle on the same level and within 25 ft of heating, air-conditioning and refrigeration equipment, not on the load side of the equipment disconnect. | In play for 3/4" EMT CONDUIT (ROOF EQUIPMENT HOMERUNS); #10 THHN CU; #1/0 THHN CU; and 16 more. Shown: #10 THHN CU; 3/4" EMT CONDUIT (ROOF EQUIPMENT HOMERUNS); GFCI DUPLEX RECEPTACLE 20A 125V (kitchen equipment, GN24); and 2 more. | RRE carries the roof receptacle where the set draws one (reading check 11). |
NEC 2023 300.11, 410.36(B) Support in suspended ceilings | shown | Raceways, cables and boxes above a suspended ceiling are supported independently of the ceiling grid, or by identified support wires; lay-in luminaires are fastened to the grid framing. | In play for LAY-IN LIGHT FIXTURE SUPPORT WIRE, 12 GA GALVANIZED, TAUT HANGER AT EACH FIXTURE CORNER TO STRUCTURE ABOVE (2X4 TROFFER R3/R3EM); LAY-IN LIGHT FIXTURE SLACK SAFETY WIRE, 12 GA GALVANIZED, DIAGONALLY OPPOSITE CORNERS TO STRUCTURE ABOVE (2X4 TROFFER R3/R3EM); LIGHT FIXTURE TYPE R3 - 2X4 RECESSED LED TROFFER (LITHONIA STAKP); and 2 more. Shown: LAY-IN LIGHT FIXTURE SUPPORT WIRE, 12 GA GALVANIZED, TAUT HANGER AT EACH FIXTURE CORNER TO STRUCTURE ABOVE (2X4 TROFFER R3/R3EM); LAY-IN LIGHT FIXTURE SLACK SAFETY WIRE, 12 GA GALVANIZED, DIAGONALLY OPPOSITE CORNERS TO STRUCTURE ABOVE (2X4 TROFFER R3/R3EM). | RRE carries the fixture support wire as its own item where the ceiling is a grid. |
NEC 2023 440.14 Disconnect within sight of HVAC equipment | shown | A disconnecting means within sight from, and readily accessible from, air-conditioning and refrigerating equipment. It may be on or in the unit. | In play for 3/4" EMT CONDUIT (ROOF EQUIPMENT HOMERUNS); #10 THHN CU; #1/0 THHN CU; and 16 more. Shown: 1-1/2" EMT CONDUIT (RTU-1 FEEDER 3#1/0 + #6G); VFD MOTOR LOAD CIRCUIT, HOOD CONTROL PANEL TO FAN DISCONNECT, 3 CONDUCTORS + GROUND 208V 3PH, DEDICATED CONDUIT EACH (EXH-1/EF-1, SUP-3/SF-1); DISCONNECT SWITCH 200A 3P 240V FUSED, 150A FUSES, NEMA 3R, HEAVY DUTY (RTU-1); and 4 more. | RRE priced this on 5 of 5 past jobs (100%). RRE carries a disconnect at every unit with a disconnect symbol or note, sized from its circuit. |
NEC 2023 422.31, 424.19, 430.102 Disconnect for water heaters, heaters, fans and motor loads | shown | A disconnect within sight of the appliance, heater or motor, or a branch-circuit breaker that can be locked in the open position. | In play for #10 THHN CU; 3/4" EMT CONDUIT (ROOF EQUIPMENT HOMERUNS); MOTOR RATED SWITCH ($M) (restroom exhaust fans EF-3/EF-4, A-44); and 10 more. Shown: VFD MOTOR LOAD CIRCUIT, HOOD CONTROL PANEL TO FAN DISCONNECT, 3 CONDUCTORS + GROUND 208V 3PH, DEDICATED CONDUIT EACH (EXH-1/EF-1, SUP-3/SF-1); DISCONNECT SWITCH 30A 3P 240V FUSED, 15A FUSES, NEMA 3R, HEAVY DUTY (EF-1 (CaptiveAire EXH-1)); DISCONNECT SWITCH 30A 3P 240V FUSED, 15A FUSES, NEMA 3R, HEAVY DUTY (SF-1 (CaptiveAire SUP-3 / MUA fan 3)); and 1 more. | A lockable breaker answers it as well as a switch: check the panel schedule before adding a disconnect. |
NEC 2023 600.5(A) Sign outlet at each tenant entrance | shown | At least one outlet at each entrance to each tenant space accessible to pedestrians, for a sign, on a 20-ampere branch circuit that supplies no other load. | Shown: JUNCTION BOX 4" SQ WITH CONNECTION (hard-wired equipment / signage / hood); DISCONNECT SWITCH 30A 1P NON-FUSED, NEMA 1, SIGN (INTERIOR) WITH J-BOX; DISCONNECT SWITCH 30A 1P NON-FUSED, NEMA 1, SIGN (EXTERIOR SIGN, INSIDE FACE OF WALL) WITH J-BOX. | RRE prices "power to building signage" where the set shows it; the matrix row is left blank where it does not. |
NEC 2023 600.6 Disconnect within sight of a sign | shown | Each sign or outline lighting system, or its feeder, has an externally operable disconnect within sight of the sign, or one capable of being locked in the open position. | In play for JUNCTION BOX 4" SQ WITH CONNECTION (hard-wired equipment / signage / hood); DISCONNECT SWITCH 30A 1P NON-FUSED, NEMA 1, SIGN (INTERIOR) WITH J-BOX; DISCONNECT SWITCH 30A 1P NON-FUSED, NEMA 1, SIGN (EXTERIOR SIGN, INSIDE FACE OF WALL) WITH J-BOX. Shown: 1-1/2" EMT CONDUIT (RTU-1 FEEDER 3#1/0 + #6G); PANEL SAFE-OFF; DISCONNECT SWITCH 30A 1P NON-FUSED, NEMA 1, SIGN (INTERIOR) WITH J-BOX; and 8 more. | RRE prices a WP switch at signage as a fused disconnect assembly (firm practice wp_switch_mapping). |
NEC 2023 Chapter 9 Table 1, 358.22 Conduit fill | shown | Over two conductors, a raceway is filled to no more than 40 % of its internal area (Chapter 9 Tables 1, 4 and 5; THHN conductors, EMT). | All 3 callouts naming conductors and conduit are within it. | — |
A takeoff cannot settle every article: load calculations and coordination are the engineer of record’s, and workmanship is the inspector’s. Each is listed so nothing is silently skipped. “Waiting on a code read” means the article is in play and this job’s drawing read has not been checked against the code yet: re-run the read, or check it on the drawings.
| 90 | Introduction | general | Scope and definitions: nothing to check on a job. |
| 100 | Definitions | general | Scope and definitions: nothing to check on a job. |
| 110 | Requirements for Electrical Installations | to check | 1 section checked against the takeoff, 1 to check: 110.16. |
| 200 | Use and Identification of Grounded Conductors | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 210 | Branch Circuits | to check | 4 sections checked against the takeoff, 1 to check: 210.8(B), 406.9(B). |
| 215 | Feeders | checked | In play; none of its checked sections applies to these lines. |
| 220 | Branch-Circuit, Feeder, and Service Load Calculations | design | The engineer of record’s: sizing, calculation or coordination, not checked against a takeoff. |
| 225 | Outside Branch Circuits and Feeders | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 230 | Services | checked | In play; none of its checked sections applies to these lines. |
| 235 | Branch Circuits, Feeders, and Services Over 1000 Volts ac, 1500 Volts dc | not in play | Nothing on this takeoff puts it in play. |
| 240 | Overcurrent Protection | checked | In play; none of its checked sections applies to these lines. |
| 242 | Overvoltage Protection | not in play | Nothing on this takeoff puts it in play. |
| 245 | Overcurrent Protection for Systems Rated Over 1000 Volts ac, 1500 Volts dc | not in play | Nothing on this takeoff puts it in play. |
| 250 | Grounding and Bonding | checked | In play; none of its checked sections applies to these lines. |
| 300 | General Requirements for Wiring Methods and Materials | checked | 1 section checked against the takeoff, all shown. |
| 305 | General Requirements for Wiring Methods and Materials for Systems Rated Over 1000 Volts ac, 1500 Volts dc | not in play | Nothing on this takeoff puts it in play. |
| 310 | Conductors for General Wiring | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 312 | Cabinets, Cutout Boxes, and Meter Socket Enclosures | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 314 | Outlet, Device, Pull, and Junction Boxes; Conduit Bodies; Fittings; and Handhole Enclosures | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 315 | Medium Voltage Conductors, Cable, Cable Joints, and Cable Terminations | not in play | Nothing on this takeoff puts it in play. |
| 320 | Armored Cable: Type AC | not in play | Nothing on this takeoff puts it in play. |
| 322 | Flat Cable Assemblies: Type FC | not in play | Nothing on this takeoff puts it in play. |
| 324 | Flat Conductor Cable: Type FCC | not in play |
| 400 | Flexible Cords and Flexible Cables | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 402 | Fixture Wires | not in play | Nothing on this takeoff puts it in play. |
| 404 | Switches | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 406 | Receptacles, Cord Connectors, and Attachment Plugs (Caps) | checked | In play; none of its checked sections applies to these lines. |
| 408 | Switchboards, Switchgear, and Panelboards | to check | 1 section checked against the takeoff, 1 to check: 408.4(A). |
| 409 | Industrial Control Panels | not in play | Nothing on this takeoff puts it in play. |
| 410 | Luminaires, Lampholders, and Lamps | checked | In play; none of its checked sections applies to these lines. |
| 411 | Low-Voltage Lighting | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 422 | Appliances | checked | 1 section checked against the takeoff, all shown. |
| 424 | Fixed Electric Space-Heating Equipment |
| 500 | Hazardous (Classified) Locations, Classes I, II, and III, Divisions 1 and 2 | not in play | Nothing on this takeoff puts it in play. |
| 501 | Class I Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 502 | Class II Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 503 | Class III Hazardous (Classified) Locations | not in play | Nothing on this takeoff puts it in play. |
| 504 | Intrinsically Safe Systems | not in play | Nothing on this takeoff puts it in play. |
| 505 | Zone 0, 1, and 2 Locations | not in play | Nothing on this takeoff puts it in play. |
| 506 | Zone 20, 21, and 22 Locations for Combustible Dusts or Ignitible Fibers/Flyings | not in play | Nothing on this takeoff puts it in play. |
| 510 | Hazardous (Classified) Locations — Specific | not in play | Nothing on this takeoff puts it in play. |
| 511 | Commercial Garages, Repair and Storage | not in play | Nothing on this takeoff puts it in play. |
| 513 | Aircraft Hangars | not in play |
| 600 | Electric Signs and Outline Lighting | checked | 2 sections checked against the takeoff, all shown. |
| 604 | Manufactured Wiring Systems | not in play | Nothing on this takeoff puts it in play. |
| 605 | Office Furnishings | not in play | Nothing on this takeoff puts it in play. |
| 610 | Cranes and Hoists | not in play | Nothing on this takeoff puts it in play. |
| 620 | Elevators, Dumbwaiters, Escalators, Moving Walks, Platform Lifts, and Stairway Chairlifts | not in play | Nothing on this takeoff puts it in play. |
| 625 | Electric Vehicle Power Transfer System | not in play | Nothing on this takeoff puts it in play. |
| 626 | Electrified Truck Parking Spaces | not in play | Nothing on this takeoff puts it in play. |
| 630 | Electric Welders | not in play | Nothing on this takeoff puts it in play. |
| 640 | Audio Signal Processing, Amplification, and Reproduction Equipment | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 645 | Information Technology Equipment |
| 700 | Emergency Systems | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 701 | Legally Required Standby Systems | not in play | Nothing on this takeoff puts it in play. |
| 702 | Optional Standby Systems | not in play | Nothing on this takeoff puts it in play. |
| 705 | Interconnected Electric Power Production Sources | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 706 | Energy Storage Systems | not in play | Nothing on this takeoff puts it in play. |
| 708 | Critical Operations Power Systems (COPS) | not in play | Nothing on this takeoff puts it in play. |
| 710 | Stand-Alone Systems | not in play | Nothing on this takeoff puts it in play. |
| 712 | Direct Current Microgrids | not in play | Nothing on this takeoff puts it in play. |
| 722 | Cables for Power-Limited Circuits and Fault-Managed Power Circuits | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 724 | Class 1 Power-Limited Circuits and Class 1 Power-Limited Remote-Control and Signaling Circuits |
| 800 | General Requirements for Communications Systems | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 805 | Communications Circuits | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 810 | Radio and Television Antenna Equipment | not in play | Nothing on this takeoff puts it in play. |
| 820 | Community Antenna Television and Radio Distribution Systems | not in play | Nothing on this takeoff puts it in play. |
| 830 | Network-Powered Broadband Communications Systems | not in play | Nothing on this takeoff puts it in play. |
| 840 | Premises-Powered Broadband Communications Systems | not in play | Nothing on this takeoff puts it in play. |
| Ch. 9 | Tables: conduit fill, conductor properties, power-limited sources | checked | 1 section checked against the takeoff, all shown. |
| LED PENDANT MOUNTED LA |
| 5.5 ft |
| E2.0 |
LIGHT FIXTURE TYPE R1E - 6" ROUND RECESSED LED DOWNLIGHT W/ REMOTE EMERGENCY BATTERY (ALPHABET NBU4) R1E, BOH, A-3,h | LED EMERGENCYLIGHT DUAL | 5 ea | E2.0 |
TRACK HEAD TYPE T1 - TRACK WALL WASH (LUMENTURE TWW160) T1 heads on banquette TR run | LED TRACK SPOT FIXTURE | 5 ea | E2.0 |
EMERGENCY LIGHTING INVERTER BODINE ELI-S-20, 20VA 120V, 90-MIN NICD, CEILING MOUNT Inverter #1 and #2 (restrooms) | LED EMERGENCYLIGHT DUAL | 2 ea | E2.0 |
| Line | Needs a price for | Count | Sheet |
|---|---|---|---|
PANELBOARD 400A MCB 208Y/120V 3PH 4W 42-CKT NEMA 1 SURFACE, 10kAIC Panel L (new), BOH | 400/42 120/208V PNL 3PH | 1 ea | E4.0 |
PANELBOARD 225A MLO 208Y/120V 3PH 4W 60-CKT NEMA 1 SURFACE, 10kAIC Panel A (new), BOH | 225/36 120/208V PNL 3PH | 1 ea | E4.0 |
PANELBOARD 225A MLO 208Y/120V 3PH 4W 30-CKT NEMA 1 SURFACE, 10kAIC Panel B (new), BOH | 225/36 120/208V PNL 3PH | 1 ea | E4.0 |
Read off the schedules and notes. RRE buys none of the material named here. Check each against the responsibility matrix on the proposal: these are what it should say is by others.
| Line | Furnished by | Installed by | RRE’s part | Sheet |
|---|---|---|---|---|
3/4" EMT CONDUIT STUB TO ACCESSIBLE CEILING (low-voltage rough-in, empty w/ pull string) RRE carries the line; the read says “wiring by others”. | Others | not stated | RRE carries it; a part is by others | E3.2 |
CAMERA BACKBOX 4" SQ (rough-in only, camera + cable by others) The drawings say “by others”. | Others | Others | Not RRE’s: furnished and installed by others | E3.2 |
SPEAKER BACKBOX 4" SQ (rough-in only, speaker + cable by others) The drawings say “by others”. | Others | Others | Not RRE’s: furnished and installed by others | E3.2 |
ELECTRIC GAS SHUTOFF VALVE 2" (CAPTIVEAIRE 'SC ELECTRICAL', FURNISHED BY CAPTIVEAIRE, SET BY PLUMBER) - EC 120V CONNECTION + FLEX WHIP FROM HOOD CONTROL PANEL The drawings say “furnished by captiveaire”. | CAPTIVEAIRE | not stated | RRE installs / connects only | 004-Copy-of-S_CaptvieAire-208V_pdf-p3 |
FEEDER TERMINATION 400A 3PH 4W, (4)500 KCMIL + #3G The drawings say “landlord-furnished”. | Landlord | not stated | RRE installs / connects only | E4.0 |
| Nothing on this takeoff puts it in play. |
| 326 | Integrated Gas Spacer Cable: Type IGS | not in play | Nothing on this takeoff puts it in play. |
| 330 | Metal-Clad Cable: Type MC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 332 | Mineral-Insulated, Metal-Sheathed Cable: Type MI | not in play | Nothing on this takeoff puts it in play. |
| 334 | Nonmetallic-Sheathed Cable: Types NM and NMC | not in play | Nothing on this takeoff puts it in play. |
| 335 | Instrumentation Tray Cable: Type ITC | not in play | Nothing on this takeoff puts it in play. |
| 336 | Power and Control Tray Cable: Type TC | not in play | Nothing on this takeoff puts it in play. |
| 337 | Type P Cable | not in play | Nothing on this takeoff puts it in play. |
| 338 | Service-Entrance Cable: Types SE and USE | not in play | Nothing on this takeoff puts it in play. |
| 340 | Underground Feeder and Branch-Circuit Cable: Type UF | not in play | Nothing on this takeoff puts it in play. |
| 342 | Intermediate Metal Conduit: Type IMC | not in play | Nothing on this takeoff puts it in play. |
| 344 | Rigid Metal Conduit: Type RMC | not in play | Nothing on this takeoff puts it in play. |
| 348 | Flexible Metal Conduit: Type FMC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 350 | Liquidtight Flexible Metal Conduit: Type LFMC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 352 | Rigid Polyvinyl Chloride Conduit: Type PVC | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 353 | High Density Polyethylene Conduit: Type HDPE Conduit | not in play | Nothing on this takeoff puts it in play. |
| 354 | Nonmetallic Underground Conduit with Conductors: Type NUCC | not in play | Nothing on this takeoff puts it in play. |
| 355 | Reinforced Thermosetting Resin Conduit: Type RTRC | not in play | Nothing on this takeoff puts it in play. |
| 356 | Liquidtight Flexible Nonmetallic Conduit: Type LFNC | not in play | Nothing on this takeoff puts it in play. |
| 358 | Electrical Metallic Tubing: Type EMT | checked | In play; none of its checked sections applies to these lines. |
| 360 | Flexible Metallic Tubing: Type FMT | not in play | Nothing on this takeoff puts it in play. |
| 362 | Electrical Nonmetallic Tubing: Type ENT | not in play | Nothing on this takeoff puts it in play. |
| 366 | Auxiliary Gutters | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 368 | Busways | not in play | Nothing on this takeoff puts it in play. |
| 369 | Insulated Bus Pipe (IBP)/Tubular Covered Conductors (TCC) Systems | not in play | Nothing on this takeoff puts it in play. |
| 370 | Cablebus | not in play | Nothing on this takeoff puts it in play. |
| 371 | Flexible Bus Systems | not in play | Nothing on this takeoff puts it in play. |
| 372 | Cellular Concrete Floor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 374 | Cellular Metal Floor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 376 | Metal Wireways | not in play | Nothing on this takeoff puts it in play. |
| 378 | Nonmetallic Wireways | not in play | Nothing on this takeoff puts it in play. |
| 380 | Multioutlet Assembly | not in play | Nothing on this takeoff puts it in play. |
| 382 | Nonmetallic Extensions | not in play | Nothing on this takeoff puts it in play. |
| 384 | Strut-Type Channel Raceway | not in play | Nothing on this takeoff puts it in play. |
| 386 | Surface Metal Raceways | not in play | Nothing on this takeoff puts it in play. |
| 388 | Surface Nonmetallic Raceways | not in play | Nothing on this takeoff puts it in play. |
| 390 | Underfloor Raceways | not in play | Nothing on this takeoff puts it in play. |
| 392 | Cable Trays | not in play | Nothing on this takeoff puts it in play. |
| 393 | Low-Voltage Suspended Ceiling Power Distribution Systems | not in play | Nothing on this takeoff puts it in play. |
| 394 | Concealed Knob-and-Tube Wiring | not in play | Nothing on this takeoff puts it in play. |
| 395 | Outdoor Overhead Conductors over 1000 Volts | not in play | Nothing on this takeoff puts it in play. |
| 396 | Messenger-Supported Wiring | not in play | Nothing on this takeoff puts it in play. |
| 398 | Open Wiring on Insulators | not in play | Nothing on this takeoff puts it in play. |
| not in play |
| Nothing on this takeoff puts it in play. |
| 425 | Fixed Resistance and Electrode Industrial Process Heating Equipment | not in play | Nothing on this takeoff puts it in play. |
| 426 | Fixed Outdoor Electric Deicing and Snow-Melting Equipment | not in play | Nothing on this takeoff puts it in play. |
| 427 | Fixed Electric Heating Equipment for Pipelines and Vessels | not in play | Nothing on this takeoff puts it in play. |
| 430 | Motors, Motor Circuits, and Controllers | checked | In play; none of its checked sections applies to these lines. |
| 440 | Air-Conditioning and Refrigerating Equipment | checked | 1 section checked against the takeoff, all shown. |
| 445 | Generators | not in play | Nothing on this takeoff puts it in play. |
| 450 | Transformers and Transformer Vaults (Including Secondary Ties) | checked | In play; none of its checked sections applies to these lines. |
| 455 | Phase Converters | not in play | Nothing on this takeoff puts it in play. |
| 460 | Capacitors | not in play | Nothing on this takeoff puts it in play. |
| 470 | Resistors and Reactors | not in play | Nothing on this takeoff puts it in play. |
| 480 | Stationary Standby Batteries | not in play | Nothing on this takeoff puts it in play. |
| 490 | Equipment Over 1000 Volts, Nominal | not in play | Nothing on this takeoff puts it in play. |
| Nothing on this takeoff puts it in play. |
| 514 | Motor Fuel Dispensing Facilities | not in play | Nothing on this takeoff puts it in play. |
| 515 | Bulk Storage Plants | not in play | Nothing on this takeoff puts it in play. |
| 516 | Spray Application, Dipping, Coating, and Printing Processes | not in play | Nothing on this takeoff puts it in play. |
| 517 | Health Care Facilities | not in play | Nothing on this takeoff puts it in play. |
| 518 | Assembly Occupancies | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 520 | Theaters, Audience Areas of Motion Picture and Television Studios, Performance Areas, and Similar Locations | not in play | Nothing on this takeoff puts it in play. |
| 522 | Control Systems for Permanent Amusement Attractions | not in play | Nothing on this takeoff puts it in play. |
| 525 | Carnivals, Circuses, Fairs, and Similar Events | not in play | Nothing on this takeoff puts it in play. |
| 530 | Motion Picture and Television Studios and Similar Locations | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 540 | Motion Picture Projection Rooms | not in play | Nothing on this takeoff puts it in play. |
| 545 | Manufactured Buildings and Relocatable Structures | not in play | Nothing on this takeoff puts it in play. |
| 547 | Agricultural Buildings | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 550 | Mobile Homes, Manufactured Homes, and Mobile Home Parks | not in play | Nothing on this takeoff puts it in play. |
| 551 | Recreational Vehicles and Recreational Vehicle Parks | not in play | Nothing on this takeoff puts it in play. |
| 552 | Park Trailers | not in play | Nothing on this takeoff puts it in play. |
| 555 | Marinas, Boatyards, Floating Buildings, and Commercial and Noncommercial Docking Facilities | not in play | Nothing on this takeoff puts it in play. |
| 590 | Temporary Installations | not in play | Nothing on this takeoff puts it in play. |
| Nothing on this takeoff puts it in play. |
| 646 | Modular Data Centers | not in play | Nothing on this takeoff puts it in play. |
| 647 | Sensitive Electronic Equipment | not in play | Nothing on this takeoff puts it in play. |
| 650 | Pipe Organs | not in play | Nothing on this takeoff puts it in play. |
| 660 | X-Ray Equipment | not in play | Nothing on this takeoff puts it in play. |
| 665 | Induction and Dielectric Heating Equipment | not in play | Nothing on this takeoff puts it in play. |
| 668 | Electrolytic Cells | not in play | Nothing on this takeoff puts it in play. |
| 669 | Electroplating | not in play | Nothing on this takeoff puts it in play. |
| 670 | Industrial Machinery | not in play | Nothing on this takeoff puts it in play. |
| 675 | Electrically Driven or Controlled Irrigation Machines | not in play | Nothing on this takeoff puts it in play. |
| 680 | Swimming Pools, Fountains, and Similar Installations | not in play | Nothing on this takeoff puts it in play. |
| 682 | Natural and Artificially Made Bodies of Water | not in play | Nothing on this takeoff puts it in play. |
| 685 | Integrated Electrical Systems | not in play | Nothing on this takeoff puts it in play. |
| 690 | Solar Photovoltaic (PV) Systems | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 691 | Large-Scale Photovoltaic (PV) Electric Supply Stations | not in play | Nothing on this takeoff puts it in play. |
| 692 | Fuel Cell Systems | not in play | Nothing on this takeoff puts it in play. |
| 694 | Wind Electric Systems | not in play | Nothing on this takeoff puts it in play. |
| 695 | Fire Pumps | not in play | Nothing on this takeoff puts it in play. |
| not in play |
| Nothing on this takeoff puts it in play. |
| 725 | Class 1, Class 2, and Class 3 Remote-Control, Signaling, and Power-Limited Circuits | not read yet | In play. This job’s read has no code pass yet: re-run the read, or check it on the drawings. |
| 726 | Class 4 (CL4) Fault-Managed Power Systems | not in play | Nothing on this takeoff puts it in play. |
| 728 | Fire-Resistive Cable Systems | not in play | Nothing on this takeoff puts it in play. |
| 750 | Energy Management Systems | not in play | Nothing on this takeoff puts it in play. |
| 760 | Fire Alarm Systems | checked | In play; none of its checked sections applies to these lines. |
| 770 | Optical Fiber Cables | not in play | Nothing on this takeoff puts it in play. |